EECI ADC-4U15 Technical Reference Download Page 1

TABLE OF CONTENTS

            

Specifications.......................................... page 1

            

Connection Diagram and Warranty......... page 2

            

Technical Support................................... page 2

            

Terminal Block Connections.................... page 2

            

Set-Up and Testing................................. page 3 & 4
Device Manager...................................... page 4
Trouble-Shooting and Sample Rate........ page 5

          

Input & Relay Expansion Ports............... page 5
The ADC-4U15 User Interface................ page 6
Auto Start-Up.......................................... page 6
The ADC-4U15 Data Logger................... page 7
Programming Examples......................... page 7
Voltage Reference for the analog inputs. page 8

            

Single Ended Analog Inputs.................... page 8

            

Analog Scaling and Differential Inputs.... page 9
Input Amplification and Conditioning..... page 11

       

Voltage Inputs and Sensor Interfacing.....page 10 & 11
Mounting..................................................page 11

SPECIFICATIONS

Power Supply.......................

5 volts DC - powered from USB port (USB version only)

Operating Temp. Range......

-40° C to +85° C 

Serial Data Protocol.............   75 to 6,000,000 baud - auto detect (defaults to 115,200 baud)

Full duplex operation (data bits, parity, stop bits will auto detect)

Maximum Sampling Rate...... 100 samples per second or better

Analog Inputs.......................

4 single-ended inputs (15 bit resolution) - no missing codes
or 2 fully differential inputs (16 bit resolution) - no missing codes
(15 bit resolution will divide your measurement range into 32,768 different increments)
(16 bit resolution will divide your measurement range into 65,536 different increments)

Input Impedance.................

Common mode better than 6 mega ohm (see page 11 and 12)

Voltage Input Range............

Selectable at:  0 to 256 millivolt, 0 to 512 millivolt, 0 to 1.024 volt, 0 to 2.048 volts,

       0 to 4.096 volts and 0 to 6.144 volts (with 5 V max)*

*the voltage resolution per increment can be determined by dividing one of the

 

above reference voltages by 32,768.

Expansion Capability............

expandable to control up to 144 relays/inputs (or combinations) using 
EX-8M, EXM-8, EXM-16 or EXM-32 Relay I/O Expansion Modules

Interface.............................. 

USB (also available in WiFi version (ADC4-15WIFI), Ethernet version 
(ADC4-15FENET) RS-232 version (ADC4-15RS232) or 
RS-485 version (ADC4-15RS485))

Software Compatibility.........

Windows XP, Vista, Windows Server, Windows 7, 8.1, Windows 10 and Windows 11

Weight.................................

.5 ounce

Size......................................

1.875 inches by 2.5 inches

      
Please see page 12 for additional specifications.

Page 1

  

TECHNICAL REFERENCE

ADC-4U15

ANALOG TO DIGITAL 

CONVERTER

Click for more info:     www.eeci.com/adc-4u15p.htm

(937) 349-6000
(800) 842-7714
(937) 349-6000
[email protected]

PHONE...................
ORDERS................
TECH SUPPORT...
E-mail.....................

www.eeci.com

Summary of Contents for ADC-4U15

Page 1: ...it resolution no missing codes 15 bit resolution will divide your measurement range into 32 768 different increments 16 bit resolution will divide your measurement range into 65 536 different incremen...

Page 2: ...USB port and install the ADC 4U15 device driver by clicking the Install EECI Device Driver button from the installer dialog window if you have auto start disabled you may browse to the Windows Driver...

Page 3: ...sion modules The relay output ports on the Page 5 installed if you have Windows 7 or higher If the Net Framework is not installed on your computer the installation program will attempt to download and...

Page 4: ...alog converter may be used to output an analog voltage For additional information please visit t the EECI web site at www eeci com THE ADC 4U15 USER INTERFACE The ADC 4U15 User Interface allows you to...

Page 5: ...A 8 instrumentation amplifier The VA 1 connects to any of the analog inputs and will convert a millivolt signal input to a 0 to 5 volt output for input into the ADC Signal levels this low will may req...

Page 6: ...24 volts or great enough to create an electrical shock hazard or fire should be connected to the ADC analog input using a step down transformer to reduce the high voltage down to the 5 volt range as...

Page 7: ...es will not be applied until you click the Apply button The changes are saved to the ADC 4U15 ini file Relay and Input labels may be changed by clicking the Relay Control or Input Setup buttons Click...

Reviews: