background image

 

P/N P-047550-1788-EN • REV 013 • ISS 08SEP19 

 

3 / 3 

Specifications 

 
Operating voltage 

15.20 to 19.95 VDC 

Current 
 

Standby 

 

Alarm 

 
170 µA 
170 µA 

Circuit resistance between 
isolators 

6 Ω max. 

Ground fault impedance 

10 kΩ 

Circuit designation 
 

Signaling line circuit 

 
Class A, Class X 

Wire size 

12 to 18 AWG (1.0 to 4.0 mm²) 

Compatible electrical boxes 

2-1/2 in. (64 mm) deep double-gang 
box; 4 in. square box, 1-1/2 in. (38 mm) 
deep with double-gang cover 

Operating environment
 

Temperature 

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Storage temperature range 

−4 to 140°F (−20 to 60°C) 

 

Regulatory information 

 
FCC compliance 

This device complies with part 15 of the FCC 
Rules. Operation is subject to the following two 
conditions: (1) This device may not cause harmful 
interference, and (2) this device must accept any 
interference received, including interference that 
may cause undesired operation. 

 

Contact information 

For contact information, see www.edwardsfiresafety.com. 

 

 

 