Cyclic presence send time
No cyclic send, 1 min to
1 hour
Object <VH> Presence Output can be send cyclically if
Presence
sensor
OFF
latency
10 to 63 sec.
This parameter is related to the time set on the
presence detector. The most of presence detectors
keep the presence status for a configurable amount of
recommended to set this time duration at the
minimum.
If the presence detector is a conventional one (dry
contact output connected to a KNX input) this time
duration is the relay time. If the knob of the
conventional presence detector is set to 10 sec. then
set this parameter to 10 sec. as well.
Send
welcome
on
unexpected presence
do not send / send
This parameter defines the behaviuor when the VH
module detects a presence inside the room and is in
possibile to send or not the welcome event.
Global enable state after
download
disabled / enabled
See paragraph Remote Sensor inputs (Global Enable).
Booked
status
after
download
not booked / booked
Set the initial value for the object <VH> Room Booked
Absence with door open
(deny=if
door
open
presence is active)
allow / deny
This parameter defines the behavior when the VH
module detects the open port. If the door remains
open longer than the wait time, this parameter defines
Additional output type
value 0-255
value 0-100%
scene
It is possible to enable an addititional CO to transmit
on the bus a command linked to presence or absemce
events.
Parameters Remote inputs
In this page the installer must set which type of
sensor are linked to the VH module
KNX PARAMETER
SETTINGS
Remote input <x>
disabled
door
presence
bus sniffer
disabled
:
non used
door
:
set this option if the communication
object <VH> Remote Input x Door is linked to a door
contact KNX input.
presence
:
set this option if the
communication object <VH> Remote Input x Presence
is linked to a presence detector KNX communication
object.
Bus sniffer
:
set this option if the communication
object <VH> Remote Input x Sniffer is linked to a
generic CO used in the room.
Usage of the Bus Sniffer Option.
When a person occupies a room interacts with it.
Turning on or off a light in the main room or in the
bathroom gives indication of the presence of people
inside the room. To reduce the risk of not correctly
identifying the "occupied room" status, it is
recommended to connect a "bus sniffer" input to all
the 1 bit objects that can be sent to the bus only by
the presence of a person in the room such as
bathroom or mirror lights or window contact or
bedside light, etc ....
WARNING ON REMOTE INPUT <X> CO
-
a Remote Input CO (type
door
) must be connected
only to one single door contant on/off telegram;
-
a Remote Input CO (type
presence
) must be
connected only to one single device with presence
on/off telegram;
-
a Remote Input CO (type
bus
sniffer
) can be
connected to more than one devices.
Local input
disabled
door
presence
Local input can be connected either to a door contact
or conventional presence detector ; by setting this
possibile to send also telegram on the KNX bus for
other purpouses.
Remote Sensor Inputs (Global Enable)
This CO is used when you need to consider 2
adjacent rooms as separated or joined as if they
were a single room (suite room).