Edge-Core AS7315-27X Quick Start Manual Download Page 1

–  1  –

Quick Start Guide

Attach the Brackets

1.

Front-Flush Mount: Using the four front screw holes, attach each 
of the brackets to the router with four of the included bracket 
screws. (Installation depth of 300 mm.)

2.

Front-Recessed Mount: Using the four recessed screw holes, 
attach each of the brackets to the router with four of the included 
bracket screws. (Installation depth of 280 mm.)

Mount the Router in a Rack

1.

Use the screws and cage/clip nuts supplied with the rack to 
secure the router in the rack.

Ground the Router

1.

Ensure the rack is properly grounded and in compliance with 
ETSI ETS 300 253. Verify that there is a good electrical 
connection to the grounding point on the rack (no paint or 
isolating surface treatment).

2.

Attach the grounding wire (#6 AWG/16 mm

2

) to the grounding 

point on the router’s rear panel or side panel. Then connect the 
other end of the wire to rack ground.

Connect Power

1.

Install one or two DC PSUs (part number CRXT-T0T12B only) in 
the router, if they are not already installed in the factory.

2.

Connect an external DC power source to the PSUs. Or, connect 
to a no-tolerance DC mains supply with a UL/CSA-approved 
circuit breaker rated at 16 A.

Caution: 

The device must be installed in a restricted-

access location.

Attention:

 le périphérique doit être installé dans un 

emplacement à accès restreint.

Note:

 The router has the Open Network Install 

Environment (ONIE) software installer pre-loaded on the 
router, but no software image. Information about 
compatible software can be found at 

www.edge-core.com

.

Note:

 The drawings in this document are for illustration 

only and may not match your particular model.

Caution:

 Installing the router in a rack requires two 

people. One person should position the router in the rack, 
while the other person secures it using the rack screws.

1

1

2

2

1

Caution:

 The earth connection must not be removed unless 

all supply connections have been disconnected.

Attention:

 Le raccordement à la terre ne doit pas être retiré 

sauf si toutes les connexions d’alimentation ont été 
débranchées.

Caution:

 Before connecting power supply cables to the 

router, ensure that power to the feed lines is turned off at the 
supply circuit breaker or disconnected from the power bus.

3

2

1

2

Rear Panel

Side Panel

4

2

1

E052020-CS-R02
150200002078H

Cell Site Gateway

AS7315-27X

1.

AS7315-27X (includes 2 PSUs and 1 fan tray)

2.

Rack Mounting Kit—2 brackets and 8 screws

3.

Grounding kit—grounding lug, 2 screws, and 2 washers

4.

Ring lugs (x4) (included with DC PSUs only)

5.

Category 6 stacking cable

6.

Documentation—

Quick Start Guide

 (this document) and 

Safety and Regulatory Information

1

Package Contents

2

3

4

6

www.edge-core.com