EDI NEMA TS-1 Operation Manual Download Page 6

NSM-3E Signal Monitor Unit 

Operations Manual 

Eberle Design Inc. 

Page 2 

input. When voltages on all inputs to a channel are sensed as inactive for less than 700 

msec, the unit will not transfer the Output relay contacts to the Fault position.  
Red Failure Monitoring is disabled when the Red Enable input is not active. 

1.3.1 WALK DISABLE (RED MONITORING) 

This option will modify the operation of Red Monitoring on the NSM-3E  Signal Monitor. 

When enabled, the Red Monitoring function will not monitor the Walk field outputs. Absence 

of signals on the Green, Yellow, and Red field outputs of a channel will place the NSM-3E 

Signal Monitor into the fault mode causing the Output relay contacts to transfer. This 

function is enabled by the front panel option switch labeled "WALK DISABLE".  See also 

section 2.2.2. 

1.4 VOLTAGE MONITORING 

Inputs are provided for monitoring two +24VDC supplies and the Controller Voltage Monitor 

(CVM) output from the controller. Should loss of proper signal occur at any of these inputs, 

the  NSM-3E  Signal Monitor will de-energize the Output Relay causing the two sets of 

contacts to transfer and will illuminate the appropriate front panel indicator(s). The Monitor 

will automatically reset when the correct input signals are restored to these inputs if the unit 

had not already been triggered by a previous fault condition. A 24V Monitor Inhibit input is 

provided to facilitate the use of these monitors with pre-timed mechanical controller 

installations. 

1.4.1 VOLTAGE MONITOR FAULT LATCH 

When the 24V Latch option is enabled by the front panel switch labeled "24V LATCH", the 

absence of the proper voltage level at either of the two 24VDC inputs (24V-I & 24V-II) will 

place the NSM-3ESignal Monitor into the fault mode causing the Output relay contacts to 

transfer. The 24V-2 and / or the 24V-1 indicator(s) will be displayed on the Fault Status 

Display along with the field output signals active at the time of the voltage fault. Restoration 

of the voltage levels will not reset the fault state of the Monitor. Only a Manual Reset or 

External Test Reset command will reset the Monitor. 

1.4.2 CVM FAULT LATCH 

When the CVM Latch option is enabled by the front panel switch labeled "CVM LATCH", 

the absence of the True state at the CVM Input will place the NSM-3E Signal Monitor into 

the fault mode causing the Output relay contacts to transfer. The CVM indicator will be 

displayed on the Fault Status Display along with the field output signals active at the time of 

the voltage fault. Restoration of the True state will not reset the fault state of the Monitor. 

Only a Manual Reset or External Test Reset command will reset the Monitor. 

1.5 AC+ BROWN-OUT / INTERRUPTION DETECTION 

When the AC+ line voltage is below the drop-out level for 475 msec (+_25 msec) the NSM-

3E Signal Monitor will suspend all fault monitoring functions, de-energize the Output relay, 

and de-energize the Start relay. The POWER indicator on the front panel will flash at a rate 

of 2Hz to indicate the brown-out status. 
When the AC+ line voltage returns above the restore level for 100 msec (+_16 msec) the 

monitor will resume normal operation and the POWER  indicator on the front panel will 

remain illuminated. After a 2.5 second (+_1 second) delay the Start relay will be energized. 

After a programmable delay determined by the minimum flash function switches on the 

front panel the Output relay will be energized. 

Summary of Contents for NEMA TS-1

Page 1: ...THIS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE NSM 3E SERIES SIGNAL MONITOR UNIT REVISION JULY 2017 pn 888 0003 002 NSM 3E NEMA TS 1 Enhanced Signal Monitor Operations Manual ...

Page 2: ...RODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING LEDGUARD IS A REGISTERED TRADEMARK OF EBERLE DESIGN INC COPYRIGHT 2017 EDI MAINTENANCE NOTE THIS EBERLE DESIGN INC AUXILIARY MONITOR UNIT HAS BEEN CAREFULLY INSPECTED AND TESTED TO ENSURE PROPER OPERATION IT IS RECOMMENDED THAT THE AUXILIARY MONITOR UNIT BE TESTED AT LEAST ANNUALLY TO ENSURE PROPER OPERATI...

Page 3: ...Test 5 Section 3 Installation 6 3 1 Harnessing Connectors 6 3 2 Minimum Flash Dip Switch Programming 6 3 3 SSM Dip Switch Programming 6 3 4 Option Dip Switch Programming 6 3 4 1 GY Enable 6 3 4 2 RP DISABLE 6 3 4 3 WALK DISABLE 7 3 4 4 CVM LATCH 7 3 4 5 24V LATCH 7 3 4 6 LEDguard 7 3 4 7 OPTION A 7 Section 4 Front Panel Description 8 4 1 Status Display 8 4 1 1 POWER Indicator 8 4 1 2 CONFLICT Indi...

Page 4: ...5 1 4 Logic Inputs 10 5 2 Timing Functions 10 5 3 Mechanical 11 5 4 Environmental 11 Section 6 Wiring Assignments 12 6 1 NSM 3E Monitor Unit Connector A 12 ...

Page 5: ...ations TS 1 part 6 the NSM 3E Signal Monitor will enter the fault mode causing the Output relay to de energize and two sets of contacts on the Output relay to transfer The cabinet assembly should be wired such that the closure of the signal monitor Output relay contacts will cause an automatic switching of the field signal outputs from normal operation to flashing operation The NSM 3E Signal Monit...

Page 6: ...e absence of the proper voltage level at either of the two 24VDC inputs 24V I 24V II will place the NSM 3ESignal Monitor into the fault mode causing the Output relay contacts to transfer The 24V 2 and or the 24V 1 indicator s will be displayed on the Fault Status Display along with the field output signals active at the time of the voltage fault Restoration of the voltage levels will not reset the...

Page 7: ...retain fault status information in the event of an AC Line power interruption The correct fault indications will be displayed upon restoration of AC Line power This EEPROM nonvolatile memory requires no battery back up No monitor configuration programming is stored under battery power 2 2 DUAL INDICATION MONITORING This monitoring function detects simultaneous indications of active Green Yellow Wa...

Page 8: ...ensing faults which are intermittent or pulsing in nature The RMS Engine is designed to filter out short term transients commonly found on the electrical service and provide noise immunity against false signal detections The Recurrent Pulse detection function is designed to respond to fault conditions which are intermittent in nature and do not meet the continuous timing requirements of the normal...

Page 9: ...ge Monitor Fault if the 24V Latch or CVM Latch options are enabled The NSM 3E Signal Monitor stores the fault and channel indicator status into non volatile EEPROM memory Should an AC power interruption occur while the monitor is in the fault mode then upon restoration of AC power the Output relay will remain in the fault mode and the correct fault and channel information will be displayed This fa...

Page 10: ...Off On 13 seconds On On On Off 14 seconds On On On On 15 seconds It is recommended that the Minimum Flash Time be programmed on the NSM 3E Signal Monitor to exceed the initialization time of all cabinet assembly components following an AC restoration The amount of flash time is typically equal to the amount programmed on the controller so that if the controller fails to execute a minimum flash per...

Page 11: ...s 1 3 1 and 2 2 2 3 4 4 CVM LATCH Set this switch to the ON position to change a CVM fault to the latched state See Section 1 4 2 3 4 5 24V LATCH Set this switch to the ON position to change a 24V 1 or 24V 2 fault to the latched state See Section 1 4 1 3 4 6 LEDGUARD Set this switch to the ON position to Enable the LEDguard function See Section 2 5 3 4 7 OPTION A This DIP switch is currently not a...

Page 12: ...icator will be illuminated when a Controller Voltage Monitor Fault is detected The Channel Status display will show the active signals for each channel at the time of the fault 4 1 5 24V 1 24V 2 VOLTAGE MONITOR INDICATORS These indicators will be illuminated if the corresponding voltage input is below the minimum specified level The Channel Status display will show the active signals for each chan...

Page 13: ... the field signals active at the time of the fault for 6 seconds and the channels which were involved in the fault fault status for 2 seconds The channels involved in the fault will flash their respective Green Yellow Walk and Red indicators simultaneously at a 4 Hz rate for the 2 second fault status interval If the fault displayed is a Recurrent Pulse Conflict Recurrent Pulse Dual Indication or a...

Page 14: ... Detect less than 50 Vrms Detect greater than 70 Vrms Red Enable Input No Detect less than 50 Vrms Detect greater than 70 Vrms LEDguard Low Threshold Signal Inputs No Detect less than 15 Vrms Detect greater than 25 Vrms LEDguard High Threshold Signal Inputs No Detect less than 50 Vrms Detect greater than 70 Vrms AC Line Voltage Monitor Drop out less than 92 _2 Vrms Restore greater than 96 _2 Vrms ...

Page 15: ...conds Fault greater than 500 milliseconds Typical 400 milliseconds Clearance Fail Short Yellow Fault less than 2 6 seconds No Fault greater than 2 8 seconds Typical 2 7 seconds AC Interruption disable greater than 475 milliseconds 25 milliseconds Minimum Flash after disable 4 to 15 seconds 1 second Start Delay Relay timer 2 5 seconds 1 second 5 3 MECHANICAL Height 6 5 inches Width 3 0 inches Depth...

Page 16: ... CHANNEL 3 YELLOW 11 L CHANNEL 2 GREEN 12 M CHANNEL 2 YELLOW 13 N CHANNEL 1 GREEN 14 P CHANNEL 1 YELLOW 15 R CHANNEL 1 WALK 16 S 24V MONITOR II 17 T CONTROLLER VOLTAGE MONITOR 18 U 24V MONITOR 19 V LOGIC GROUND 20 W CHASSIS GROUND 21 X AC 22 Y CABINET INTERLOCK A 23 Z OUTPUT RELAY 1 CLOSED 24 a OUTPUT RELAY 2 OPEN 25 b START DELAY RELAY CLOSED 26 c CHANNEL 3 WALK 27 d CHANNEL 3 RED 28 e CHANNEL 2 ...

Reviews: