background image

P/N 3100273 • REV 07 • REB 30JAN13 

 

3 / 4 

Figure 5: Wiring Diagram 

 

1. 

First speaker-strobe 

2. 

Last speaker strobe 

3. 

EOL resistor, voltage determined by control panel  

Amplifier output voltage must match the voltage ratings of the 
speaker (25 or 70 VRMS) 

Note:

 Signal polarity is shown in the alarm condition. 

Table 3: Strobe operating current in RMS (A) 

 

15 cd 

30 cd 

75 cd 

110 cd 

VDC 

0.096 

0.130 

0.239 

0.294 

VFWR 

0.120 

0.169 

0.329 

0.375 

VDC = Volts direct current, regulated and filtered 
VFWR = Volts full wave rectified 

Operating currents shown above were measured by UL at 16 VDC and 
16 VFWR. 
 

Table 4: Sound level output (dBA) 

Wattage 

Output 

 

 

 

1/4 W 

80 

 

 

 

1/2 W 

83 

 

 

 

1 W 

86 

 

 

 

2 W  

89 

 

 

 

UL 1480: Sound level output at 10 ft (3.05 m) measured in a 
reverberant room using 400 to 4,000 Hz band limited pink noise. 

ULC-S541: Meets or exceeds 85 dBA in an anechoic chamber at 10 ft 
(3.05 m). 

Directional characteristics: Within 6 dB of on-axis sound level when 
measured 90

°

 off-axis (horizontal). 

Maintenance 

This unit is not serviceable or repairable. Should the unit fail to 
operate, contact the supplier for replacement. 

Perform a visual inspection and an operational test twice a 
year or as directed by the local authority having jurisdiction. 

Do no change the factory-applied finish. 

Specifications 

 

Operating voltage 
 

Speaker 

 

Strobe 

 
25 VRMS (model S2) or 70 VRMS (model 
S7) 
24 VDC, 24 VFWR 

Supervisory voltage 

30 V maximum 

Strobe operating 
current 

See Table 3 

Sound level output 

See Table 4 

Speaker response 

400 to 4,000 Hz 

Light output 

Selectable at 15, 30, 75, and 110 cd 

Default settings 

1 flash per second (fps) 

Wire size 

12 to 18 AWG (0.75 TO 2.50 mm²) 

Compatible electrical 
boxes 

North American 4 in. square electrical box, 
2-1/8 in. deep (no extension ring) 
G4 Series surface mount box: See Table 1 

Operating environment
 

Temperature

 

Relative humidity 

 
32 to 120°F (0 to 49°C) 
0 to 93% noncondensing 

Intended Installation 

Indoor dry 

 

Regulatory information 

 

Manufacturer 

Edwards, A Division of UTC Fire & Security 
Americas Corporation, Inc. 
8985 Town Center Parkway, Bradenton, FL 
34202, USA 

Year of 
manufacture 

The first two digits of the DATE MFG number 
(located on the product identification label) are 
the year of manufacture 

UL/ULC rating 

Regulated 24 DC and 24 FWR 

This device was tested to the regulated 
24 DC/FWR operating voltage limits of 16 V and 
33 V. Do not apply 80% and 110% of these 
values for system operation. 

Environmental 
class 

UL: Indoor 

Synchronization 

Meets UL 1971 requirements. Maximum allowed 
resistance between any two devices is 20 

Ω. 

Refer to specifications for the synchronization 
control module, this strobe, and the control panel 
to determine allowed wire resistance. 

Agency listings 

UL 1638, UL 1480, and UL 1971 
CAN/ULC S526, ULC-S541 
BS EN 60065:2002 [1] 

[1] Nameplate marking is located on the inside surface of the device. 

Contact information 

For contact information, see www.edwardsutcfs.com. 

3