Edwards EXT250 Series Instruction Manual Download Page 25

© Edwards Limited 2007. All rights reserved. 

Page 19

Edwards and the Edwards logo are trademarks of Edwards Limited.

Installation

B722-01-880 Issue K

3.3.5

Backing connection

Use suitable vacuum tubing and connectors to connect the NW flange of the backing-port to your backing-pump. If 
necessary, use flexible pipe or bellows to reduce the transmission of vibration from the backing-pump to the EXT 
pump. 

We recommend that you use an Edwards two-stage backing-pump. The backing-pump can also be controlled by the 
EXC Controller. The minimum size of the backing-pump required is given in 

Table 1

. You may have to use a larger 

backing-pump if you run the pump at a high inlet pressure or high throughput or if you purge the pump with more 
than 25 sccm (0.42 mbar l s

-1

, 42 Pa l s

-1

) of purge gas.

Do not use the EXT pump with a backing pressure below 1 x 10

-4

 mbar (1 x 10

-2

 Pa). Lower backing pressures will 

increase the evaporation rate of the lubricating oil and so will reduce the life of the bearings.

3.4

Vent-valve connection and control

When you design your system and when you install a vent-valve, take note of the information in 

Section 1.3

 and in 

Section 2.5

. You can vent the EXT pump and your vacuum system by any of the following methods:

z

Use the manual vent-valve supplied.

z

Use a TAV5 solenoid vent-valve accessory (see 

Section 7.4.6

) in place of the manual vent-valve, together with 

a vent-restrictor, if necessary.

z

Use a TAV5 vent-valve connected to a convenient flange on your vacuum system, with a vent-restrictor, if 
necessary.

z

Use an alternative valve connected to your vacuum system, together with a vent-restrictor, if necessary.

If you use the manual vent-valve, you must open the vent-valve only after the EXT pump speed has fallen to 50% of 
full rotational speed.

If you use the TAV5 vent-valve, you can only vent the EXT pump when it is at full speed if the vacuum system has a 
volume of 5 litres or more. If the volume of your vacuum system is less than 5 litres, you can incorporate a suitable 
restrictor (see 

Table 9

and vent the pump when it is at full speed. Alternatively, if you do not fit a restrictor, you 

can use the EXC Controller to control the vent-valve and configure the EXC Controller to open the vent-valve after 
the EXT pump speed has fallen to 50% of full rotational speed: do not select the ‘Vent On Stop’ option (refer to the 
EXC Controller instruction manual for more information).

If you use another vent-valve, you must ensure that you have a suitable vent-restrictor fitted to suit your vacuum 
system to limit the rate of pressure rise: refer to 

Table 9

. If you do not have a suitable vent-restrictor fitted, you 

must open the vent-valve only after the speed of the EXT pump has fallen to 50% of full rotational speed.

If you connect the vent-valve to your vacuum system, select a point upstream of the EXT pump to prevent 
backstreaming of oil from the backing pump. Do not connect the vent-valve to the backing pipeline. Connect the 
inlet of the vent-valve to the vent gas supply (refer to 

Section 2.5

 for the vent gas specification).

Note:

If you use a vent-restrictor, you may find that the time required to vent your system is unacceptably long. 
You may be able to reduce the vent time if you use an unrestricted vent port without a vent-restrictor and 
wait until the pump speed has fallen to 50% of full rotational speed before you vent the pump.

Table 9 - Vent-valve orifice diameter (with atmospheric pressure at the inlet of the vent-valve) 

Vacuum system volume (l)

Orifice diameter (mm)

< 20
< 10

< 5

< 2.5

< 1.25

 1.0

 0.7

 0.5

 0.35

 0.25

Summary of Contents for EXT250 Series

Page 1: ...l Instruction Manual EXT70 and EXT250 Turbomolecular Pumps Description Item Number EXT70 NW40 B722 03 000 EXT70 NW50 B722 04 000 EXT70 ISO63 B722 01 000 EXT70 63CF B722 02 000 EXT250 ISO100 B736 01 00...

Page 2: ......

Page 3: ...3 Installation 15 3 1 Unpack and inspect 15 3 2 Typical installation 15 3 3 Connect to the vacuum system 17 3 3 1 Inlet screen 17 3 3 2 Mechanical fixing 17 3 3 3 Base mounting 18 3 3 4 Inlet connecti...

Page 4: ...4 7 4 5 FL20K foreline trap 34 7 4 6 TAV vent valve and vent port adaptor 34 7 4 7 ACX air cooler 34 7 4 8 Vibration isolators 35 7 4 9 PRX purge restrictor 35 7 4 10 VRX vent restrictor 35 For return...

Page 5: ...performance data 8 4 EXT250 performance data 9 5 Vent gas data 11 6 Purge gas data 12 7 Cooling water data 12 8 Checklist of items 15 9 Vent valve orifice diameter with atmospheric pressure at the inl...

Page 6: ...This page has been intentionally left blank B722 01 880 Issue K Page iv Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited...

Page 7: ...eout band Important safety information is highlighted as WARNING and CAUTION instructions you must obey these instructions The use of WARNINGS and CAUTIONS is defined below CAUTION Cautions are given...

Page 8: ...aring is lubricated from an oil reservoir and wick mechanism 9 EXT pumps are supplied with an inlet screen 2 fitted in the bore of the inlet flange The inlet screen protects you from the sharp blades...

Page 9: ...trademarks of Edwards Limited Introduction B722 01 880 Issue K Figure 1 Cross section view of EXT70 Turbomolecular Pump 1 Inlet flange 2 Inlet screen 3 Magnetic bearing 4 Safety bearing 5 Envelope 6 S...

Page 10: ...e Edwards logo are trademarks of Edwards Limited Introduction Figure 2 Cross section view of EXT250 Turbomolecular Pump 1 Inlet flange 2 Inlet screen 3 Magnetic bearing 4 Safety bearing 5 Envelope 6 S...

Page 11: ...e may be reduced We therefore recommend that you either limit the rate of pressure rise in accordance with Figure 3 or only open the vent valve after the EXT pump speed has fallen to 50 of full rotati...

Page 12: ...B722 01 880 Issue K Page 6 Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 13: ...m3 h 1 EXT250 DN100CF DN100ISO K Recommended backing pump A larger backing pump may be required for maximum throughput E2M0 7 EXT70 DN40NW DN50NW E2M1 5 EXT70 DN63CF DN63ISO K E2M5 EXT250 DN100CF DN1...

Page 14: ...e rotational speed drops below nominal Water cooling at 15 oC 9 x 10 1 mbar 9 x 101 Pa 9 x 10 1 mbar 9 x 101 Pa 9 x 10 1 mbar 9 x 101 Pa 9 x 10 1 mbar 9 x 101 Pa Air cooling at 35 o C 9 x 10 2 mbar 9...

Page 15: ...x 101 Pa 3 x 10 1 mbar 3 x 101 Pa Air cooling at 35 oC 3 x 10 2 mbar 3 x 100 Pa 3 x 10 2 mbar 3 x 100 Pa Nominal rotational speed 60000 r min 1 60000 r min 1 Standby rotational speed 42000 r min 1 420...

Page 16: ...use the pumps to pump oxygen and water vapour subject to the following conditions If you wish to pump a gas not in the list above contact your supplier for advice If you do not contact your supplier...

Page 17: ...t pumping time To reduce pump down times vent the pump with dry clean gases Figure 3 Maximum allowed rate of pressure rise during venting system pressure Pa mbar with the backing pump isolated against...

Page 18: ...um size of particulates 1 m Maximum concentration of oil 0 1 parts per million Allowable purge gas flow when required 20 to 100 sccm 0 33 to 1 67 mbar l s 1 33 to 167 Pa l s 1 Recommended purge gas fl...

Page 19: ...logo are trademarks of Edwards Limited Technical data B722 01 880 Issue K Figure 4 EXT70 Turbomolecular Pump dimensions mm 1 Vent valve 2 Earth ground screw 3 Backing port 4 Allowance for right angle...

