P/N 3102149-
EN • REV 02 • ISS 25MAR14
3 / 6
Figure 3: Surface mount
(1)
Surface mount box (G4B or
G4RB)
(2
)
Horn
-strobe
(3)
Screw (4X provided with
G4B or G4RB box)
(4)
Cover
Figure 4: Wiring diagram
(1)
From NAC output
(2)
To next device
or EOL
Note: Polarity is shown in the active condition.
Specifications
Operating v
oltage
24
VDC
or 24
VFWR
[1]
Operating horn
-strobe
current
See Table 6
Sound level output
See Table 2 and Table 3
Audible directional
characteristics
See Table 4 and Table
5
Light output
Selectable at 15, 30, 75, and 110 cd
(see
Figure
5
, Figure 6, and Figure 7
)
[2]
Synchronization
Maximum allowed resistance between any
two devices is 20
Ω. Refer to specifications
for the synchronization control module, this
strobe, and the control panel to determine
allowed wire resistance.
Default settings
1 flash per second (fps)
Wire size
12 to 18 AWG (1.0 to 4.0
mm²)
Compatible electrical
boxes
Standard 4 in. square box 1-
1/2 in. (38 mm),
2-
1/8 in. (54 mm) deep, or G4B/G4RB
surface mount box
Operating environment
Temperature
Relative humidity
32 to 120°F (0 to 49°C)
0 to 93% noncondensing
[1] This device was tested to the
Regulated 24 DC/FWR operating
voltage limits of 16 V and 33 V. Do not apply 80% and 110% of these
values for system operation.
[2] When this device is used as a low frequency sounder in sleeping
quarters, the strobe's candela switch (Figure 1
) must be set to 110 cd.
Table 2: UL sound level output (dBA) [1]
Signal and voltage
Low
High
Temporal
16 VDC
72.4
76.0
24 VDC
72.3
75.7
33 VDC
73.3
75.4
Continuous
16 VDC
75.7
79.8
24 VDC
76.1
78.6
33 VDC
75.4
78.8
[1] UL 464: Sound level output
at 10 ft. (3.05 m) measured in a
reverberant room.
Table 3: Nominal sound level output (dBA, temporal tone) [1]
Voltage
Low
High
16 VDC
84.0
85.5
24 VDC
83.9
85.4
33 VDC
83.7
85.5
16 VFWR
83.7
86.1
24 VFWR
83.9
85.9
33 VFWR
84.0
85.9
[1] Measured
in an anechoic chamber at 10 ft. (3.05
m)
.