Table 8
General electrical data
Description
Rating
Units
Supply voltage 3-phase
Either 200 - 230 or 380 - 460 (see
rating plate)
V a.c.
Frequency
50/60
Hz
Wiring configuration
3 wire plus Earth (ground)
Voltage tolerance range
± 10%
Installation category
II (IEC 60664-1)
Input supply voltage unbalance
Should not exceed 2% when
assessed over any one minute
period
Short circuit current rating (when
installed with class T or class J fuses)
200
kA
Second protective earth (ground)
conductor
Must be fitted with cross
‑
sectional
area at least equal to phase
conductor size
Maximum permitted overcurrent protection for systems with the Han
®
K 4/4 mains
connector*
For 200 - 230 V systems
For 380 - 460 V systems
60
35
A
A
Typical earth leakage†
For 200 - 230 V systems
For GXS750/2600 and GXS750/4200
For all other GXS systems
9
<5
mA
mA
For 380 - 460 V systems:
For GXS750/2600 and GXS750/4200
For all other GXS systems
18
<10
mA
mA
* If the overcurrent protection is used above the ratings in
for the
systems with the Han®K 4/4, the minimum cable sizes no longer apply and you must
ensure that the pump cable size is appropriately rated and in accordance with local
legislation and electrical regulations. Ensure that the cable size is compatible with the
mains connector. Refer to
†Typical earth leakage values were measured at steady-state conditions.
Note that higher leakage currents may occur:
i) under transient conditions such as power on or pump acceleration
ii) with the abnormal supply configurations such as a missing or earthed phase or
unbalanced supply voltages.
Contact us for more information about the configuration requirements for earth leakage
reduction.
Recommended fuse type:
Fuse Class gG (IEC 60269), UL class T, class J or class RK5, Bussmann type JJS or
equivalent 12t characteristic rated to 600 V.
Page 22
M58800880_H - Technical data
Summary of Contents for 9773512584
Page 6: ...This page has been intentionally left blank ...
Page 87: ...Figure 19 GXS160 installation drawing Sheet 4 Page 83 M58800880_H Installation drawings ...
Page 178: ...This page has been intentionally left blank ...
Page 179: ...This page has been intentionally left blank ...
Page 180: ...edwardsvacuum com ...