E & OE  As our policy is one of continuous product development, we reserve the right to alter product details without prior notice

.       

Ei176 DataSht RevA

 

 
 

Model 

Ei176 Optical 

Placement Information 

 

 

 

         

       

 

 
 
Alarms should be placed in accordance with the general guidelines shown in 
the diagram above. These recommendations are based on the problem of  
areas of “dead air” close to corners of rooms and apexes of ceilings, which 
could result in the prevention of smoke reaching the smoke detector 
 
 

Important Precaution: 

Do not install the actual smoke/heat 
alarm itself in new or renovated 
buildings until all work is completed 
(including floor coverings) and the 
building has been fully cleaned. 
The wiring can be installed when 
appropriate. (Excessive dust and 
debris from building work can 
contaminate the smoke chamber 
and cause problems, and it will also 
invalidate the guarantee). If it must 
be installed, cover it completely, 
particularly around the edges, with 
a dust cover (eg. a plastic bag), 
until all cleaning is finished.. 
Connect wires to the unit as in 
wiring diagram. All wiring must 
comply with local codes. 
 
 

 

Technical Specification 

 

Sensor  

Optical, uses light scatter from 
smoke 

 

Sensitivity:

 

Complies with BS 5446 Part 1: 
2000 

 

Source: 

Contains no radioactive material 

 

Airspeed:

 

Essentially immune to the effect 

 

of airspeed. 

Ambient Light:

 

Chamber housing design and 
compensation overcomes 
problems with stray light 

 

Button Test:

 

Tests strobe, vibration pad and 
panel 

Fault Monitor: 

Open/short circuit 

 

 

Supply Voltage: 

230V AC standby 8mA, alarm 
40mA 

Battery back up: 

Sealed

 

Rechargeable lead acid 

battery  

Auxiliary socket:

 

Provides 12V/200mA in alarm

 

 

 

 

 
 

 

  

 

Power-On Indicator:

   Continuous green LED 

 

Alarm:  

Xenon tube strobe (1Hz) 

 

Temperature Range:

  0 to 40°C 

 

Humidity Range:

 

0% to 90% Relative Humidity 

 

Interconnect:

 

Up to 12 interconnected 
Ei100C/105C/103C smoke/heat 
alarms 

 

Fixing:

 

Screw fixings supplied 

 

Plastic material:

 

UL94VO flame retardant 

 
Warranty:

 

5 year (limited) warranty 

 

Approvals:

 

BS 415:1990 electrical safety

 

 
Specifications are subject to change 