Installation 

Caution: 

To ensure correct operation of your system, you 

must follow the recommended cabling practices described 
below. 

Wiring 

Connect the detector base as shown in Figure 1: 

1.  PIN 1 Positive line 
2.  PIN 2 Data line 
3.  PIN 3 Negative line 

The cable used should: 

• 

Have a cross-sectional area of at least 1.5 mm

2

 

• 

Have maximum resistance of 13.3 Ω/km per core 

Detector placement 

Detectors should be installed above the level at which the gas 
is generated. 

Note: 

Installing the detectors too high or placing the detectors 

too close to windows, air inlets or ventilation systems may 
prevent the carbon monoxide from reaching the detector. 

Detector installation 

Insert the detector head into the base, rotating it clockwise until 
it clicks into place. 

The detector head can be locked into the base by breaking the 
locking tab at the base of the detector head (Figure 2, item 1). 
To remove a locked detector, insert a screwdriver into the base 
slot and push. 

LED indications 

When in service the detector LED will flash green. A flashing 
red LED indicates a fault. A steady red LED indicates an alarm 
(by default this occurs when CO levels of 50 ppm or higher are 
detected). 

Maintenance 

Basic maintenance consists of a yearly inspection. Do not 
modify the internal wiring or circuitry. 

Specifications 

 

Operating voltage 

10 to 20 VDC 

Current consumption 
 

Standby (LED off) 

 

Alarm (red LED illuminated) 

 
6 mA 
15 mA 

LED indications 
 

Standby 

 

Fault 

 

Alarm (50 PPM) 

 

Detector uncalibrated 

 
Flashing green LED every 15 s 
Flashing red LED every 15 s 
Steady red LED 
Flashing red LED every 2 s 

Accuracy 
 

0 to 50 ppm 

 

50 to 300 ppm 

 
± 5 ppm 
5% of measured value 

CO detection range 

0 to 300 ppm 

IP rating 

IP42 

Maximum number of detectors per 
zone 

15 

Operating temperature 
Storage temperature 
Relative humidity  

−10 to +40°C 

−10 to +70ºC 
10 to 95% noncondensing 

Dimensions (Ø x H) 

124 x 62 mm 

Weight 

300 g 

Regulatory information 

 

Manufacturer 

United Technologies Safety System Co. Ltd. 
80, Changjiang East Road, 
QETDZ, Qinhuangdao, 
Hebei Province, China 066004 

Authorized EU manufacturing representative:  
UTC Fire & Security B.V.  
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Year of 
manufacture 

The first two digits of the product serial number 
(located on the product identification label) 
indicate the year of manufacture. 

Certification 

 

Year of first CE 
marking 

09 

LOM certificate

 

09MOGA3101

 

Compliance 

UNE 23300:1984 +1M:2005 

 

2012/19/EU (WEEE directive): Products marked 
with this symbol cannot be disposed of as 
unsorted municipal waste in the European Union. 
For proper recycling, return this product to your 
local supplier upon the purchase of equivalent 
new equipment, or dispose of it at designated 
collection points. For more information see: 
www.recyclethis.info. 

Contact information 

For contact information, see www.utcfssecurityproducts.eu. 

ES: Instrucciones de instalación 

Descripción 

Este documento incluye información de instalación para el 
detector de monóxido de carbono KMD300 de UTC Fire & 
Security. 

El modelo KMD300 está diseñado para su uso con los 
sistemas de detección de CO KM300 y KM260. 

La vida útil del detector KMD300 es de cinco años

Principio de operación 

Detección basada en sensor electroquímico que mejora la 
exactitud de la medida y reduce el consumo, con 
compensación térmica integrada, y control basado en 
microcontrolador de 16 bits. 

 