Edwards A366-04-934 Instructions Manual Download Page 22

© Edwards Limited 2014. All rights reserved. 

Page 17

Edwards and the Edwards logo are trademarks of Edwards Limited.

Operation

A366-04-880 Issue A

4

Operation

4.1

Gas-ballast control

Use the gas-ballast control (

Figure 1

, item 1) to change the amount of air (or inert gas) introduced into the 

low-vacuum stage of the pump. Use of the gas-ballast will prevent the condensation of vapours in the pump. The 
condensed vapours would contaminate the oil.

Turn the gas-ballast control fully clockwise:

to achieve ultimate vacuum

to pump dry gases.

Turn the gas-ballast control anti-clockwise to open. Use the gas-ballast control fully open:

to pump high concentrations of condensable vapour

to decontaminate the oil.

When you operate the pump with the gas-ballast control open, there is an increased rate of oil loss from the pump.

4.2

Start-up procedure

If the oil is contaminated, or if the pump temperature is below 13°C, or if the supply voltage is more than 10% below 
the lowest voltage specified for the motor, the pump may operate at reduced speed for a few minutes.

1. Switch on the cooling water supply to the pump.

2. Switch on the electrical supply to the pump.

3. Check that the oil-level in the sight-glass drops slightly (3 to 5 mm) after start-up. This shows that the pump has 

primed with oil.

4. If the pump fails to prime, operate the pump with the inlet open to atmosphere for approximately 30 seconds. 

Then isolate the inlet and check that the oil-level drops 3-5 mm.

5. If you want to achieve ultimate vacuum, to pump condensable vapours or to decontaminate the pump oil, refer 

to the procedures in 

Section 4.3

4.4

 and 

4.5

 respectively. Otherwise, open the vacuum system isolation-valve.

4.3

To achieve ultimate vacuum

If the pump does not achieve the performance specified in 

Section 2

, make sure that this is not due to your system 

design before you contact your supplier or Edwards for advice. In particular, the vapour pressure of all materials used 
in your vacuum system, including pump oil, must be much lower than the specified ultimate vacuum of the pump. 
Refer to 

Section 5.12.2

 for a list of possible causes for failure to achieve the specified performance. The most 

common causes are:

Your pressure measurement technique or gauge head is unsuitable or the gauge head is faulty

You have used an oil other than the recommended oil, and the vapour pressure of the oil is higher than the 
specified ultimate vacuum of the pump.

WARNING

Do not block the pump outlet or allow the outlet pressure to rise above 1.5 bar absolute. If you do, 
the oil box may fracture: this may cause injury to people nearby.

Summary of Contents for A366-04-934

Page 1: ... 380 V 60 Hz 50 60 Hz three phase Azide prepared A366 07 934 E2M175 Rotary Vacuum Pump 380 400 V 50 Hz 230 460 V 60 Hz three phase Azide prepared A366 07 940 E2M275 Rotary Vacuum Pump 200 V 50 60 Hz 380 V 60 Hz 50 60 Hz three phase A367 04 934 E2M275 Rotary Vacuum Pump 380 400 V 50 Hz 230 460 V 60 Hz three phase A367 04 940 E2M275 Rotary Vacuum Pump 200 V 50 60 Hz 380 V 60 Hz 50 60 Hz three phase ...

Page 2: ... 13 3 7 Electrical installation 13 3 7 1 Connect the pump to your electrical supply 13 3 7 2 Check the direction of rotation 14 3 8 Connect the pump inlet to your system 14 3 9 Connect the pump outlet to your system 15 3 10 Gas ballast inlet connection 15 3 11 Leak test the system 15 4 Operation 17 4 1 Gas ballast control 17 4 2 Start up procedure 17 4 3 To achieve ultimate vacuum 17 4 4 To pump c...

Page 3: ...ccessories 29 7 1 Introduction 29 7 2 Service 29 7 3 Spares 29 7 4 Accessories 30 7 4 1 Inlet dust filter 30 7 4 2 Inlet catchpot 30 7 4 3 High capacity inlet dust filter 30 7 4 4 Inlet chemical trap 30 7 4 5 Outlet catchpot 30 7 4 6 Outlet mist filter clean applications 31 7 4 7 External oil filter 31 7 4 8 Solenoid operated gas ballast control valve 31 7 4 9 Thermostatic control valve 31 7 4 10 ...

Page 4: ...Vacuum pump and vacuum system safety P400 40 100 Ultragrade 15 19 and 20 oils P110 10 010 Vibration isolators A248 01 880 Oil return kits MF100 and 300 for E1M40 to E2M275 pumps A500 04 880 EOF300 external oil filter A500 09 880 EBV100S 300D and 300S gas ballast valves A500 18 881 EOF external oil filtration system A540 01 880 EOF adapter kit for E1M E2M175 and 275 A540 36 880 IT20K IT100 IT300 an...

Page 5: ...This page has been intentionally left blank A366 04 880 Issue A Page iv Edwards Limited 2014 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited ...

Page 6: ...y information is highlighted as WARNING and CAUTION instructions you must obey these instructions The use of WARNINGS and CAUTIONS is defined below CAUTION Cautions are given where failure to observe the instruction could result in damage to the equipment associated equipment and process The units used throughout this manual conform to the SI international system of units of measurement The follow...

Page 7: ...trademarks of Edwards Limited Introduction Figure 1 The E2M175 pump 1 Gas ballast control 2 External oil filter connections 3 Oil filler plug 4 Outlet port 5 Inlet port 6 Motor terminal box 7 Oil filter location 8 Oil pressure gauge 9 Oil level sight glass 10 Oil drain tap 11 Cooling water connections ...

Page 8: ...evel and condition of oil in the oil box through an oil level sight glass 9 An oil filler plug 3 is fitted at the top of the oil box An oil drain tap 10 is fitted at the bottom of the oil box The pump has an inlet port 5 with an ISO63 flange and an outlet port 4 with an ISO40 flange Connections for an external oil filter are provided 2 these are not shown in Figure 1 external oil filter outlet is ...

Page 9: ...e maintained inside the pump For remote control fit a solenoid operated gas ballast control valve available as an accessory from Edwards refer to Section 7 to the gas ballast inlet and open the gas ballast control Connect the gas ballast valve to your control system so that the valve is closed when the pump is switched off and if the electrical supply to the pump is interrupted Under these circums...

Page 10: ...placement m3h 1 50 Hz electrical supply 178 292 60 Hz electrical supply 214 350 Maximum Speed Pneurop m3h 1 50 Hz electrical supply 160 255 60 Hz electrical supply 196 306 Motor rotational speed r min 1 50 Hz electrical supply 1 440 1 440 60 Hz electrical supply 1 720 1 720 Ultimate vacuum without gas ballast partial pressure mbar Pa 10 4 10 2 10 4 10 2 without gas ballast total pressure mbar Pa 1...

Page 11: ...A366 04 880 Issue A Page 6 Edwards Limited 2014 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited Technical data Figure 2 Dimensions E2M175 mm ...

Page 12: ... Edwards Limited 2014 All rights reserved Page 7 Edwards and the Edwards logo are trademarks of Edwards Limited Technical data A366 04 880 Issue A Figure 3 Dimensions E2M275 mm ...

Page 13: ...erate with either the high range or low range electrical supply We endeavour to supply dual voltage motors preset to the highest of the selectable voltages For motor current information please refer to the motor rating plate Overall dimensions See Figure 2 E2M175 pumps and Figure 3 E2M275 pumps Degree of protection IEC 34 5 1981 IP55 Pump inlet port ISO63 flange with trapped O ring Pump outlet por...

Page 14: ...et for the following oil is available on request Hydrocarbon Pumps Recommended oil Ultragrade 70 PFPE Prepared Pumps Recommended oil To operate your pump when the ambient temperature is outside the limits specified in Section 2 1 or to optimise your pump performance when you pump condensable vapours you may need to use a different oil Fomblin 16 6 E2M175 E2M275 Oil capacity litres Maximum 25 28 Mi...

Page 15: ...A366 04 880 Issue A Page 10 Edwards Limited 2014 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank ...

Page 16: ...from the electrical supply so that they cannot be operated accidentally 3 2 System design considerations Consider the following points when you design your pumping system Use a suitable valve to isolate the pump from your vacuum system if you need to allow the pump to warm up before you pump condensable vapours or if you need to maintain vacuum when the pump is switched off Avoid high levels of he...

Page 17: ...any physical hazards For example trip hazards to personnel 3 5 Connect the pump to the cooling water Connect the two 3 8 in BSP internally threaded connections to the cooling water supply The maximum pressure that can be admitted to the cooling circuit is 3 bar and the recommended minimum cooling water supply flow rates at 20 C are Your pump will reach optimum operating temperature and will operat...

Page 18: ...to the pump Figure 4 Oil level indication 4 Refit the oil filler plug Tighten the plug firmly by hand Do not over tighten 3 7 Electrical installation 3 7 1 Connect the pump to your electrical supply CAUTION If your pump motor can be used with more than one voltage range you must ensure that the motor is configured for your electrical supply voltage If you do not you may damage the motor Note The p...

Page 19: ...9 or better 5 Pass the motor electrical supply cable through the cable gland 6 Connect the cables to the terminals as shown in the wiring diagram supplied in the motor terminal box 3 7 2 Check the direction of rotation CAUTION Ensure that the pump motor rotates in the correct direction If it does not the pump and your vacuum system can become pressurised 1 Watch the motor cooling fan through the m...

Page 20: ...bar gauge 1 5 bar absolute 1 5 x 105 Pa at full pump throughput In the following circumstances we recommend that you fit an oil mist filter to the pump outlet if you use the pump with the gas ballast control open if you operate the pump with an inlet pressure greater than 10 mbar for extended periods or if you frequently pump down from atmospheric pressure The mist filter will trap the oil exhaust...

Page 21: ...A366 04 880 Issue A Page 16 Edwards Limited 2014 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank ...

Page 22: ...ss drops slightly 3 to 5 mm after start up This shows that the pump has primed with oil 4 If the pump fails to prime operate the pump with the inlet open to atmosphere for approximately 30 seconds Then isolate the inlet and check that the oil level drops 3 5 mm 5 If you want to achieve ultimate vacuum to pump condensable vapours or to decontaminate the pump oil refer to the procedures in Section 4...

Page 23: ...scoloured it is contaminated with process vapours 1 Look at the condition of the oil in the sight glass Figure 1 item 9 If the oil is cloudy or discoloured continue with the procedure at Step 2 below 2 Close the vacuum system isolation valve 3 Turn the gas ballast control fully anti clockwise 4 Operate the pump until the oil is clear 4 6 Unattended operation The pump is designed for unattended ope...

Page 24: ... or inhale the thermal breakdown products of fluorinated materials which may be present if the pump has been heated to 310 C and above Fluorinated materials are safe in normal use but can decompose into very dangerous substances which may include hydrofluoric acid if they are heated to 310 C and above The pump may have overheated if it was misused or if it was in a fire Health and Safety Data shee...

Page 25: ... oil level while the pump is operating however you must switch off the pump and isolate the pump and other components in the pumping system from the electrical supply before you pour oil into the pump Refer to Figure 1 for the items in brackets 1 Check that the oil level in the sight glass 9 is between the MAX and MIN level marks indicated on the bezel of the sight glass see Figure 4 2 If the oil ...

Page 26: ...n the drain tap and allow the oil to drain into the container 5 If the oil drained from the pump is contaminated pour clean oil into the filler hole and allow it to drain out of the pump Repeat this step until the oil reservoir in the pump has been thoroughly cleaned 6 Close the drain tap 7 Fill a suitable container with clean oil and pour the oil into the filler hole until the oil level reaches t...

