5.
WARNING: Make sure that specific warnings and cautions in Chapter 2 “Precautions” are carefully read, understood and applied!
INSTALLATION
This section describes how to install the unit correctly.
The unit must be installed according to these instructions.
Unpacking
Verify that the unit (and eventual accessories) delivered is according to order before starting the installation. Any discrepancies from the ordered
equipment must be reported to the supplier.
Where/how to install
•
VIGO units work best when installed inside the bulding envelope, due to the VIGO’s insulated construction they can be installed
in loft spaces and outbuildings.
•
Mount the unit on flat surface (wall).
•
The unit must always be installed vertically.
•
It’s important that the unit is completely leveled before it is put into operation.
•
Place the unit preferably in a separate room (e.g. storage, laundry room or similar).
•
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspection doors should
be easily accessible.
•
Leave free space for opening the removable panels and for removal of the main components (page 3).
•
The outdoor air grilles if possible be put in the northern or eastern side of the building and away from other exhaust outlets like
kitchen fan exhausts or laundry room outlets.
Installation
The unit must be installed in the following position.
It is important that the unit is vertical in order for the condensation drainage to work properly.
5b
5a
Spirit level
Spacers
x2