Eden CS/4S 21 Installation, Operation And Maintenance Manual Download Page 6

Vers. 2009-3

water cassettes

6

INSTALLATION, OPERATION
AND MAINTENANCE MANUAL

WORKING LIMITS

RECCOMENDATIONS FOR THE INSTALLER

GENERAL FEATURES AND MAIN COMPONENTS

Maximum inlet water temperature

70°C

Minimum inlet water temperature

+4°C

Maximal working pressure

8 bar

Maximal inlet air temperature

32°C

Minimal inlet air temperature

+4°C

ATTENTION!
Air strati

fi

 cation increases with the raise of inlet water temperature!

1  Air

fl

 ow direction louvers

2  Air intake grille with 

fi

 lter

3  Air

fl

 ow direction louvers

4  Indicator lights (the only model with a control board that is managed on        
board)
5  Power
6  Sleep mode
7  Timer mode
8  Infrared remote control receiver
9  

EMERGENCY

 switch (used to switch on the air conditioner manually, without 

using the remote control, following the order given below).

STRUCTURE

Made in heavy-gauge galvanised sheet, the structure comes complete with ex-
ternal brackets on the 4 corners for easy 

fi

 xing to the ceiling. Thermal-acoustic 

insulation: lining (polystyrene), external cladding (closed cell). Set-up for di-
stribution of air to adjacent rooms through knock-out holes, either circular Ø 
150 mm or rectangular 350x100 mm (CS/4S), and rectangular 120 x 80 mm 
(HC/4S),  located on two sides of the appliance. Set-up for external air intake 
through Ø 65 mm circular knock-out hole (CS/4S). Rectangular 120x80 mm 
knock-out (HC/4S). Located on a squared off corner of the appliance.

HEAT EXCHANGER

Coil in copper piping expanded into aluminium 

fi

 ns in continuous block. The 

headers have easily accessible female gas 

fi

 ttings and air vent/drainage valve 

located on the squared off corner of the appliance.

AIR FILTER

The 

fi

 lter comprises a plastic frame holding the 

fi

 ltering membrane. Inserted in 

the inner part of the front panel, it may be easily removed and cleaned using a 
vacuum cleaner followed by washing with water.

MOTOR FAN GROUP

Single-inlet centrifugal fan with statically and dynamically balanced plastic 
impeller. The 4-speed electric motor, made to international standards, has an 
overload cut-out and the run capacitor always connected. The motor is directly 
coupled to the fan and cushioned with 

fl

 exible mountings. 

It is particularly ef

fi

 cient and low noise.

DÉCOR PANEL

The décor panel has an innovative design so that the appliance may be used 
in both dwellings and business premises. The white (RAL 9003) panel is made 
in lightweight but strong plastic. Fixing to the load-bearing structure is quick 
and easy. 4 adjustable louvers ensure best air distribution throughout the room. 
Central intake grille with 

fi

 lter for cleaning the air.  The grille may be removed to 

access internal parts without having to remove the panel from the ceiling.

ELIMINATION OF CONDENSATION

Condensate collecting system comprising:
-  internal  plastic  tray  for  collecting  condensation  coming  from  the  heat                       
 exchanger;
-  external auxiliary plastic tray for collecting condensation coming from the
  valves and connecting pipes.
Electric pump, which is an integral part of the appliance and connected to the 
external 

fi

 tting.

WALL MOUNTED CONTROL FOR PANELS WITH A CONTROL BOARD 
THAT IS MANAGED ONBOARD (accessory)

Wall mounted control for the water cassette with a 10 m headed cable with a 
connector (it maintains the same functions as the remote control).

Upon receiving the unit check for any damage, which should be reported imme-
diately. For the water cassette to operate correctly, it should be installed accor-
ding to the instructions given in this manual. Removal of a water cassette after it 
has been installed is an operation that requires special training: if this is neces-
sary, please consult your dealer. After installation, explain the correct operating 
procedure to the customer using the booklet as a reference. Leave this manual 
with the customer since it is part of the kit supplied with the appliance.
Take care not to scratch the units when handling them.

UNIT INSTALLATION 

- Read this instruction manual thoroughly before starting installation.
- This unit complies with the low-voltage (EEC/73/23) and electromagnetic com-
patibly (EEC/89/336) directives.
- The installation should be carried out by a quali

fi

 ed installer.

- Follow all current national safety code requirements. In particular ensure that 
a properly sized and connected ground wire is in place.
- Check that the voltage and frequency of the mains power supply are as requi-
red for the unit to be installed; the available power source must be adequate to 
operate all other appliances connected to the same line. 
- Ensure that national safety code requirements have been followed the main 
supply circuit.
- Where necessary, use 

fi

 eld-supplied 25 mm I.D. PVC pipe of appropriate leng-

th and with the correct thermal insulation for the condensate drain extension.
- After installation thoroughly test system operation and explain all system fun-
ctions to the owner.
- Use this only for factory approved applications: the unit cannot be used in 
laundry or stream pressing premises.

Pic. 03

Pic. 04

OFF

COOL

HEAT

ON

OFF

CS/4S

POWER SLEEP

TIMER EMERGENCY

OFF

COOL

HEAT

HC/4S

ON

OF

F

Summary of Contents for CS/4S 21

Page 1: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL WATER CASSETTES 2009 3...

Page 2: ...INSTALLATION OPERATION AND MAINTENANCE MANUAL MANUALE IN USO E MANU...

Page 3: ...ALLATION OF AUXILIARY DRAIN PAN 9 CONDENSATE DRAINAGE 9 ELECTRIC POWER CABLES AND VALVE PASSAGE 10 ELECTRICAL CONNECTIONS 10 Eccess to the control panel 10 WIRING DIAGRAM FOR CASSETTE 2 PIPE SYSTEM WI...

Page 4: ...Hu mm 280 280 280 280 240 305 305 305 Depth of the panel Lp mm 720 720 720 720 953 953 953 953 Lenght of the panel Pp mm 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80...

Page 5: ...280 280 280 240 305 305 305 Depth of the panel Lp mm 720 720 720 720 953 953 953 953 Lenght of the panel Pp mm 720 720 720 720 953 953 953 953 Height of the panel Hp mm 65 65 65 65 80 80 80 80 Air su...

Page 6: ...ture is quick and easy 4 adjustable louvers ensure best air distribution throughout the room Central intake grille with filter for cleaning the air The grille may be removed to access internal parts w...

Page 7: ...r correct connection of the receiver panel to the unit Establish the position and size of the hole in the ceiling using the external dia meter of the cardboard mounting template pic 07 To fix the unit...

Page 8: ...correctly or it will not go on 2 The unit has a protection system that intervenes by closing the water flow via the valve in cases such as a Where there is a condensate discharge problem if the valve...

Page 9: ...f condensation which could drip into suspended ceilings causing considerable problems The water connections are fixed to the unit body to avoid damage when pi pes are connected It is advisable to tigh...

Page 10: ...with European standard EN60947 3 Make sure that the electrical system is suitable for providing not only the working current required by the appliance but also the necessary current for powering house...

Page 11: ...rain pump 230Vac 50Hz FS Float switch NC LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit wii stop Com Common P1 P2 Pn Terminals C3 Condenser FS P...

Page 12: ...FS Float switch NC LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit will stop Com Common P1 P2 Pn Terminals C3 Condenser L N L N C FS P23 P18 P19...

Page 13: ...HOUT A CONTROL BOARD THAT IS MANAGED ONBOARD Pic 28 LEGENDA Connector Earth M1 Fan motor 230Vac 50Hz SM Louver motor 230Vac 50Hz DP Drain pump 230Vac 50Hz FS Float switch NC DT Timer C1 Condenser FRON...

Page 14: ...filter panel the unit wii stop Com Common P1 P2 Pn Terminals C3 Condenser LEGENDA Connector Earth L Phase N Neutral M1 Fan motor 230Vac 50Hz SM Louver motor 230Vac 50Hz DP Drain pump 230Vac 50Hz FS F...

Page 15: ...LS1 SM limit switch 60x60 cassette Safety switch 90x90 cassette when opening the filter panel the unit will stop Com Common P1 P2 Pn Terminals C3 Condenser LEGENDA Connector Earth L Phase N Neutral M...

Page 16: ...Vers 2009 3 water cassettes 16 INSTALLATION OPERATION AND MAINTENANCE MANUAL SECOND PART FOR THE USER...

Page 17: ...in order to identify possible damage After prolonged use apply to specialised service personnel to control the instal lation conditions of the air conditioner Do not use flammable gas near the air con...

Page 18: ...the corresponding part on the display will flash the current time is set via the key Once this is com pleted confirm the time by pressing the SEND key and the acoustic signal will verify that the corr...

Page 19: ...REMOTE CONTROL Keep the key pressed for 2 seconds to block the remote control Keep the key pressed for 2 seconds to unblock the remote control ECONO Press the ECONO key in cooling heating or automatic...

Page 20: ...c 49 WALL MOUNTED CONTROL SAME FUNCTIONS AS THE REMOTE CONTROL WALL MOUNTED CONTROL OPERATIONS TROUBLESHOOTING CASSETTE WITH A CONTROL BOARD THAT IS MANAGED ONBOARD CASSETTE WITH A CONTROL BOARD THAT...

Page 21: ...the room HEAT The writing HEAT appears on the air conditioner control display The unit ope rates in the air conditioning mode the zone valve starts if Troom Tset 1 the zone valve stops if Troom Tset I...

Page 22: ...SEASON MAINTENANCE Clean and replace the filters On a sunny day leave the cassette running in fan mode for a few hours to allow the inside of the unit to dry completely Remove the plug or turn off the...

Page 23: ...NOTES...

Page 24: ......

Page 25: ......

Page 26: ...With the perspective of improvement and against the continuous action of research and development the Manufacturer might modify even without any prior notice the given technical data...

Reviews: