Important Notice
】
With 230V/50Hz/1Ph power supply:
Use wiring diagram A1. L1, L2 and L3 from
terminal block T2 should be connected to terminal
U of terminal block T1;N1, N2 and N3 from
terminal block T2 should be connected to terminal
N of terminal block T1.Power supply cable must
be able to carry the maximum running current of
the system (recommand to use power cable no
smaller than 8mm2).
With 415V/50Hz/3Ph power supply:
Use wiring diagram A2. L1, L2 and L3 from
terminal block T2 should be connected to terminal
U, V and W of terminal block T1;N1, N2 and N3
from terminal block T2 should be connected to
terminal N of terminal block T1Power supply
cable must be able to carry the maximum running
current of the system (recommand to use power
cable no smaller than 2.5mm2).
With 230V/50Hz/3Ph power supply:
Use wiring diagram A3. L1 and N1 from terminal
block T2 should be connected to terminal U of
terminal block T1;L2 and N2 from terminal block
T2 should be connected to terminal V of terminal
block T1;L3 and N3 from terminal block T2 should
be connected to terminal W of terminal block T1;
Power supply cable must be able to carry the
maximum running current of the system
(recommand to use power cable no smaller than
4mm2).
5
1.Wiring diagram
Wiring diagram