Fault 

Indication 

Action 

Communication 

The board ON LED flashes 
quickly 

Check that all board 
connections are 
secure. 

Check the board 
configuration at the 
control panel. 

Power supply 

The board ON LED and all 
board OUT LEDs flash 
slowly 

Check that the power 
supply of the board is 
> 21 V. 

Check that jumper J3 
is correctly configured 
for the power source 
in use. 

Output 

The board OUT LED 
flashes slowly 

Locate and fix the 
fault on the 
corresponding output. 
Reset the control 
panel if required (see 
note).

 

Board failure 

The board ON LED and all 
board OUT LEDs flash 
quickly 

Replace the board. 

 

Note: 

For the supervised expansion board all faults must be 

reset manually by pressing the Reset button on the control 
panel interface. Open and short circuit faults in Class B wiring 
are reset automatically when the output is deactivated. 

Specifications 

 

Operating voltage 

24 VDC 

Relay contact rating 

2A at 30 VDC 

Operating temperature 

−5 to +40ºC 

Storage temperature 

−5 to +70ºC 

Relative humidity 

10 to 95% noncondensing 

Dimensions 

127 × 76 mm 

Number of boards that can be installed 
 

Two- and four-zone control panels 

 

Eight-zone control panels 

 

Evacuation panels 

 

Extinguishing panels 

 
2 max. 
4 max.  
4 max. 
4 max. 

Weight 
 

2010-1-RB 

 

2010-1-SB 

 
46g 
48g 

Control panel current consumption [1] 
 

Two- and four-zone control panels 

 

Eight-zone control panels 

 

Evacuation control panels 

 

Extinguishing control panels 

Maximum current 
160 mA 
300 mA 
300 mA 
300 mA 

2010-1-RB current consumption per 
board 
 

Standby  

 

Activated 

 
 
15 mA max. 
45 mA max. 

2010-1-SB current consumption per 
board  
 

Standby  

 

Activated 

 
 
15 mA max. 
1 A max. [2]  
300 mA max. (at 40ºC) [3] 

2010-1-SB current consumption per 
output 
 

Standby  

 

Activated 

 
 
2 mA max. 
250 mA max.(at 25ºC) 

Output voltage for the 2010-1 SB
 

Standby 

 

Activated 

 

 

Nominal output voltage 

 

 

Maximum output voltage 

 

 

Minimum output voltage 

 
-15 VDC 
 
+24 VDC 
+28 VDC 
+21 VDC 

[1] Maximum current provided by the panel for all installed boards. 
[2] With power supplied by an external 24 VDC power supply. 
[3] With power supplied by the control panel. 

Regulatory information 

 

Certification 

 

Manufacturer 

UTC CCS Manufacturing Polska Sp. Z o.o. 
Ul. Kolejowa 24, 39-100 Ropczyce, Poland. 

Authorized EU manufacturing representative: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands. 

Year of first CE 
marking 

09 

Contact Information 

For contact information, see www.utcfssecurityproducts.eu. 

DE: Installationsanleitung 

Bezeichnung 

Dieses Dokument enthält Installationsinformationen für die 
folgenden Erweiterungsplatinen: 

• 

2010-1-RB-Erweiterungsplatine mit vier Relaisausgängen 

• 

2010-1-SB-Erweiterungsplatine mit vier überwachten 
Ausgängen 

Relaiserweiterungsplatine 

Die Relaiserweiterungsplatine verfügt über vier spannungsfreie 
Ausgänge, die jeweils für 2 A bei 30 V DC ausgelegt sind. Die 
Relais können Meldergruppen zugewiesen oder zur 
Aktivierung auf Grundlage von Systemereignissen 
programmiert werden. 

Überwachte Erweiterungsplatine 

Die überwachte Erweiterungsplatine verfügt über vier 
überwachte Ausgänge mit je 24 V DC. Die überwachten 
Ausgänge können als Signalgeberausgang, 
Hauptmelderausgang, Löschanlagenausgang oder 
Störungswarnungsausgang konfiguriert, Meldergruppen 
zugewiesen oder zur Aktivierung auf Grundlage von 
Systemereignissen programmiert werden. 

