background image

 

 

 

 

Technical Bulletin  

 

SuperDuct Signature Duct Smoke Detector 

Operation 

Controls and indicators 

Magnetic

test switch

Alarm

Power

 

Figure 3: Duct smoke detector controls and indicators 

The controls and indicators on the duct smoke detector (see 
Figure 3) are as follows: 
 

Control or indicator  Description 

Magnetic test switch 

Activates (alarms) the detector when it 
is in the normal state. The switch is 
inoperative when the detector is in the 
trouble state. 

Alarm LED 

Indicates the detector is in the alarm 
state as follows: 

Flashes at a continuous rate if the first 
detector in alarm 

Flashes intermittently if not the first 
detector in alarm 

Power LED 

Off when the detector is in the alarm 
state 

Flashes intermittently when the 
detector is in the normal state  

Notes 

1. The intermittent flash indicates each time the control panel 
polls the detector 

2. Both LEDs are on continuously when the detector is in alarm 
and in the standalone mode. 

Normal state 

The duct smoke detector operates in the normal state in the 
absence of any trouble conditions and when its sensing 
chamber is free of smoke. 

Alarm state 

The duct smoke detector enters the alarm state (is activated) 
when the amount of smoke in its sensing chamber exceeds its 
alarm threshold setting or when an alarm test is initiated. Upon 
entering the alarm state, the duct smoke detector’s: 

• 

Alarm LED turns on 

• 

Common alarm relay contacts switch positions 

• 

Remote alarm LED output turns on (is activated) 

In addition, the duct smoke detector generates an alarm or 
supervisory event message depending on the device type with 
which it is configured.  

Trouble state 

The duct smoke detector enters the trouble state under the 
following conditions: 

• 

Its cover is removed and 20 minutes pass before it is 
properly secured 

• 

Its environmental compensation limit is reached  

• 

The detector is 100% dirty 

• 

An internal detector fault is present  

Upon entering the trouble state, the duct smoke detector 
generates an event message based on the type of trouble 
encountered. 

Note: 

All troubles are latched by the duct smoke detector. You 

must clear the trouble condition then reset the control panel in 
order to restore the detector to its normal state. 

Installation 

Installation guidelines 

To ensure correct operation, install the duct detector using the 
following guidelines: 

• 

Locate the detector so its sampling tube is positioned in a 
straight length of square duct between six and ten duct 
widths from any bends or obstructions as shown in the 
diagram below. See Figure 7 for detector dimensions. 

Summary of Contents for 3100738

Page 1: ...e following standards NFPA 70 National Electrical Code NFPA 72 National Fire Alarm Code NFPA 90A Installation of Air Conditioning and Ventilating Systems UL 268A Smoke Detectors for Duct Applications...

Page 2: ...es are stored in nonvolatile memory This information can be retrieved and reviewed when desired Air is introduced to the duct smoke detector s sensing chamber through a sampling tube that extends into...

Page 3: ...rm red Power green Common alarm relay Unsupervised and power limited Quantity 1 Type Form C Ratings 2 0 A at 30 Vdc resistive Operating voltage 15 2 to 19 95 Vdc Operating current Standby 45 A Alarm 4...

Page 4: ...ed when the amount of smoke in its sensing chamber exceeds its alarm threshold setting or when an alarm test is initiated Upon entering the alarm state the duct smoke detector s Alarm LED turns on Com...

Page 5: ...velocity 2 Drill the mounting holes 3 Assemble the detector 4 Mount the detector on the HVAC duct 5 Verify the detector pressure differential Installing the sampling tube from the front of the detecto...

Page 6: ...ion for more than 5 seconds Using an SD TRM hold the SD MAG test magnet to the target area for more than 5 seconds Once activated verify the following The detector s Alarm LED is flashing If connected...

Page 7: ...oft bristle brush remove loose dirt and debris from inside the detector housing and cover Use isopropyl alcohol and a lint free cloth to remove dirt and other contaminants from the gasket on the detec...

Page 8: ...uct Signature Duct Smoke Detector 8 70 in 22 1 cm 7 75 in 19 7 cm 8 15 in 20 7 cm 2 28 in 5 78 cm 5 45 in 13 84 cm 5 40 in 13 72 cm 1 38 in 3 51 cm 1 90 in 4 83 cm 3 08 in 7 82 cm 1 60 in 4 06 cm Figu...

Page 9: ...Active SIGA LED 1 Notes 1 No more than one remote test station or LED indicator can be connected to the detector at the same time Wiring is unsupervised Maximum wire resistance is 10 ohms per wire Pow...

Reviews: