UPS MKD 1500 RT
Safety Instructions
MKD series
16
2.5
Connection
Only connect the UPS to an earthed electric safety socket or be sure to
connect it to the protective conductor in the event of a connecting termi-
nal. Under no circumstances may the device may be operated without a
protective conductor.
The socket for home installation must be easily accessible and in the
vicinity of the UPS. Be sure to have the shortest possible cable lengths
for fixed connections.
When operating with a generator, you must ensure the correct polarity of
the connection for the UPS.
To connect the UPS to the socket of the home installation, only use a
VDE tested and CE labelled mains cable. For a fixed connection, an ap-
propriate cable is to be used.
To connect the loads to the UPS, only use a VDE-tested and CE-labelled
cable. For a permanent connection of the loads, an appropriate cable is to
be used.
The protection of the loads must always take place directly on a load,
never centrally at the UPS.
Do not operate any household or craftsman tools such as fan heaters,
vacuum cleaners, drills, hair dryers, toasters, etc. with the UPS.
Do not connect any loads to the UPS, which could overload the device
(e.g. laser printer).
The total earth leakage currents of all the loads connected to the UPS
may not exceed 3.5 mA.
Keep cables as short as possible and always lay them correctly. Dangers
such as stumbling, squeezing, clipping, etc. are to be avoided with the
cables.
To connect the loads to the UPS, only use a VDE-tested and CE-labelled
power cables with the appropriate cable diameter. The protection of the loads
must always take place directly on a load, never centrally at the UPS. Do not
connect any loads to the UPS, which could overload the device (regard the
high starting currents).