P/N P-047550-1788-EN • REV 013 • ISS 08SEP19
3 / 3
Specifications
Operating voltage
15.20 to 19.95 VDC
Current
Standby
Alarm
170 µA
170 µA
Circuit resistance between
isolators
6 Ω max.
Ground fault impedance
10 kΩ
Circuit designation
Signaling line circuit
Class A, Class X
Wire size
12 to 18 AWG (1.0 to 4.0 mm²)
Compatible electrical boxes
2-1/2 in. (64 mm) deep double-gang
box; 4 in. square box, 1-1/2 in. (38 mm)
deep with double-gang cover
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
Storage temperature range
−4 to 140°F (−20 to 60°C)