Bei Konfiguration als Signalgeber-, Hauptmelder-, 
Löschanlagen- oder Störungswarnungsausgang werden über 
die Steuerzentrale entsprechende Anzeigen und die 
verfügbaren Steuerungsoptionen bereitgestellt. 

Bei Konfiguration als universelle akustische Signalgeber-
Ausgangsplatine werden Kurzschlüsse und Unterbrechungen 
über die allgemeine LED "Störung" und die LED "E/A 
Erweiterung Störung/Abgeschaltet" auf der Oberfläche der 
Steuerzentrale angezeigt. 

Summary of Contents for 2010-1 RB

Page 1: ... 2013 UTC Fire Security All rights reserved 1 20 P N 501 414000 1 41 REV 04 10 ISS 25NOV13 2010 1 RB SB Expansion Board Installation Sheet EN DE ES FR IT NL PT SV 1 2 3 4 5 6 ...

Page 2: ...rs of each board as shown in Figure 2 before pushing the boards into the appropriate slots 4 To install a supervised expansion board configure the power source if required See Configuration 5 Replace the control panel PCB and reconnect all battery and power supply cables 6 Connect the expansion board in slot A to the control panel PCB as shown in Figure 3 Wiring Relay expansion board To wire the r...

Page 3: ...the 2010 1 SB Standby Activated Nominal output voltage Maximum output voltage Minimum output voltage 15 VDC 24 VDC 28 VDC 21 VDC 1 Maximum current provided by the panel for all installed boards 2 With power supplied by an external 24 VDC power supply 3 With power supplied by the control panel Regulatory information Certification Manufacturer UTC CCS Manufacturing Polska Sp Z o o Ul Kolejowa 24 39 ...

Page 4: ...n Siehe Abbildung 6 Achtung Verwenden Sie niemals den AUX Ausgang für die Stromversorgung von Erweiterungsplatinen die an dieselbe Steuerzentrale angeschlossen sind da dadurch die Hardware der Steuerzentrale beschädigt werden kann Installation von Ausgängen der Klasse B Zum Abschließen ist für alle Ausgänge ein Endwiderstand mit 15 kΩ erforderlich Wird ein Ausgang nicht verwendet muss der Endwider...

Page 5: ...stand Aktiviert Nominale Ausgangsspannung Maximale Ausgangsspannung Minimale Ausgangsspannung 15V DC 24 V DC 28 V DC 21 V DC 1 Von der Zentrale für alle installierten Platinen gelieferter Maximalstrom 2 Mit Spannung von einer externen Spannungsquelle mit 24 V DC 3 Mit Stromversorgung durch die Zentrale Regulatorische Informationen Zertifizierung Hersteller UTC CCS Manufacturing Polska Sp Z o o Ul ...

Page 6: ... el hardware de la central Para instalaciones de salida de clase B Todas las salidas requieren una resistencia final de línea de 15 kΩ para la terminación Si una salida no se usa la resistencia final de línea de 15 kΩ debe instalarse en los terminales de las salidas no utilizadas Para instalaciones de salida de clase A Todos los grupos de salidas OUT1 2 OUT3 4 requieren una resistencia final de lí...

Page 7: ...sión suministrada por el panel de control Información normativa Certificación Fabricante UTC CCS Manufacturing Polska Sp Z o o Ul Kolejowa 24 39 100 Ropczyce Polonia Representante de fabricación autorizado en Europa UTC Fire Security B V Kelvinstraat 7 6003 DH Weert Países Bajos Año inicial de marcado CE 09 Información de contacto Para obtener información de contacto consulte www utcfssecurityprod...

Page 8: ...igne de 4 7 kΩ 1 1 4 W pour leur terminaison Si un groupe de sorties n est pas utilisé la résistance de fin de ligne de 4 7 kΩ 1 1 4 W doit être montée sur les bornes du groupe de sorties non utilisé Consultez le guide d installation de la centrale pour tout autre renseignement sur le câblage de Classe A Respectez la polarité pour toutes les connexions Configuration Configuration de l alimentation...

