Chapter 3: FireWorks node connections
P/N 3102213-
EN • REV 006 • ISS 18FEB19
33
Using an MN-COM1S
Figure 31 and Figure 32
show you how to connect an EST3 control panel to the
FW-UL6W using an MN-
COM1S.
For more information, see
MN-COM1S RS-232 to Ethernet Interface Installation Sheet
(P/N
3101601-EN
).
Figure 31: Local MN-COM1S connection
(1)
FW-UL6W and FW-UL6CC1.
(2)
RJ
-
45 Ethernet patch cable, Cat 5e or better. Limit connection to
the same room, within 20 ft. (6.1 m) for UL
or 59 ft. (18 m) for ULC, and enclose in conduit or equivalent protection against mechanical injury.
(3)
EST3 CPU card and RS
-232 option card.
Figure 32: Remote MN-COM1S connection
(1)
FW-UL6W and FW-UL6CC1.
(2)
RJ
-
45 Ethernet patch cable, Cat 5e or better. Limit connection to the same room, within 20 ft. (6.1 m) for UL
or 59 ft. (18 m) for ULC, and enclose in conduit or equivalent protection against mec
hanical injury.
(3)
MN-
FNSx Ethernet switch.
(4)
Dedicated fiber network.
(5)
EST3 CPU card and RS
-232 option card.
Configure a FireWorks TCP/IP port as shown in Figure 33.
(2)
(3)
EST3
(1)
MN-COM1S
(5)
(3)
(3)
EST3
(1)
(4)
(2)
MN-COM1S
Summary of Contents for FireWorks FW-UL6S
Page 1: ...FW UL6W FireWorks Workstation Installation Manual P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 8: ...vi P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 20: ...Chapter 1 Introduction 12 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 36: ...Chapter 2 Installation 28 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 60: ...Chapter 4 UL ULC programming instructions 52 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 68: ...Appendix A System calculations 60 P N 3102213 EN REV 006 ISS 18FEB19 ...
Page 80: ...Appendix C Applications 72 P N 3102213 EN REV 006 ISS 18FEB19 ...