background image

6 MSC‑1 

Installation & Operating Instructions

Manual Operation

The  power  to  any  one  of  the  snow‑melting  zones  may  be 

activated  manually  by  pressing  and  holding  the  ZONE  X 

button until the information below appears on the LCD screen. 

Manual  activation  will  only  work  as  long  as  the  ambient 

temperature is below the MSC‑1 shut‑off temperature. The 

duration  of  the  time  the  zone  will  remain  energized  (Time 

Delay) is pre‑set to 2.0 hours; this can be adjusted by following 

the programming instructions below.  

The minimum and maximum settings possible are noted on 

the LCD, adjustable in 0.5 hour increments.

Pressing UP increases the delay time.

Pressing DOWN decreases the delay time.

Press the SET button to accept the chosen delay time.

Once  the  delay  time  is  set,  the  MSC‑1  returns  to  normal 

control  function,  and  energizes  the  heating  equipment  for 

the selected zone.

To  de‑energize  the  manually  activated  heating  equipment, 

turn off using the toggle switch on the front panel.

When  operating  in  Mode  2  –  Priority,  the  manual  override 

works as described if no snow melting zones are energized. 

If any snow‑melting zone is energized the manual override 

only works to energize the higher priority zone, thereby de‑

energizing the lower priority zone.

It is important to note that manual operation is not possible if 

the MSC‑1 has already energized the zone, and that manual 

control will be overridden if the zone moisture sensor detects 

precipitation. 

LCD Explanation

    

Programming Instructions

The MSC‑1 program has been structured into 6 levels; within 

each  of  these  levels  are  further  degrees  of  selection.  Each 

programming step is clearly described on the LCD, and easily 

adjusted by the “UP”, “DOWN”, and “SET” buttons.

During programming:

· 

All  regular  operating  functions  of  the  MSC‑1  are 

suspended. 

· 

If a button is not pressed for approximately 90 seconds, 

the  program  will  return  to  normal  operation,  saving 

programming changes made up to the point exited. 

· 

Pressing  the  BACK  button  results  in  an  exit  from  the 

programming sequence, with the changes made up to 

that point saved.

Resetting to Factory Conditions

When the MSC‑1 is first energized, and during the time the 

initial LCD display (MSC Ver. X.X) screen shows push the UP 

and DOWN buttons simultaneously to access the option to 

revert to factory set conditions. Use the UP or DOWN button 

to select “yes” or “no”; the program accepts the selection and 

returns to normal operation. 
To begin programming the MSC‑1 hold the SET button down 

for 5 seconds. The display will start in program level 1. To 

move to other levels use the UP or DOWN buttons.

Level 1. Temperature Unit Selection

        

The default temperature units setting is°F.
To move to the next level use the UP or DOWN buttons. Press 

the SET button to select the temperature display units.

   

Pressing UP selects Degrees C.

Pressing DOWN selects Degrees F.

After  pressing  the  UP  or  DOWN  button,  the  program 

automatically accepts the selection and advances to the next 

program level. 

Level 2. Operating Mode Selection 

 

        

The default mode setting is Mode 1.

To move to the next level use the UP or DOWN buttons.

Press the SET button to select the operating mode.

Pressing UP selects Mode 1 (Independent).

Pressing DOWN selects Mode 2 (Priority).

After  pressing  the  UP  button  for  Mode  1,  the  program 

automatically accepts the selection and advances to the next 

program level.

After pressing the DOWN button for Mode 2, the program 

automatically accepts the selection and then moves to another 

input screen, as shown below. 

Temperature

at TS‑1 location

Temperature

Value & Units

°C or °F

Aerial or Gutter Sensor & ZONE

(only sensors activated will show)

A1=MSA‑1 or MSG‑1 ZONE 1

A2=MSA‑1 or MSG‑1 ZONE 2

A3=MSA‑1 or MSG‑1 ZONE 3

In‑ground Sensor & ZONE

(only sensors activated will show)

P1=MSP‑1 ZONE 1

P2=MSP‑1 ZONE 2

P3=MSP‑1 ZONE 3

M1= Mode 1 Independent

M2= Mode 2 Priority

Summary of Contents for EASYHEAT MSC-1

Page 1: ...ave a temperature sensor TS 1 in order to function a TS 1 is included with each MSC 1 The MSC 1 is housed in an enclosure NEMA 4 4X suitable for commercial industrial indoor applications and features...

Page 2: ...ot a do it your self product A qualified electrician must install the MSC 1 2 Completely read these instructions prior to any and all installations 3 If after carefully reading these instructions you...

Page 3: ...as noted ensure voltage and amperages are suitable for the contactor being used The MSC 1 will not function properly if the output connections are improperly made See Fig 4 10 The power supply is conn...

Page 4: ...med sensor In ground Sensor MSP 1 installed in ground to detect moisture and slab temperature theMSC 1mustbeprogrammed to recognize this sensor refer to the instruction manual for details TS 1 Termina...

Page 5: ...ne 1 re energized Similar logic applies for Zone 2 3 i e the lower numbered zone always takes priority The Priority mode available in the MSC 1 can reduce circuit loading by splitting up a large snow...

Page 6: ...approximately 90 seconds the program will return to normal operation saving programming changes made up to the point exited Pressing the BACK button results in an exit from the programming sequence w...

Page 7: ...t level use the UP or DOWN buttons Press the SET button to adjust the ambient off temperature the temperature above which the MSC 1 will no longer energize the heating equipment The minimum and maximu...

Page 8: ...o the terminal block then after a minimum10 seconds turn back on the power The MSC 1 program will recognize the sensor and begin normal operation 0 5 hour increments The minimum and maximum settings p...

Page 9: ...ossibly covered with sealant Turn on power using switch on front panel Check power supply If LED above power input terminal connection is not lit replace fuse 4A spare fuse supplied with MSC 1 NORMAL...

Page 10: ...System Memory Nonvolatile no data loss with a loss of system power Dimensions 11 wide cabinet 12 375 overall width X 10 25 high X 4 75 deep Certification UL Listed to US and Canadian safety standards...

Page 11: ...ons information representation of operating conditions or other data to Easy Heat in the selection or design of the Goods and the preparation of Easy Heat s quotation and in the event that actual oper...

Page 12: ...2 MSC 1 Installation Operating Instructions USA 2 Connecticut South Drive East Granby CT 06026 Tel 800 537 4732 Fax 888 324 2440 CANADA 99 Union St Elmira Ont N3B 3L7 Tel 519 669 2444 Fax 519 669 6419...

Reviews: