Chapter 2: Installation and configuration
26
LaserSense 100 Aspirating Smoke Detector Installers Handbook
In the example shown in Figure 15 on page 25, if detectors 4-126 (not shown)
are all this type of detector, then the total length of wiring between Detectors 3
and 127 would be limited to 1.2 km (3/4 mile). However, each additional
LaserSense HSSD-2 detector wired up using both RS-485 buses would allow an
additional1.2 km (3/4 mile) of cabling to be added to the RS-485 loop.
Final installation
Once the power and signal connections are made, slide the detector body up into
the docking station and fasten it into position using the M4 pan head screws
provided. Slot the power and signal terminal blocks into the relevant sockets on
the detector PCB (which will only click fully home in the correct orientation).
Lastly, replace the detector cover using the six pan head screws provided. Refer
to Figure 16 below.
Note:
The detector is designed solely for operation with the front cover securely
fitted using all six fixing screws.
Removing the detector
Removing the detector is the reverse of the installation process, leaving the
pipework and wiring connections installed in the docking station (as shown in
Figure 4 on page 10). See Figure 16.
Figure 16: Final installation of the detector
(1) Docking station attachment screws (3X)
(2) Cover attachment screws (6X)