Page 9: ... schede di espansione Scheda di espansione 2010 1 RB con quattro uscite relè Scheda di espansione 2010 1 SB con quattro uscite supervisionate Scheda di espansione relè La scheda di espansione relè dispone di quattro uscite relè prive di tensione ciascuna con capacità di 2 A a 30 V CC I relè possono essere assegnati a zone di rivelazione o programmati per l attivazione in funzione di eventi di sist...

Page 10: ...te non utilizzato Per i requisiti aggiuntivi del cablaggio di classe A fare riferimento al manuale di installazione della centrale Rispettare la polarità per tutti i collegamenti Configurazione Configurazione dell alimentatore Se i requisiti di alimentazione superano la corrente massima che la centrale è in grado di fornire collegare un alimentatore esterno da 24 V CC e rimuovere il ponticello J3 ...

Page 11: ...atie van de volgende uitbreidingsmodules 2010 1 RB uitbreidingsmodule met vier relaisuitgangen 2010 1 SB uitbreidingsmodule met vier bewaakte uitgangen Relaisuitbreidingskaart De relaisuitbreidingskaart heeft vier potentiaalvrije relaisuitgangen die elk geschikt zijn voor 2 A bij 30 VDC De relais kunnen worden toegewezen aan detectiegroepen of geprogrammeerd voor activering op basis van systeemgeb...

Page 12: ... Voor extra Klasse A aansluitvereisten raadpleegt u de installatiehandleiding van uw centrale Let bij alle aansluitingen op de polariteit Configuratie Configuratie van de voedingsbron Als de voedingsvereisten de maximum waarde overschrijden die de centrale kan leveren sluit u een externe voedingseenheid van 24 VDC aan en verwijdert u jumper J3 afbeelding 4 Jumper J3 Voedingsbron AAN standaard De c...

Page 13: ...Placa de expansão de relé A placa de expansão de relé possui quatro saídas de relé sem tensão cada uma com a capacidade de 2 A a 30 VDC Os relés podem ser atribuídos às zonas de detecção ou programadas para activação com base nos eventos do sistema Placa de expansão com supervisão A placa de expansão com supervisão tem quatro saídas supervisionadas cada uma com 24 VDC As saídas supervisionadas pod...

Page 14: ...nte de alimentação Se os requisitos de alimentação forem superiores à corrente máxima que o painel pode fornecer ligue uma fonte de alimentação de 24 VDC externa e retire o jumper J3 Figura 4 Jumper J3 Fonte de alimentação ON Colocado 24 VDC é fornecido pelo painel de controlo OFF Desligado 24 VDC é fornecido por uma fonte de alimentação externa Funcionalidade da placa de expansão A funcionalidade...

Page 15: ... V DC Relän kan tilldelas sektioner eller programmeras för aktivering vid systemhändelser Övervakade expansionskort Det övervakade expansionskortet har fyra övervakade utgångar på vardera 24 V DC De övervakade utgångarna kan konfigureras som larmdons brandöverförings brandskydds eller felvarningsutgångar och kan tilldelas detektionssektioner eller programmeras för aktivering vid systemhändelser Nä...

Page 16: ...s funktioner och händelseprogrammering konfigureras i centralapparatens gränssnitt Se installationsmanualen för din centralapparat för mer information Underhåll Normalt underhåll består av en årlig inspektion Modifiera inte den inre kabeldragningen eller kretsarna på kortet Felindikeringar för expansionskort Övriga feldiagnoser indikeras av dioderna ON OUT1 OUT2 OUT3 och OUT4 på expansionskortet e...

Page 17: ...g Maximal utspänning Minimal utspänning 15 V DC 24 V DC 28 V DC 21 V DC 1 Maxström som ges av centralen för alla installerade kort 2 Med en extern strömförsörjning på 24 V DC 3 Strömförsörjs från centralapparaten Information om regler och föreskrifter Certifiering Tillverkare UTC CCS Manufacturing Polska Sp Z o o Ul Kolejowa 24 39 100 Ropczyce Polen Auktoriserad representant för tillverkning i EU ...

Page 18: ...18 20 P N 501 414000 1 41 REV 04 10 ISS 25NOV13 ...

Page 19: ...P N 501 414000 1 41 REV 04 10 ISS 25NOV13 19 20 ...

Page 20: ...20 20 P N 501 414000 1 41 REV 04 10 ISS 25NOV13 ...

Reviews: