background image

LMD222 and LMD224 Series 

Operations Manual 

Eberle Design Inc. 

Page 7 

Section 3  

Loop Installation  

The typical sensing height is 2/3 of the shortest leg of a loop (in feet). Therefore a 4’ x 8’ 
loop typically has a detection height of 2.6’.  

The inductance of a conventional four-sided loop can be estimated using the formula: 
 

L = P x (T

2

 + T) / 4  Where  

L = Loop Inductance in microHenries 

 

 

 

 

P = Loop Perimeter in feet 

 

 

 

 

T = Number of wires in saw slot 

 

Therefore a 4’ x 8’ loop with 3 turns would be: 

 

L = (4 + 8 + 4 + 8) x (3

+ 3) / 4 

 

L = 24 x (9 + 3) / 4 

 

L = 24 x 12 / 4 

 

L = 72 microHenries 

Note: Loop feeder cable typically adds 0.22 microHenries of inductance per foot of cable. 

The following are suggested guidelines for loop installation: 

To begin, make sure that the pavement surface in the area that loops are to be installed is 
dry and free of debris. The outline of the loop(s) should be marked on the pavement in such 
a way that the lines can be followed easily by the saw operator and not be erased by the 
water feed from the saw itself. 

All  90-degree corners should be chamfered so that the course of the loop wire does not 
change direction sharply but rather at shallower angles of 45 degrees or less. Core drilling 
of the corners achieves the same effect but can still lead to failure due to sharp edges 
remaining in the corner area. When the outline of the loop and lead-in has been marked, 
the pavement can be cut. Diamond blade cutting saws are recommended. The saw cut 
should be approximately 2.0 inches deep and 0.25 inches wide. The saw slot should then 
be cleaned out and allowed to dry. Compressed air is useful both for ejecting debris and 
speeding up the drying process. All debris in the vicinity of the saw slot should also be 
removed so that it is not accidentally pushed back in. 

As a general rule loops with circumference lengths less than 12 feet require 5 turns of wire, 
12 to 60 feet require 3 to 4 turns of wire, loops with greater circumference lengths should 
have 2 to 3 turns. 

Recommended loop wire is typically 14, 16, 18, or 20 AWG with cross-linked polyethylene 
insulation. Since moisture can cause significant changes in the dielectric constant of the 
insulation, which results in excessive loop (frequency) drift, choose insulation, which is 
most impervious to moisture. PVC, TFFN, THHN, and THHN-THWN should be avoided 
since they tend to absorb moisture and crack easily. XLPE (Cross Linked Polyethylene) is 
very resistant to moisture absorption and provides good abrasion resistance.  

If long lead-ins are required, it is suggested that the loop cable be spliced onto shielded, 
pre-twisted, lead-in wire (IMSA specification 50-2 is suggested) at a convenient pull box 
location close to the loop. The shield may be connected to earth at the cabinet end but 
should then be insulated and isolated from earth ground at the loop end. The inductance of 
the loop itself should be at least 50% of the sum of loop inductance plus lead-in inductance. 

Start laying the loop wire from the termination of the lead-in out towards the loop, continue 
around the loop for the  number of turns required and finally return to the lead-in 
termination. Leave the lead-in wire out of the slot so that it may be twisted together before 
being laid in the slot. Lead-ins should be twisted with a minimum of 4 to 6 twists per foot to 
prevent any separation of the lead-in wires. 

Make sure that the loop wire is pushed fully to the bottom of the saw slot. Small pieces of 
foam rubber (backer rod) or similar material may be used at various points around the 

Summary of Contents for LMD222

Page 1: ...IS MANUAL CONTAINS TECHNICAL INFORMATION FOR THE LMD222 LMD224 and LMD222 R SERIES INDUCTIVE LOOP MONITOR REVISION AUGUST 2015 pn 888 0222 003 LMD222 and LMD224 Inductive Loop Monitor Operations Manua...

Page 2: ...01 2008 REGISTERED COMPANY INFORMATION CONTAINED HEREIN IS PROPRIETARY TECHNICAL INFORMATION OF EBERLE DESIGN INC PUBLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS A...

Page 3: ...ff Mode 5 2 3 Set the Frequency 5 2 3 1 Displaying the Loop Frequency 5 2 4 Miscellaneous 5 2 4 1 Channel Off 5 2 4 2 Retune or Reset a Channel 6 2 4 3 Factory Default Settings 6 2 5 Loop Fault Monito...

Page 4: ...ept to the inductive loop detector field that revolutionizes the process of installing and programming a loop detector The new user interface of the LMD Series provides the feedback necessary to the s...

Page 5: ...rle Design Inc Page 2 The unit will detect inductance changes as small as 0 010 L L Each channel is sequentially energized and sampled so as to negate the possibility of crosstalk between loops connec...

Page 6: ...ading 5 This is done by pressing the front panel SENS down button twice If a mid size vehicle located over the roadway loop causes the value 2 to be displayed on the DEFLECTOMETER the sensitivity shou...

Page 7: ...hree seconds Pressing the SENS or SENS button during this interval will modify the Sensitivity Level as described in section 2 1 1 with the DEFLECTOMETER display remaining in the Call Strength mode Pr...

Page 8: ...several seconds The Frequency level needs to be changed only if interference occurs between adjacent loops connected to different sensor units Interference or crosstalk may manifest itself as chatteri...

Page 9: ...cuit loops shorted loops or sudden changes in inductance exceeding 25 of the nominal inductance 2 5 1 CURRENT FAULT If a fault is detected both the DET Red and FLT Yellow LEDs continuously emit a sequ...

Page 10: ...in the vicinity of the saw slot should also be removed so that it is not accidentally pushed back in As a general rule loops with circumference lengths less than 12 feet require 5 turns of wire 12 to...

Page 11: ...to the bottom of the slot and completely encase the loop wire The wire should not be able to move when the sealant has set Ensure that there is enough sealant to completely fill the slot if possible...

Page 12: ...he tuning range of 20 to 2500 microHenry with a Q factor greater than 5 4 4 2 ENVIRONMENTAL TRACKING The detector automatically and continuously compensates for component drift and environmental effec...

Page 13: ...nnel 1 Redundant Loop Input E Channel 1 Loop Input 5 Channel 1 Redundant Loop Input F Channel 1 Output 6 Reserved H Channel 1 Output 7 Reserved J Channel 2 Loop Input 8 Channel 2 Redundant Loop Input...

Page 14: ...eserved N Reserved 12 Reserved P Channel 3 Loop Input 13 Channel 3 Redundant Loop Input R Channel 3 Loop Input 14 Channel 3 Redundant Loop Input S Channel 3 Output 15 Reserved T Channel 3 Output 16 Re...

Reviews: