2 / 2 

 

P/N 3101677-EN • REV 04 • ISS 16NOV15 

Figure 2: Installing the cable tie over data cable connections on a 
chassis rail 

 

(1)  Cable tie 
(2)  Data cable connections 

Securing the SA-ETH Ethernet card ribbon cable in 
analog/addressable fire alarm cabinets 

Caution: 

Equipment damage hazard. This product is sensitive to 

electrostatic discharge (ESD). To avoid damage, follow accepted ESD 
handling procedures. 

When using the BC-1 battery cabinet to house standby batteries for 
analog/addressable fire alarm cabinets with an SA-ETH Ethernet card 
installed, you must secure its ribbon cable to ensure that the cable 
does not disconnect.  

Figure 2 provides an example of how to secure the cable. If you 
choose a different method, make sure the cable cannot move. 

To secure the SA-ETH Ethernet card ribbon cable: 

1.  Open an alcohol wipe and clean the top of the ferrite on the 

SA-ETH ribbon cable where a 1-inch square cable mount will be 
placed. See Figure 3. 

2.  Clean an area on the cabinet rear wall for a second cable mount. 

The area must be located so a cable tie can loop from the ferrite 
cable mount to the wall cable mount. 

3.  Remove the adhesive paper from the backs of the cable mounts 

and attach the mounts to the cleaned areas. 

4.  Thread a cable tie through the slot in the cable mount on the 

ferrite, and then through the cable mount on the wall. 

5.  Loop the cable tie back and tighten it. Cut off any excess. Do not 

overtighten the cable tie, to avoid pulling the cable mounts away 
from their surfaces. 

Figure 3: Installing the cable mounts and cable tie for an SA-ETH 
ribbon cable 

 

(1)  Cable mount on the cabinet rear wall 
(2)  Cable tie 
(3)  Cable mount on the ribbon cable ferrite clamp 

Contact information 

For contact information, see www.edwardsfiresafety.com. 