REMARKS ON INSTALLATION

Note that:
•  The appliance may only be installed by a qualified 

technician authorised to issue the declaration of 
conformity.

•  The appliance must be installed and operated 

in compliance with local and national law and 
European regulations. The applicable Italian 
regulation is UNI 10683.

•  If installed in a condominium, the appliance must 

be approved by the administrator.

We give some general instructions below, however 
these do not obviate the need to comply with local 
regulations and do not affect the installer’s liability for 
the installation.

Checking the suitability of the installation 
space 

•  The room must have a volume of at least 30 m

3

•  The floor must be able to bear the weight of the 

product and its accessories.

•  Level the appliance
•  The appliance may not be installed in a bedroom, 

bathroom or in the same room as other equipment 
which draws air for combustion from the room 
itself, or in any area with an explosive atmosphere. 
Any extraction fans operating in the same room or 
area as the product, may affect its draw.

•  In Italy, check the compatibility pursuant to UNI 

10683 and UNI 7129 in the presence of gas fired 
products.

Protection from heat and safety clearances

All adjacent surfaces must be protected against 
overheating.The insulation to be used will depend on 
the type of surface in question.Observe the following 
clearances from flammable materials:
- 10 cm at the sides and back

Positioning the product

The product is designed to operate in all climatic 
conditions. In special circumstances, such as strong 
wind, its safety equipment may switch the fireplace off.
Contact the authorised Edilkamin Technical Assistance 
Centre.

INSTALLATION

FLUE SYSTEM 
(Fumes duct, flue and chimney pot)

Thsi chapter has been drawn up pursuant to European 
regulations EN 13384, EN 1443, EN 1856 and EN 
1457. The installer must observe both these and any 
other local regulations. This manual does not in any 
way substitute such regulations.The product must 
be connected to a flue system which ensures that 
the fumes produced by combustion are exhausted in 
complete safety.
Before positioning the product, the installer must 
check that the flue pipe is properly rated.

FUMES DUCT, FLUE

The fumes duct (which connects the hearth’s fumes 
outlet with the flue) and the flue itself must, among 
other regulatory requirements:
•  receive the fumes from a single product (the outlets 

of multiple appliances may not be conveyed into 
a single flue) 

•  be routed vertically for the most part
•  have no downwards sloping sections
•  preferably have a circular internal cross section, or 

with a ratio of the sides of less than 1.5

•  terminate at roof level with a proper chimney pot: 

the flue may not discharge directly from the wall 
or into an enclosed space, even if the space in 
question is open to the sky

•  be made of material rated fire reaction class A1 per 

UNI EN 13501 or analogous national regulations.

•  be certified, with a chimney plate if metal
•  be of uniform cross section or vary in cross section 

only immediately after the outlet, not at some mid 
point of its length

THE FUMES DUCT

Further to the general prescriptions for the fumes duct 
and flue, the fumes duct:
•  may not be made of flexible metal material
•  must be insulated, if routed through unheated 

areas or outdoors

•  must not be routed through rooms in which the 

installation of combustion heat generators is 
prohibited, or subject to fire hazard, or which 
cannot be inspected.

•  must enable the recovery of soot and be open for 

inspection

•  must have at most 3 bends, through an angle of 

no more than 90°

•  must have a single horizontal section of length 

no more than 3 metri, depending on the draw. 
Note in any case that long sections promote the 
accumulation of dirt and are harder to keep clean.

Summary of Contents for 807970

Page 1: ...PELLKAMIN 12 PELLET FIREPLACE UK Installation use and maintenance 807970 807980...

Page 2: ...ce declaration DoP EK No 137 Rating plate reference Moreover the company hereby declares that PELLKAMIN 12 complies with the requirements in the following European Directives 2014 35 EC Low Voltage Di...

Page 3: ...ted up for the first time commissioned by a qualified Edilkamin technician In Italy commissioning by an authorised technician is required by UNI 10683 and is recommended in all countries to ensure bes...

Page 4: ...THAN WOOD PELLETS IN THE HEARTH The product may be soiled the flue may catch fire and environmental damage may ensue cleaning the hearth when hot DO NOT CLEAN THE HEARTH WITH A VACUUM CLEANER WHILE IT...

Page 5: ...loading trapdoor PELLKAMIN 12 with ducted ventilation and a pellet loading drawer 93 60 5 2 5 5 8 cm smoke outlet 87 5 12 75 93 60 5 2 5 THE REAR THAT IS THE SAME FOR ALL 2 MODELS 10 cm ducted air 87...

Page 6: ...for the vents V NOT SUPPLIED WITH THE PRODUCT BUT ARE ESSENTIAL E hole for ventilation air recovery a 10x10 cm hole in the side of the cladding MEASUREMENTS cm OF HOLES ON PLASTERBOARD Vents V 19 x 18...

Page 7: ...iameter male 50 mm Weight including packaging cod 807970 220 kg cod 807980 270 kg kg TECHNICAL DATA FOR RATING THE FLUE which must in any case satisfy the requirements of this sheet and the installati...

Page 8: ...atory fashion CONTENTS OF PACKAGE The packaging varies according to the Pellkamin version The packages are described in the Packaging section The air outlet vents are not included but you can choose t...

Page 9: ...facilitate handling the Pellkamin 12 is fitted with handles B Do not use the air intake or fumes outlet to handle the appliance This may lead to slight misalignments TO UNPACK THE PRODUCT undo screws...

Page 10: ...t loading trapdoor the Pellkamin frame the trapdoor loading system the two compensation vents the inlet surround Version cod 807980 with pellet loading drawer the Pellkamin frame the two compensation...

Page 11: ...ent with regulatory grounding system Hole for ventilation air a hole at least 10x10 cm in size preferably on the side of the covering Ducting for ventilation air always channel the ventilation warm ai...

Page 12: ...to European regulations EN 13384 EN 1443 EN 1856 and EN 1457 The installer must observe both these and any other local regulations This manual does not in any way substitute such regulations The produ...

Page 13: ...for ensuring these conditions THE FLUE Further to the general prescriptions for the fumes duct and flue the flue must serve solely to exhaust fumes must be correctly sized to satisfy the requirements...

Page 14: ...ION 1 2 3 4 5 6 7 8 9 10 11 12 connection V3 connection V2 Pre wired electrical power connection TERMINAL BOARDS The right side of the appliance seen from the front has a bracket with two terminal boa...

Page 15: ...y that the plug is accessible once the installation is complete Secure the bottom of the base to the floor with 8 mm steel anchor bolts to prevent it from tipping over Position the top of the base 2 n...

Page 16: ...Secure the loading inlet A Screw A with B Open the loading inlet to reach the screws Insulate the loading tube and make sure that it does not touch the fumes duct The loading tube must be well extende...

Page 17: ...the technician does not adjust the parameters The air vents are not included in the product but you can choose at the retailer s which of the five available models described above best suits your tast...

Page 18: ...LOADING DRAWER posizionarli all interno del serbatoio pellet place them inside the pellet tank Regolare i part A B C e fissarli con viti part D adjust the parts A B C and fix them with screws part D K...

Page 19: ...2 screw the ceramic front panel to the frame with its support 3 There are 5 screws in all two on each side and one in the centre 3 replace the metal cover with the drawer Kit 2 and screw it on the si...

Page 20: ...20 ENGLISH PELLET LOADING DRAWER 2 3 Figure 12 Drawer fitted Connecting the pipes for ducting hot air Connecting the pipes for ducting hot air 2 3 repeat on the other side 4 screws Figure 11...

Page 21: ...an additional opening of at least 10x10 cm in size is available in one side of the cover for ventilation air recovery any wooden beams are insulated and not resting against the metal structure WE RECO...

Page 22: ...round on to its supports secure it with the four grub screws included for the side versions fasten it to the bracket with a nut D For versions 2 with frontal ventilation and pellet loading trapdoor se...

Page 23: ...For reasons of safety and environmental compatibility DO NOT burn plastic painted wood coal bark or other such materials in the stove Do not use the product as an incinerator Caution Using fuels other...

Page 24: ...s ON Flame ignites and grows stable This is the result of manual ignition with ignition button request from Crono power request during stand by request from external contact Ignition has a variable du...

Page 25: ...the type of batteries and the intensity of use Edilkamin and the reseller will not consider claims for battery life under any circumstances If the battery charge is low a warning displays at the top l...

Page 26: ...splay shows figure 4 1 the current time 2 the current room temperature 3 the room temperature setting or manual mode 4 the power level represented by the flames 5 the fan level represented by the fill...

Page 27: ...3 and displayed as positions 2 and 3 see below The two fans can be adjusted separately First adjust fan 2 and then fan 3 as described below Ventilation setting Press OK once The fan setting displays...

Page 28: ...temperature setpoint is reached To access the function from the main menu as indicated in the Menu section above press the M button Scroll using the buttons and select the function by pressing OK Use...

Page 29: ...ress the M button LOAD PELLETS STAND BY CRONO NIGHT DATE TIME DISPLAY LANGUAGE BEEP INFO TECHNICAL MENU scroll buttons OK button to confirm The following screen will appear Scroll to ENABLE underlined...

Page 30: ...buttons Press the OK button to confirm and select SET Press the M button to go back to the previous screen press the OK button to enter the SET function ENABLE TEMP CHANGE SET scroll buttons OK button...

Page 31: ...ckly Press the OK button to confirm and go to the temperature selection T1 T2 or T3 Press the buttons to switch between the temperatures To continue with other changes press the OK button To choose be...

Page 32: ...n during commissioning Available only in the OFF state If you attempt to activate the function in other states access is not granted To access the function from the main menu as indicated in the Menu...

Page 33: ...Confirm by pressing the OK button for 2 seconds Beep Allows you to enable disable the beep To access the function from the main menu as indicated in the Menu section above press the M button Scroll u...

Page 34: ...N B Any unauthorised modification is forbidden Use spare parts recommended by the manufacturer The use of counterfeit parts results in the guarantee becoming null and void MAINTENANCE Never vacuum ho...

Page 35: ...tray 3 and grate into a non flammable container the ashes may still contain embers and or hot parts Vacuum out the interior of the hearth the bed and the compartment around the grate into which the as...

Page 36: ...iability for damage resulting therefrom DISPOSAL At the end of its service life dispose of the product as required by regulations Deliver to the special recycling centres The remote control s exhauste...

Page 37: ...uantity of combustion air Check that the firebox door is closed Check that the grate and fume discharge are clean Check that the external air inlet is free i e the grilles are not obstructed Contact a...

Page 38: ...cian MESSAGE PROBLEM SOLUTION H07 Shutdown due to exceeding maximum fumes temperature Check the type of pellet contact the technician if in doubt Contact the technician H08 Shutdown due to overheating...

Page 39: ......