EN • REV 002 • ISS 16MAR18

 

 

3 / 4 

Wiring 

See 

Figure 4. Connect all wiring in accordance with national electrical 

codes and applicable local requirements.

 

Caution:

 Equipment hazard. To avoid equipment damage, ensure that 

the signal voltage does not exceed the volta

ge rating of the device. 

Figure 4: Wiring diagram 

 

(1)

  Horn-

strobe

 

I

−  

 

(2)

  Horn-

strobe

 

I

N + 

(3) 

 

Marking indicates the signal polarity 

required to activate the device 

(4) 

 Horn-

strobe

 OUT 

− 

 

(5) 

 Horn-

strobe

 OUT + 

(6) 

 Not used  

Figure 5: UL 1971 minimum light output (% of rating vs. angle) 

 

(1)

 

Angle

 

(2)

  Percentage of rated output 

Note: Horizontal plot 

Maintenance 

Do not change the factory finish.

 

Perform a visual inspection and an operational test twice a year, or as 

directed by the local authority having jurisdiction.

 

This unit is not serviceable or repairable. Should the unit fail to 

operate, contact the supplier for replacement.  

Specifications 

 
Operating voltage 

Horn-

strobe

 

 

24 VDC, 24 VFWR nominal

 

Dimensions (W × H × D)

 

5.6 × 8.5 × 1.4 in. (142 × 216 × 36 mm)

 

Sound level output

 

See

 

Table

 4, 

Table

 5, 

Table

 

6

, an

Table

 7 

Horn tone 

3.2 kHz

 

Strobe operating current

 

See Table

 11 

Light output 

See Table

 8, 

Table

 

9

Table

 10, and 

Figure 5 

Wire size 

12 to 18 AWG (0.75 to 2.50 mm²)

 

Compatible electrical box

 

 

Outdoor 

 

Indoor

 

 

Model 449

 

4 in. square by 1.5 in. deep box

 

Operating environment 

 

Temperature 

 

Relative humidity

 

  

−40 to 151°F (−40 to 66°C)

 

0 to 95% noncondensing

 

 

Table 4: Sound level output (dBA), per UL 464 
Volume Setting 

16V 

24V 

33V 

Continuous High 

89.7

 

94.7

 

97.4

 

Continuous Low 

85.4 

89.5

 

92.5

 

Temporal High 

84.2 

90.5

 

93.5

 

Temporal Low 

81.7 

85.4 

88.1 

dBA = Decibels, A

-weighted 

UL 464: Sound level output measured in a reverberant room at 10 ft. 

(3.05

 

m)

 

 

Table 5: Sound level output (dBA), per CAN/ULC-S525 
Volume setting 

16V 

24V 

33V 

Continuous High 

94.0

 

99.6

 

102.9

 

Continuous Low 

92.8

 

97.2

 

98.6

 

Temporal High 

96.5

 

100.5 

104.2 

Temporal Low 

90.3

 

94.2

 

97.0

 

dBA = Decibels, A

-weighted. 

CAN/ULC

-

S525: Sound level output measured in an anechoic room at 

10ft (3.05m).

 

 

Table 6: Directional sound characteristics (horizontal pattern), per 

CAN/ULC-S525 
Angle (°) [1] 

Sound output (dBA)  

90 (Ref)

 

0 (Ref) 

 

60 and 115

 

45 and 132 

−6

 

[1] Angles are measured from a perpendicular axis; positive angles to 

the right. 

 

(4)

(5)

(6)

(1)

(2)

(3)

100

9

5

9

0 85 80 75 70

6

5

6

0 55 50 45 40 35 30 25 20 15 10 5 0 5 10 15 20 25 30 35 40 45 50 55

6

0

6

5 70 75 80 85

9

0

9

5

100

0 5 10 15

20

25

30

35

40

45

50

55

60

65

70

75

80

85

90

-5

-10

-15

-20

-25

-30

-35

-40

-45

-50

-55

-60

-65

-70

-75

-80

-85

-90

firealarmresources.com

Reviews: