EDI SSM-12LE Operation Manual Download Page 6

SSM-LE Series 

Operations Manual 

Eberle Design Inc. 

Page 1 

Section 1  

General 

1.1 DESCRIPTION 

The SSM-LE series Signal Monitors consists of two models; the SSM-6LE, and SSM-12LE. 
The SSM-6LE is a six channel unit and the SSM-12LE is a twelve channel unit. Both 
models provide the same operational functions and features including advanced NEMA 

A

plus

@

 fault coverage, a full intersection liquid crystal display (LCD), comprehensive event 

logging and signal sequence reporting, and true RMS voltage measuring and reporting. A 
serial communications port is provided on all units that interfaces with the EDI 

ECcom

 

Signal Monitor Communications software running on a personal computer. Where not 
specified otherwise, the information in this manual will apply to both models. 

The  SSM-LE Series

 

Signal Monitor  is a device used in a Traffic Controller Assembly to 

accomplish the detection of, and response to improper and conflicting signals and improper 
operating voltages in a Controller Assembly caused by malfunctions of the Controller Unit 
(CU), load switches, or mis-wiring of the cabinet. The SSM-LE Series

 

also provides error 

sensing of two +24Vdc cabinet supplies and the controller power supplies via +24V 
MONITOR I, +24V MONITOR II, and Controller Voltage Monitor (CVM) inputs respectively. 
The Eberle Design SSM-LE Series

 

is directly interchangeable with a standard NEMA 

Signal Monitor and meets with or exceeds all specifications outlined in Section 6 (Conflict 
Monitor) of the National Electrical Manufacturers Association (NEMA) 

Standards 

Publication TS1-1989 R2005, Traffic Control Systems

1.2 ADVANCED FEATURE OVERVIEW 

1.2.1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY 

The  SSM-LE Series

 

uses a Liquid Crystal Display (LCD) to show monitor status and two 

icon based LCDs to show field signal channel and fault status. This versatile display system 
provides  a service technician with  both  detailed information regarding cabinet status and 
configuration,  and at the same time  an  easily read field signal status display  showing full 
intersection status.  

1.2.2 RMS VOLTAGE REPORTING 

Input  voltages are measured using a true Root Mean Squared (RMS) technique. A 
dedicated Digital Signal Processor (DSP) RMS-Engine controls the analog to digital (A/D) 
hardware which samples each AC input voltage a minimum of 32 times per cycle. The 
RMS-Engine  then calculates the true RMS voltage value producing accurate results which 
are very insensitive to changes in frequency, phase, wave shape, and distortion. 

1.2.3 ECCOM SOFTWARE INTERFACE 

The field proven EDI 

ECcom

  Signal Monitor Communications software provides  a laptop 

computer  or system interface to all information contained in the monitor. This includes 
detailed status, voltages, configuration, as well as historical event logs, and five thirty 
second Signal Sequence logs. 

Event logs provide a historical record of previous fault data, ac line event data, monitor 
reset events, and configuration programming change events. These logs are invaluable 
when analyzing fault data to diagnose cabinet equipment malfunctions. 

The  Signal Sequence logs  provide  a graphical display of the signal states of all sixteen 
channels for up to thirty seconds prior to the fault trigger point at 50 millisecond resolution. 
The SSM-LE Series

 

stores these signal records for the last five fault events. 

The EDI ECcom software  is available at no charge from the EDI web site at 

www.EDItraffic.com

Summary of Contents for SSM-12LE

Page 1: ...NS TECHNICAL INFORMATION FOR THE SSM 6LE SSM 6LEip SSM 6LEC SSM 12LE SSM 12LEip and SSM 12LEC SERIES SIGNAL MONITOR REVISION MARCH 2012 pn 888 1216 002 SSM LE Series NEMA TS 1 Enhanced Signal Monitor...

Page 2: ...INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING COPYRIGHT 2012 EDI MAINTENANCE NOTE THIS SIGNAL MONITOR UN...

Page 3: ...tion 3 Enhanced Features 7 3 1 Hardware Features 7 3 2 Dual Indication Monitoring 7 3 2 1 GY ENABLE Option 8 3 2 2 Walk Disable Option 8 3 3 Minimum Yellow Clearance Monitoring 8 3 4 External Watchdog...

Page 4: ...TX Indicator 19 6 1 14 PREV FAIL Indicator 19 6 2 Field Status Display 19 6 3 LED Status Display 19 6 3 1 POWER Indicator 19 6 3 2 FAULT Indicator 20 6 3 3 DIAGNOSTIC Indicator 20 6 4 Buttons 20 6 4 1...

Page 5: ...8 3 EIA 232 Connector 27 8 3 1 EIA 232 Cable to a PC 28 8 4 Ethernet LAN Port 28 8 4 1 Ethernet LAN Cable 28...

Page 6: ...RE OVERVIEW 1 2 1 LIQUID CRYSTAL STATUS AND FIELD DISPLAY The SSM LE Series uses a Liquid Crystal Display LCD to show monitor status and two icon based LCDs to show field signal channel and fault stat...

Page 7: ...g either full wave or positive and negative half wave sinusoidal field signal inputs at the specified voltage levels When triggered by the detection of a fault condition which exists longer than the m...

Page 8: ...reshold value to determine On Off status This differs from conventional standard NEMA operation where the active threshold is picked according to the color of the field signal Once the high and low On...

Page 9: ...ill be disabled when the RED ENABLE input is not active 2 2 1 RED ENABLE INPUT The RED ENABLE input will be sensed as active by the SSM LE Series when it exceeds the Red Enable Input threshold Section...

Page 10: ...lt mode transfer the OUTPUT relay contacts to the Fault position and display the CVM status screen When the TRUE low state is absent for less than the CVM No Fault time the SSM LE Series will not tran...

Page 11: ...and the last component to sense a proper AC LINE operating voltage The AC LINE and AC NEUTRAL inputs are used to generate the internal voltage supplies required to operate the monitor AC NEUTRAL also...

Page 12: ...ruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM device requires no battery back up The time of day in the SSM LE Series is stored in a battery bac...

Page 13: ...he Clearance Fail Fault time 7 4 The Yellow Change interval consists of the duration of time in which the Yellow field signal input is active in a sequence from Green to Yellow to Red When this minimu...

Page 14: ...A real time clock is provided on the SSM LE series Signal Monitor to identify each event occurrence with the time of day and date This information is displayed and stored along with the event status w...

Page 15: ...eries will enter the fault mode transfer the Output relay contacts to the Fault position and display the appropriate CONFLICT DUAL INDICATION or RED FAIL status screen along with RP STATUS The unit wi...

Page 16: ...FYA Overlap phase must be driven by a load switch monitored on channels 9 10 11 12 respectively The SSM LE Series associates channel 1 with 9 channel 3 with 10 channel 5 with 11 and channel 7 with 12...

Page 17: ...proaches This mode requires that the Controller Unit be capable of remapping the Protected Green Arrow signal driver to the channel 9 10 11 and 12 Yellow load switch inputs The cabinet must be re wire...

Page 18: ...from the flashing Yellow Arrow 1 3 5 7 to the solid Red Arrow 1 3 5 7 without a minimum clearance time on the solid Yellow Arrow 1 3 5 7 The fault icon will be displayed for the FYAc channel 1 3 5 7 i...

Page 19: ...vent 4 1 2 CURRENT STATUS S Fault Type the fault type description Field Status the current or latched RYGW field status and RMS voltages Cabinet Temperature the current or latched temperature if the m...

Page 20: ...the reported configuration 4 1 7 SIGNAL SEQUENCE EVENT LOG The Signal Sequence event log graphically displays all signal states and Red Enable state for up 30 seconds prior to the SSM LE Series fault...

Page 21: ...fault mode until the Program Card is correctly seated and the SSM LE Series is reset by the RESET button or the EXTERNAL RESET input 5 2 MINIMUM FLASH TIME PROGRAMMING It is recommended that the Mini...

Page 22: ...2 2 2 5 4 5 CONTROLLER VOLTAGE MONITOR CVM LATCH PROGRAMMING The CVM Latch function is ENABLED by setting the Option switch labeled CVM LATCH to the ON position See Section 2 3 2 1 5 4 6 24VDC MONITOR...

Page 23: ...w all active field output signals at the time of the CVM fault 6 1 4 24V 1 INDICATOR The 24V 1 indicator will be illuminated when unit detects a 24V 1 fault The Field Status display will show all acti...

Page 24: ...dicator will be displayed when the EIA 232 or Ethernet port has correctly received a message 6 1 13 TX INDICATOR The Tx indicator will be displayed when the EIA 232 or Ethernet port has transmitted a...

Page 25: ...epressing the MODE button changes the mode of the front panel displays to display the Previous Fault Log information PF Data Log mode the AC Power Interruption and Restoration Log Information AC Data...

Page 26: ...utton will display the SSM switch programming Each channel with the SSM switch On will be denoted by a dark solid arrow and the Red Yellow Green and Walk indicators illuminated The CLEARANCE and DUAL...

Page 27: ...hreshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect...

Page 28: ...c Controller Voltage Monitor CVM No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec 24Vdc Monitor No Fault less than 125 msec Fault greater than 175 msec Typical 150 msec Clearan...

Page 29: ...ses when fault occurs O C Output Relay 2 Closed FTR Drive Opens when fault occurs O D Channel 12 Green I E Channel 11 Green I F Channel 10 Green I G Channel 9 Green I H Channel 8 Green I J Channel 7 G...

Page 30: ...Yellow I y Channel 2 Walk I z Channel 1 Walk I AA Spare 1 BB Reset I CC Cabinet Interlock A I DD Cabinet Interlock B O EE Channel 6 Walk I FF Channel 4 Walk I GG Spare 2 HH Spare 3 8 1 2 SSM 12LE CONN...

Page 31: ...ate with a MS 3116 22 55 SY 8 2 1 SSM 6LE CONNECTOR MS A PIN TERMINATIONS Pin Function I O A AC Line I I B AC Line II I C Output Relay 1 Open Stop Time Closes when fault occurs O D Output Relay 2 Clos...

Page 32: ...II I m Controller Voltage Monitor I n 24V Monitor Inhibit I p Cabinet Interlock A q Spare 1 r Output Relay 1 Closed Stop Time Opens when fault occurs O s Start Delay Relay Closed Opens during Start D...

Page 33: ...Monitor DB 9 RX pin 2 connect to TX pin 2 TX pin 3 connect to RX pin 3 DTR pin 4 connect to DTR pin 4 optional GND pin 5 connect to GND pin 5 A typical cable assembly for a DB 25 connector on the PC...

Reviews: