EFOY-MASTERVOLT CABLE                                                SCHEME / SETTINGS / SPECIFICATIONS 

 

SCHEME 

        
 

                                                                                          

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 2: Installation scheme of the EFOY-MASTERVOLT cable, this is not a complete system  

 

MASTERBUS SETTINGS 

MasterBus settings must be done on the Multipurpose Contact output (MPC) and the MasterShunt (for Gel batteries) or the MLi Ultra batteries.  

For the Masterbus settings we refer to the Mastershunt (for Gel batteries) or the MLI Ultra battery user manual.    

The percentages below are recommended values for the use of the EFOY fuel cell in combination with MASTERVOLT batteries.  

 

Multipurpose contact settings 

 

 

 

Device name 

MPC Fuel cell 

 

 

1 second pulse option 

On (checked) 

 

 

 

 

 

 

Alarm setpoints 

 

MasterShunt (for Gel battery up to 200Ah) 

MLi 12/2500 or MLi12/5000 

 

Battery pre low 

50%    (fuel cell is switched On) 

40%    (fuel cell is switched On) 

 

Battery low 

40%    (inverter is switched Off) 

20%    (battery is disconnected) 

 

Battery full 

80%    (100 % by battery charger only) 

90%    (to avoid triggering stop charge event) 

 

 

 

 

 

Events for Gel (MasterShunt) or MLi Ultra batteries

 

 

 

Event Source 

Event Target 

Event Command 

Event Data 

Battery pre low 

MPC Fuel cell

 

Activate 

On 

Battery low (for Gel batteries) 

Mass Combi 

Inverter 

Off 

Battery low (for MLi Ultra batteries) 

MLi Ultra 

Open relay 

On 

Battery full 

MPC Fuel cell 

Activate 

Off 

 

 

 

 

Safety events for MLi Ultra battery 

 

 

 

 

Event Source 

Event Target 

Event Command 

Event Data 

Stop charge 

MPC Fuel cell 

Activate 

Off 

Battery safety 

MPC Fuel cell 

Activate 

Off 

Stop charge (on charger or Mass Combi) 

device dependent 

Charger On 

Copy invert 

Battery settings for MLi Ultra 

 

 

 

 

MasterBus power 

Off (unchecked) 

 

 

 
 

EFOY FUEL CELL SETTINGS 

 
 
 

 1. Select the External control mode 

 

    

• Press 

  on the operating panel

,

 or select "Operating mode" in the main menu. The operating mode selection appears. 

 

    

• Select the "External control on" operating mode. 

 

 

• Press [ok] to confirm your selection. 

 
        
        

• If the EFOY-MASTERVOLT cable is correctly connected to the EFOY fuel cell, the infoscreen will show “Hybrid” and an open padlock.

 

        

• If the EFOY fuel cell is activated via the EFOY-MASTERVOLT cable, “RC” will be displayed on the Infoscreen 

 
 

2. Choose the battery type in the expert menu 

  

 

     

• To access the expert menu, press and hold [ok] and [menu] at the same time for two seconds. The expert menu appears. 

 

     

• Press 

[

][

] to select a submenu. 

 

     

• Choose the submenu “Battery type” and press OK. 

 

     

• Choose the battery type “Gel” for the Gel batteries or “LiFePo4” for the MLi Ultra batteries 

 

Figure 3: EFOY fuel cell settings

 

 

              Note: The standard factory settings correspond to lead-acid batteries. 

 

 

 

 

 

   For all settings and language versions, please refer to the standard EFOY user manual 

 

SPECIFICATIONS 

Model  

77032100 EFOY-MASTERVOLT Cable  

Applicable for MASTERVOLT Gel batteries 

12V GEL batteries up to 12V-200Ah  

Applicable for MASTERVOLT Li-ion batteries 

MLi Ultra 12/2500, MLi Ultra 12/5000 

Applicable for EFOY fuel cells 

EFOY COMFORT 140 and 210, EFOY Pro 2400, 2400 Duo 

Cable length 

1500 mm including the connectors 

Connectivity 

Multipurpose contact (article nr 77030500 not included) 

 
 

 

English 

Nederlands 

Deutsch 

1.

 

Mastervolt MLi Ultra battery or 
GEL battery with MasterShunt  

Mastervolt MLi Ultra accu of 
GEL accu met MasterShunt. 

Mastervolt MLi Ultra Batterie oder 
GEL-Batterie mit MasterShunt 

2.

 

Fuse in positive battery cable 

Zekering in pluskabel 

Sicherung in Pluskabel 

3.

 

MasterBus cable 

MasterBus kabel 

MasterBus kabel 

4.

 

Multipurpose contact  

Multipurpose contact  

Multipurpose contact  

5.

 

EFOY-MASTERVOLT cable 

EFOY-MASTERVOLT kabel 

EFOY-MASTERVOLT kabel 

6.

 

EFOY fuel cell 

EFOY brandstofcel 

EFOY Brennstoffzelle 

7.

 

Loads 

Lasten 

Lasten 

8.

 

Positive DC line 

DC Pluskabel 

DC Pluskabel 

9.

 

Minus DC line 

DC Minuskabel 

DC Minuskabel 

10.

 

MasterBus cable 

MasterBus kabel 

MasterBuskabel 

11.

 

MasterBus terminator 

MasterBus terminator 

MasterBusterminator 

12.

 

Fuse in positive cable 

Zekering in pluskabel 

Sicherung in Pluskabel 

13.

 

Optional: Battery Safety relay 
only in combination with MLI 
Ultra battery. Refer to the MLi 
Ultra manual.

 

Optioneel: Battery Safety 
relais, alleen in combinatie 
met de MLi Ultra accu. Zie de 
MLi Ultra handleiding.

 

Optional: Batterie Sicherheitsrelais 
nur in Kombination mit MLI Ultra-
Batterie. Siehe Bedienungs-
anleitung MLi Ultra.

 

 

Reviews: