background image

2 / 6 

 

P/N 3101077 • REV 05 • REB 23JAN13 

Figure 1: AB4G-SB box installation 

 

1

2

3

4

5

6

7

 

1. 

Conduit connector 

2. 

AB4G-SB electrical box 

3. 

Lock tab 

4. 

Trim rings 

5. 

Screw 

6. 

Nut 

7. 

Reinforcing plate 

 

Figure 2: Base installation  

 

1. 

Detector 

2. 

Trim ring 

3. 

Screw 

4. 

Base plate 

5. 

Compatible electrical box 

 

Wiring 

Wire in accordance with NFPA 72 and CAN/ULC-S524. Be 
sure to observe the polarity of the terminals on the terminal 
block as shown in the diagram. 

Break the wire run at each terminal. Do not loop signaling 
circuit field wires around terminals. 

Refer to the applicable technical reference manual for 
application diagrams. 

Note: 

Shielded wire is required only in environments with very 

high electrical noise. When you use shielded cable, follow 
these recommendations

• 

Shield connection to and from the base must be 
continuous and must be insulated from ground. Insulate 
the shield using tape. 

• 

For Class B wiring, there is no shield connection to ground 
at the last device. 

Figure 3: Output configuration and wiring diagram 

4

SLC 

+

SLC 

+

AUX_RISER 

+

AUX_RISER 

+

SLC 

SLC 

AUX_RISER 

AUX_RISER 

 

1. 

AUX-RISER IN (from power supply or previous base) 

2. 

Volume setting: default is high volume; cut per item 4 for low 
volume 

3. 

Tone setting: default is temporal pattern; cut per item 4 for steady 
tone 

4. 

To configure output volume or tone, cut the circuit board as 
shown 

5. 

AUX_RISER OUT To next base or EOL relay 

6. 

SLC OUT to next intelligent addressable device 

7. 

SLC IN from intelligent addressable controller or previous device 

 

Reviews: