- AB AB600A5015
Instruction Manual
- 27 -
7.12 Light barrier
Function
Parameters
Light barrier On/Off
009
The light barrier function at the input of socket B18/8 is active only if parameter value
239 = 0
.
7.12.1 Speed after Light Barrier Sensing
Function
Parameters
Speed after Light Barrier Sensing
(n5)
114
7.12.2 General Light Barrier Functions
Function
Parameters
Light barrier compensating stitches
Number of light barrier seams
Light barrier sensing uncovered/covered
Start of sewing blocked/unblocked with light barrier uncovered
Light barrier seam end with thread trimming On/Off
Speed of the light barrier compensating stitches
LS
(LSn)
(LSd)
LSS
(LSE)
PLS
004
006
131
132
133
192
After sensing the seam end, the compensating stitches are counted at light barrier speed.
Suspension of the procedure with pedal in pos. 0 (neutral). Interruption of the procedure with pedal in
pos. -2.
The thread trimming operation can be disabled using parameter
133
. Stop in the basic position.
Programming of max. 15 light barrier seams depending on the setting of parameter
006
with stop in the
basic position. Thread trimming after the last light barrier seam.
Light barrier sensing uncovered or covered at the seam end can be selected using parameter
131
.
Start blockage with light barrier uncovered programmable using parameter
132
.
Speed selection pedal controlled / n5 during the light barrier compensating stitches using parameter
192
.
7.12.3 Reflection Light Barrier LSM002
Sensitivity setting:
Set minimum sensitivity depending on the distance between light barrier and reflection area (turn potentiometer
as far as possible to the left).
Potentiometer directly on the light barrier module
Mechanical orientation:
Orientation is facilitated by a visible light spot on the reflection area.