4
/ 10
P/N 3100010-
EN • REV 09 • ISS 14JAN15
Figure 5: Wiring the 5540M series tone generator
(1)
Power and earth ground leads, black and white or black for power,
yellow striped green for earth ground
(2)
Plastic cable ties
(provided).
Use to separate power leads from
signal and tone initiating leads.
(3
)
Signal/Tone initiating leads to be connected to the input board
(4)
Audio output wiring to be connected to the audio coupler board of
5532M. Double wire, shielded cable with braid or drain connected
to earth ground lead of 5540. Up to 2,500 5532M series can be
connected in parallel to a single 5540M series unit.
Figure 6: Wiring the 5540MV series tone generator with voice
messaging
(1)
Power and earth ground leads, black and white or black for power,
yellow striped green for earth ground
(2)
Plastic cable ties
(provided). Use to separate power leads from
signal and tone initiating leads.
(3
)
Signal/Tone initiating leads to be connected to the input board
(4)
Audio output wiring to be connected to the audio coupler board of
5532M. Double wire, shielded cable with braid or drain connected
to earth ground lead of 5540.
Figure 7: Wiring an open collector transistor to tone generator
input board
(1)
On the input
board
(2)
5 VDC to 24 VDC +/− 1% (from customer circuit)
(3)
Customer circuit
Figure 8: Wiring multiple dry relay contacts to 24 V tone generator
input board (Method 1*)
(1)
On the input
board
*
Consult
Applications Engineering for compatibility with earlier versions
of Adaptatone
(1)
(2)
(3)
(4)
(1)
(2)
(3)
(4)
IN4
N
+VS
GND
IN3
IN2
IN1
(1)
(2)
(3)
K4
K3
K2
K1
IN1
IN2
IN3
IN4
N
+VS
(1)
GND