Page 27: ...e filter head plate 3 Remove the filter head plate and its gasket 5 from the pump end plate 1 4 Withdraw the filter adaptor assembly 2 with filter element attached from the pump end plate 5 Unscrew the filter element from the adaptor Clean the filter element in a suitable cleansing solution Allow the filter to dry 6 Screw the filter element firmly back into the adaptor 2 Replace the assembly back ...

Page 28: ...ove the four retaining screws 4 securing the gas ballast adjustor knob bearing plate 2 4 Withdraw the adjustor knob bearing plate from the pump end plate 1 5 Replace the felt filter elements 6 There are two for E2M175 275 pumps Clean the assembly before re fitting new filter elements by washing in a suitable cleaning solution Allow the assembly to dry 6 Fit the filter elements Replace the assembly...

Page 29: ...er 1 4 Clean the inlet filter by washing it in a suitable cleaning solution Allow the filter to dry 5 Replace items 1 and 2 6 Reconnect the pump to your vacuum system 7 Reconnect the electrical supply to your pump 5 8 Clean the motor fan cover You must keep the motor fan cover clean Your pump may overheat if the air flow over the motor is restricted 1 Isolate the pump from your electrical supply 2...

Page 30: ...fy a fault when you use this guide call your nearest Edwards Service Centre for help 5 12 1 The pump has failed to start The electrical supply fuse is blown The electrical supply voltage does not match the motor The outlet pipeline or the outlet filter if fitted is blocked The oil temperature is below 12 C The oil is too viscous The oil is contaminated The pump has seized after long storage The pu...

Page 31: ...illed the pump with the wrong type of oil The oil is contaminated The process gas is too hot or the throughput is too high 5 12 5 The vacuum is not fully maintained after the pump is switched off The gas ballast control is open Damaged or missing O ring Anti suckback valve faulty Shaft seals damaged Exhaust valve damaged 5 12 6 The pumping speed is poor The connecting pipelines are too small in di...

Page 32: ... drain from the pump 5 Purge your vacuum system and the pump with dry nitrogen and disconnect the pump from your vacuum system 6 Replace the oil as described in Section 5 4 paragraphs 3 to 8 7 Place and secure protective covers over the inlet and outlet ports 8 Store the pump in cool dry conditions until required for use When required prepare and install the pump as described in Section 3 If the p...

Page 33: ...A366 04 880 Issue A Page 28 Edwards Limited 2014 All rights reserved Edwards and the Edwards logo are trademarks of Edwards Limited This page has been intentionally left blank ...

Page 34: ... including equipment decontamination service exchange repair rebuild and testing to factory specifications Equipment which has been serviced repaired or rebuilt is returned with a full warranty Your local Service Centre can also provide Edwards engineers to support on site maintenance service or repair of your equipment For more information about service options contact your nearest Service Centre...

Page 35: ... through a glass cover at the top of the filter The filter is supplied with bolts washers and 63 mm co seal 7 4 4 Inlet chemical trap The inlet chemical trap see Figure 8 item 1 protects your pump against chemically active gases which may attack your pump or pump oil You must provide the trapping material suitable for your application The trapping material is contained in a removable fine mesh con...

Page 36: ... but removes abrasive particles down to 0 5 microns You must check that the external oil filter you choose is suitable for your application 7 4 8 Solenoid operated gas ballast control valve The solenoid operated gas ballast control valve see Figure 8 item 5 gives you automatic or remote control of gas ballast You can connect the valve to shut off gas ballast when the pump is switched off and so pr...

Page 37: ... is floor or frame mounted You must use flexible bellows or other flexible piping between inlet and outlet connections when you fit vibration isolators Figure 8 Accessories Product Item Number Vibration Isolators set of 4 A248 01 406 1 Inlet dust filter or inlet catchpot or high capacity inlet dust filter or inlet chemical trap 2 External oil filter 3 Outlet catchpot or outlet mist filter 4 Vibrat...

Reviews: