562NSTT-OEM-ATT01 

Smoke Alarm with Heat Detection Sensor 

 

Product Introduction

 

This wireless photoelectric smoke alarm and heat detector  (product) 

continually monitors  operational status and provides  a visual trouble 
condition if it drifts out of the sensitivity range or fail internal diagnostics. 
This product meets National Fire Protection Association (NFPA) 72 field 
sensitivity testing requirements without the need for external meters. 

The alarm sensitivity level can be determined at the product. Another 
feature is built-in drift compensation that allows the product to adjust 
sensitivity automatically as it becomes dirty over time. The drift 
compensation feature dramatically increases the time between 

cleanings,  and  reduces  the chance of a nuisance alarm. Additional 
diagnostic information is activated by applying a magnet near the 
detector’s integral reed switch. This initiates a self-diagnostic routine 
and provides visual indication of sensitivity level, or if service is 

required. The product  is powered by long-life 3V Lithium batteries 
providing power to both the sensor and wireless transmitter.

 

 

This  wireless  product  works in conjunction with your wireless Control 

Panel, providing a local indication.  

 
 

About This Guide 

This User Guide describes how to install, operate, and maintain  this 
product. The User Guide is organized as you are intended to use this 

product, following the step-by-step instructions. 
 
Keep this document in a handy location and refer to it when you have 
questions about this product and its functions and features. Reading 

this guide is the only way to learn how to use your product wisely and 
to know how to react in the event of an alarm. 
 
 

1.

 

General Information

 

Congratulations on purchasing your Smoke Alarm with Heat Detection. 
The product is designed to be used with a Control Panel as part of the 
Fire and Life Safety signaling device. This product has an optical sensor 
capable of detecting smoke particles in the event of fire. It also contains 

an integrated heat sensor that is triggered if a room experiences a 
sharp rise in temperature in the event of fire. 
 

Parts List 

One Smoke Alarm 
Two CR123A lithium batteries 

Mounting Plate 
Mounting Screws and Anchors 
User Guide 
 

NFPA Guidelines 

NFPA 72, 17.5.3.1 Total (Complete) Coverage 

Where required, total coverage shall include all rooms, halls, storage 
areas, basements, attics, lofts, spaces above suspended ceilings, and 
other subdivisions and accessible spaces,  as well as the inside of all 

closets, elevator shafts, enclosed stairways, dumbwaiter shafts, and 
chutes.  
 

NFPA 72, 17.5.3.2 Partial or Selective Coverage 

Where codes, standards, laws, or authorities having jurisdiction require 
the protection of selected areas only, the specified areas shall be 
protected in accordance with this Code. 

 

 

NFPA 72, 17.5.3.3 Non-required Coverage 

Where installed, detection that is not required by an applicable law, 
code, or standard, whether total (complete), partial, or selective 
coverage, shall meet all of  the requirements of this Code, with the 
exception of the prescriptive spacing criteria of Chapter 17.  

 

NFPA 72, 17.6 Heat-Sensing Fire Alarms 

Heat-sensing fire alarms shall be installed in all areas where required 
by the NFPA codes and standards or by the authority having 

jurisdiction. 
 

NFPA 72, 29.5.1.1 Required Detection for Single-  and Multiple-
Station Smoke Alarms 

Approved, single-station smoke alarms shall be installed as follows:  

(1)

 

In all sleeping rooms  (applies to several occupancies 
including: one- and two-family dwellings; lodging or rooming 

houses; hotels, motels, and dormitories; apartment buildings; 
residential board and care facilities; and day-care homes) 
and guest rooms  (applies in the context of hotel and 
dormitory occupancies) 

(2)

 

Outside of each separate dwelling unit (applies to one- and 
two-family dwellings and dwelling units of apartment 
buildings, including condominiums) sleeping area, within 21 ft 
(6.4 m) of any door to a sleeping room, with the distance 

measured along a path of travel 

(3)

 

On every level of a dwelling unit, including basements 

(4)

 

On every level of a residential  board and care occupancy 
(small facility), including basements and excluding crawl 

spaces and unfinished attics 

(5)

 

In the living area(s) of a guest suite (an accommodation with 
two or more contiguous rooms comprising a compartment, 
with or without doors between such rooms, that provides 

living, sleeping, sanitary, and storage facilities) 

(6)

 

In the living area(s)  (any normally occupiable space in a 
residential occupancy, other than sleeping rooms or rooms 
that are intended for combination sleeping/living, bathrooms, 

toilet compartments, kitchens, closets, halls, storage or utility 
spaces, and similar areas)  of a residential board and care 
occupancy (small facility) 

 

 

2.

 

Mounting Guideline

 

This  product  is a member of  a reliable, high-quality product family 
using the latest technology available. Review the information in this 
section to ensure you get the most out of the product. The information 
in this User Guide is in accordance with NFPA 72. 

 

Pre-installation Considerations 

Install the smoke alarm in accordance with NFPA Standard 72, 
Chapters  17 and  29. Depending on the application, you may need to 

reference other chapters of NFPA 72 or NFPA 101. 

 

Choosing an Installation Location 

When choosing an installation location, consider: 

o

 

Use of structure and type of construction 

o

 

Contents you want to protect and their burning characteristics 

o

 

Human occupancy 

o

 

Total area to be monitored 

o

 

Ceiling height and surface condition 

o

 

Air movement and vent locations 

o

 

Obstructions 

o

 

Deflections 

 