E F A P O W E R   E V - Q C 4 5   -   I N S T A L L A T I O N   A N D   U S E R   M A N U A L  

11 | 32                           

5.3

 

HANDLING AND PLACING 

 

 

Before installing stations  

The instructions provided in this manual assume that the appropriate wiring, circuit protection, and 
metering are in place at the installation location.  
To assist in the process of preparing the installation site, it is recommended that before you begin 
installing  the  Quick  Charging  Station,  you  thoroughly  review  the  contents  of  this  document  to 
familiarize yourself with the required installation steps. 

 

In case of any doubt regarding items described in this guide, please contact us at: 
 

5.3.1

 

PACKAGING 

EFAPOWER EV-QC45 is shipped in a package with the following dimensions (WxDxH): 

 

1150x850x2150mm (45.3x33.5x84.6 inches) 

 

 
 
 
 
 
 
 
 

5.3.2

 

VISUAL INSPECTION 

 

Check

 

if

  the 

exterior

 

packaging

  has  been 

damaged

  by  mechanical  impacts  or  any  accidents  during 

transportation 

 

If applicable, 

check

 

if

 the 

exterior panels 

of the EFAPOWER EV-QC45 are in 

perfect

 

condition

  

 

Check

 

if

 the interior of the 

Quick

 

Charger

 Station is 

clean

 

 

Check

 

if

 the 

door

 of the Quick Charger Station is 

working

 

properly

 

 

Check

  for  proper  Quick  Charger  Station 

protective

 

ground

 

connection

 

point

,  which  should  be 

interconnected with the low voltage switchboard ground connection during the installation 

 
 

 

                

Rua Eng.º Frederico Ulrich - Apartado 3078 
4471-907 MOREIRA MAIA - PORTUGAL 
Tel: (+351) 229403241 - Fax: (+351) 229403209 
[email protected] 
www.electricmobility.efacec.com 

 

                 

2725 Northwoods Parkway, Ste. B  
Norcross, Georgia 30071 USA  
Tel: (1) 470 395-3648

 

Fax: (1) 770 446 8920 

[email protected] 
www.electricmobility.efacec.com  

Power   
cabinet 

Summary of Contents for EFAPOWER EV-QC45

Page 1: ...loser than 6 1m 20 feet of an outdoor motor fuel dispensing device EFAPOWER EV QC45 is in an IP54 IK10 NEMA 3R enclosure This Unit is intended to work below 50ᵒC 122ᵒF ambient temperature Clearance around the cabinet The air must circulate freely throughout the ventilation grids in order for the charger s cooling system to be effective The ventilation areas on the sides and back must not be blocke...

Page 2: ... temperatures heavy dust snow and or very low temperatures it s recommended to provide additional protection either inside a building or a shelter or providing a protection roof for the Unit See example in Figure 6 Figure 6 EFAPOWEREV QC45 with shelter 5 1 2 SITE VERIFICATION AND INSPECTION Check if the installation of the Quick Charger is not planned to be made in a commercial garage repair facil...

Page 3: ... outputs connections not available for USA market Requires a dedicated 160A circuit breaker 3P C curve Figure 7 EFAPOWEREV QC45Wiring Information NOTES In areas with frequent thunder storms Efacec recommends adding transient voltage surge suppression TVSS at the service panel for all circuits Unless required by local codes it is not necessary to install a residual current device RCD for the circui...

Page 4: ... 2 above the concrete and 89 5mm 3 52 into the concrete 4 four sealing screws Socket head button cap screws M12x25 metric with matching flat rubber washers supplied with the Quick Charging Station End terminals for input wiring Depending on the EFAPOWER EV QC45 configuration Only DC outputs 5 five end terminals up to 35mm2 3phases neutral protective ground or DC and AC outputs not available for US...

Page 5: ... WxDxH 1150x850x2150mm 45 3x33 5x84 6 inches 5 3 2 VISUAL INSPECTION Check if the exterior packaging has been damaged by mechanical impacts or any accidents during transportation If applicable check if the exterior panels of the EFAPOWER EV QC45 are in perfect condition Check if the interior of the Quick Charger Station is clean Check if the door of the Quick Charger Station is working properly Ch...

Page 6: ...4 ASSEMBLY PLACING INSTRUCTIONS 5 3 4 1 ANCHORING TO THE CONCRETE PAD The Quick Charging Station must be anchored on the surface compliant with the specifications mentioned in chapter 5 2 2 The power cabinet must be installed on a concrete pad using 4 four chemical anchors M8 5 16 10mm thread diameter length must comply with local codes but must have at least 120mm 5 In the following figure some d...

Page 7: ...instructions For the Power Cabinet it s advised to have a concrete block of at least 1000mm 34 9 square by 254mm 10 deep Check local codes to ensure compliance The bolts must extend at least 30 5mm 1 2 above the concrete and 89 5mm 3 52 into the concrete ALL SERVICING MUST BE PERFORMED ONLY BY QUALIFIED PERSONNEL DO NOT ATTEMPT TO SERVICE THE EFAPOWER EV QC45 QUICK CHARGING STATION YOURSELF DO NOT...

Reviews: