EGS Electrical Group • www.appletonelec.com • 800-621-1506
330086-000 Rev. J 4/15/10
Page 7
Maintenance
Electrical and mechanical inspection of all components must be performed regularly. It is recommended that
inspection be performed a minimum of once a year.
WARNING
If any parts of the plug, receptacle or cable connector
appear to be missing, broken or show signs of damage;
DISCONTINUE USE IMMEDIATELY!
This condition could cause serious/fatal personal injury
due to electrocution and/or equipment damage. Repair with
proper replacement part(s) before continuing service.
1. Inspect all contact wire terminals for tightness.
(Retorque). Discoloration due to excessive heat is
an indicator of possible problems and should be
thoroughly investigated and repaired as necessary.
2. Check grounding and bonding for correct installa-
tion and secure connection. (
Re-torque
)
3. Check gaskets for deterioration and replace if nec-
essary.
4. Clean exterior surfaces making sure nameplates
remain legible.
5. Inspect gland nut and cable grip tightness to ensure
proper cord/cable gripping.
6. Torque all screws as described in instructions
before re-using device.
7. Inspect housing parts and replace those which are
broken or excessively worn.
8. Check contacts for signs of excessive arcing or
burning and replace if necessary.
In addition to these required maintenance procedures,
we recommend an Electrical Preventive Maintenance
program as described in the National Fire Protection
Association Bulletin NFPA No. 70B.
ELECTRICAL RATING
Maximum Voltages: 600 VAC @ 50-400Hz, 250V
DC; Maximum continuous current: 30, 60, 100 or 150
Amperes.
Retain this Instruction Sheet for Future Reference
Replacement Parts Lists for Powertite “ADR” Receptacles
Housing not offered as a replacement part.
E
Insulator Block
Assembly
D
Gasket
C
Mounting Bolts
A
Spring Cover &
Ring
B
Threaded
Cover
F
Insulator Block
Retaining
G
Screws &
Washers
Item A
Item B
Item C
Item D
Item E
Item F
Item G
Ampacity
Style
Description
Spring Cover
& Ring
Threaded
Cover
Mounting
Bolts
Gasket
Contact Block
Assembly
Insulator Block
Retaining
Screws
Washers
30
1
2W 2P
PTSC30
PTTC30
69P05340000 69060871000
ARI-3022
69P05738000 69W05127000
1
3W 3P
PTSC30
PTTC30
69P05340000 69060871000
ARI-3033
69P05738000 69W05127000
1
4W 4P
PTSC30
PTTC30
69P05340000 69060871000
ARI-3044
69P05738000 69W05127000
2
2W 3P
PTSC30
PTTC30
69P05340000 69060871000
ARI-3023
69P05738000 69W05127000
2
3W 4P
PTSC30
PTTC30
69P05340000 69060871000
ARI-3034
69P05738000 69W05127000
60
1
2W 2P
PTSC60A
PTTC60A
69P07311000 69060567000
ARI-6022
69P05738000 69W05127000
1
3W 3P
PTSC60A
PTTC60A
69P07311000 69060567000
ARI-6033
69P05738000 69W05127000
1
4W 4P
PTSC60B
PTTC60B
69P07311000 69060567000
ARI-6044
69P05738000 69W05127000
2
2W 3P
PTSC60A
PTTC60A
69P07311000 69060567000
ARI-6023
69P05738000 69W05127000
2
3W 4P
PTSC60B
PTTC60B
69P07311000 69060567000
ARI-6034
69P05738000 69W05127000
100
1
2W 2P
PTSC100A
PTTC100A
69P07311000 69060567000
ARI-1022
69P05738000 69W05127000
1
3W 3P
PTSC100A
PTTC100A
69P07311000 69060567000
ARI-1033
69P05738000 69W05127000
1
4W 4P
PTSC100B
PTTC100B
69P07311000 69060567000
ARI-1044
69P05738000 69W05127000
2
2W 3P
PTSC100A
PTTC100A
69P07311000 69060567000
ARI-1023
69P05738000 69W05127000
2
3W 4P
PTSC100B
PTTC100B
69P07311000 69060567000
ARI-1034
69P05738000 69W05127000
150
2
3W4P
PTSC100B
PTTC100B
69P07311000 69060567000
ARI-15034
69P05738000 69W05127000
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com