Omni-Phase OSW & OSE Transient Voltage Surge Suppressor (TVSS)
Instruction Bulletin

EFI Electronics Corporation
1751 South 4800 West • SLC, UT 84104
1-800-877-1174 • www.efinet.com

1230-1030J    03/03

1. Turn off all power supplying this equipment before working on or inside any

enclosure containing this equipment.

2. Identify proper location for surge protective device.  Locate as close as possible

to the panel being protected. Mount unit securely, as  close to the electrical
connection as possible.  See Figure 2 for  mounting instructions.  
NOTE: The surge protective device must be installed in an accessible  location
(not within walls).

3. Confirm surge protective device is rated for your system by comparing voltage

measurements to the Line Voltage (L-L, L-N) on  the product label.

4. Install in accordance with National and Local Electrical Codes and  match

branch circuit breakers to the size of wire being used (up to 30 A circuit
breaker).

5. Confirm that the electrical terminals used to attach this device are  identified for

these conductors.

6. Twist conductors 1/2 turn or more for every 12 inches of length. 

7. Do not loop or coil wires. Be sure to maintain adequate wire bending space per

NFPA 70 2002 Edition, article 408.35. 

8. Use on solidly grounded systems only. 

Diagnostic Operation

LED ON = Normal operation
(see Figure 3)

LED OFF (one or more) = Fault.  
Check phase voltage, circuit 
breakers and connections.  
If OK replace unit.

Figure 4: Dimensions

Dimensions:

in.

[mm]

6.0

[152]

4.0

[102]

2.0

[51]

LED ON = OK

LED OFF = Fault 

Figure 3:  Diagnostic Operation

0.75 in. [19 mm] knockout (trade size)
Actual hole size 1.0 in. [25 mm]

Nut

Figure 2:  Mounting Unit

NOTE: The surge protective device must be 
installed in an accessible location (not within walls).

General Specifications

Max Surge Current 

80 kA/Phase

Short Circuit Current Rating

5 kA, 600 V Maximum

Housing Rating

NEMA Type 1

Product Weight

3.05 lbs. (1.38 kg)

Connection Method

Parallel, #10 AWG Stranded Wire

EMI/RFI Noise Rejection

Up to -35 dB (OSW only)

Operating Temperature

-40˚ to +140˚F (-40˚ to +60˚C)

Operating Frequency

50/60/400 Hz

Diagnostics

Green Status LEDs

Product Standards

to UL 1449-2nd Ed, CSA C22.2 No. 0-M91

Black

Black

White

Green

Orange

Figure 1:  Wiring Diagrams

1Ø 3-wire 120/240 Vac

L1

N

L2

L1

N

L2

L3

3Ø 4-wire 208Y/120 Vac,

380Y/220 Vac, 480Y/277 Vac,

 or 600Y/347 Vac

L1

L2

L3

N

3Ø 4-wire 240D/120 Vac

Black

Black

Green

L1

L2

N

3Ø 3-wire (grounded B phase) 

240D Vac, 480D Vac or 600D Vac

White

Black

Black

Green

White

Black

Black

Black

Green

White

Black

INSTALLATION