Page 20: ...wards logo are trademarks of Edwards Limited Technical data Figure 5 EXT250 Turbomolecular Pump dimensions mm 1 Purge plug in purge port 2 Vent valve 3 Earth ground screw 4 Electrical supply connector...

Page 21: ...r Retain all packing materials for inspection Do not use the pump if it is damaged Check that your package contains the items listed in Table 8 If any of these items is missing notify your supplier in...

Page 22: ...ypical pumping system 1 Alternative position for vent valve 2 Vacuum system 3 High vacuum gauge 4 Inlet screen 5 EXT pump 6 Backing valve 7 Vacuum gauge 8 Flexible bellows 9 Foreline trap 10 Rotary ba...

Page 23: ...gure 7 with the Edwards logo uppermost Ensure that the dimples on the rim of the screen engage in the groove in the pump flange If necessary gently bend the tags of the screen outwards to ensure a tig...

Page 24: ...ust point vertically downwards 20o to reduce the risk of contamination from the backing pump oil Make sure that the pump inlet and all components fitted to the pump inlet are clean and dust free If th...

Page 25: ...you must open the vent valve only after the EXT pump speed has fallen to 50 of full rotational speed If you use the TAV5 vent valve you can only vent the EXT pump when it is at full speed if the vacu...

Page 26: ...al applications is 25 sccm 0 42 mbar l s 1 42 Pa l s 1 This flow will protect the pump when you pump oxygen in concentrations above 20 by volume 3 6 Electrical installation Always make the electrical...

Page 27: ...e water cooler can be used for the water supply or return connections 1 Push reinforced hose approximately 6 mm internal diameter over the ends of the riffled hose connectors on the water cooler 2 Att...

Page 28: ...B722 01 880 Issue K Page 22 Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 29: ...of the speed indicator on the front panel of the EXC Controller will light Note The first time you pump down the system to vacuum you must re tighten the bolts which secure the inlet flange refer to S...

Page 30: ...minal speed then the pump is stopped immediately or after a user defined time delay and the Fail LED on the EXC Controller lights z If pump rotational overspeed is detected by the EXC Controller the p...

Page 31: ...o drain all fluids does not apply to the lubricant in the EXT pump oil reservoirs 5 3 Rotor life The life of the EXT pump rotor is typically 40 000 to 50 000 cycles of acceleration to full speed and t...

Page 32: ...the correct links are made on the EXC Controller logic interface refer to the instruction manual supplied with the EXC Controller Check that any system interlocks are correctly made refer to the inst...

Page 33: ...large a chamber Increase the conductance or reduce the volume Is the backing pressure 0 2 mbar 20 Pa If not check for backing line leaks If the throughput is high you may need a larger backing pump Is...

Page 34: ...B722 01 880 Issue K Page 28 Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 35: ...desiccant 3 Store the pump in cool dry conditions until required for use When required prepare and install the pump as described in Section 3 4 Keep the pump upright at all times to prevent the drain...

Page 36: ...B722 01 880 Issue K Page 30 Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Page 37: ...nation service exchange repair rebuild and testing to factory specifications Equipment which has been serviced repaired or rebuilt is returned with a full warranty Your local Service Centre can also p...

Page 38: ...following EXC Controllers are available 7 4 3 Pump to controller cable A pump to controller cable must be used with each pump It is not supplied with the EXT Pump or the EXC Controller The following c...

Page 39: ...al accessories and spares 1 Vibration isolator 2 Bakeout band 3 Inlet flange seal supplied 4 EXT pump 5 Solenoid vent valve 6 DN10NW adaptor 7 Manual vent valve supplied 8 Vent port 9 Water cooler 10...

Page 40: ...alve is 24 V d c normally open and can be driven automatically from the EXC Controller The solenoid valve is fitted in place of the manual valve or alternatively can be fitted with an adaptor supplied...

Page 41: ...ate to the recommended flow of 25 sccm The restrictor is suitable for all EXT pumps fitted with a purge port 7 4 10 VRX vent restrictor Use a VRX fixed orifice vent restrictor to restrict the flow of...

Page 42: ...B722 01 880 Issue K Page 36 Edwards Limited 2007 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank...

Reviews: