8

3.3  Boiler Location Considerations

• Ambient room temperature always above 32°F (0°C) to 

prevent the potential of freezing. 

• Drainage of water (or water/ antifreeze solution) during 

boiler service or from safety relief valve discharge.

• Access to system water piping, gas supply, and 

electrical service. 

• 

Boiler shall be installed on flat surface which is capable 

of supporting the weight of the boiler, water, and 

equipment. 

• 

Raise boiler above the floor on blocks if floor may get 

wet.

• Horizontal run to chimney shall be as short a possible.

3 - LOCATING THE BOILER

Items to Avoid

Products Which May Contain These 

Items

Areas Where These Items May Be 

Found

Chlorine, Fluorine, and Compounds

Spray cans containing chlorofluorocarbons

Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Swimming pool  or spa chemicals
De-icing salts or chemicals
Carbon Tetrachloride

Swimming pools and pool storage areas

Laundry room (Note 2)
Confined storage areas

Airborne Particulates

Drywall dust
Road or gravel dust
Dryer lint
Cat litter

Construction or remodelling areas (Note 1)

Laundry room (Note 2)

Acids, Solvents, etc.

Paint, Varnish, Turpentine, etc.
Cleaning Solvents
Hydrochloric acid/muriatic acid
Cements, adhesives and glues

Photo processing plants
Garages with workshops

Furniture refinishing areas and 

establishments

Laundry Chemicals

Laundry detergents, bleaches, fabric 

softeners, etc.
Antistatic fabric softeners (dryer sheets)

Dry cleaning/laundry areas and 

establishments

Other

Permanent wave solutions
Refrigerants (Freon, etc) (only where 

the refrigerant may be leaking from the 

appliance)

Beauty shops
Refrigeration repair shops

Notes:  

1. It is recommended the boiler be isolated and not operated during construction/

renovation.  Excessive particles ingested by the boiler may accumulate in the flueway 

passages possibly resulting in unsafe operation.  In this case, unit servicing shall include 

cleaning of flueway passages and burner ports.
2. If locating boiler in laundry room is unavoidable, it is manufacturer recommended 

the room be generously ventilated (well in excess of combustible air requirements), and 

homeowner seal  laundry supply containers, and minimize room vapors.

3

. Piping allowing fresh air in should also be considered.  See Section 5-1.

t

Table 3-1: CONTAMINANTS

• System piping exposed to freezing conditions: Use 

inhibited propylene glycol solutions certified by fluid 

manufacturer for use with closed water heating system.  

Do not use automotive or ethylene glycol.
Maximum recommended mixture 50% gylcol.

 PN 240012809, Rev. C [11/15/2020]

Summary of Contents for Utica Heating UH15B-060K

Page 1: ...s For Forced Hot Water With Hydrolevel 3200 Control INSTALLATION OPERATION MAINTENANCE MANUAL Tested For 50 psi ASME Working Pressure C S A Certified For Natural Gas Or Propane Manufactured by ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 253 7900 www ecrinternational com PN 240012809 REV C 11 15 2020 ...

Page 2: ...ams Document Package Junction Box Circulator Harness Items found in parts box included with your boiler Information and specifications outlined in this manual in effect at the time of printing of this manual Manufacturer reserves the right to discontinue change specifications or system design at any time without notice and without incurring any obligation whatsoever For Parts lists see manual 2400...

Page 3: ... 24 10 1 Electrical Wiring 24 10 2 Thermostat Installation 24 11 Wiring Diagram 25 12 Lighting Instructions 27 12 1 Lighting Procedure For Boiler With Intermittent Pilot System 27 12 2 Operating Instructions For Intermittent Pilot System 27 12 3 To Turn Off Gas To The Appliance 27 13 Normal Sequence Of Operation 28 14 General Maintenance And Care Instructions 29 14 1 Seasonal Startup 29 14 2 Clean...

Page 4: ... 8 24 1 8 24 1 8 24 1 8 24 1 8 613 mm 613 mm 613 mm 613 mm 613 mm 613 mm 613 mm H Flue Diameter 4 5 6 6 7 7 7 102 mm 127 mm 153 mm 153 mm 178 mm 178 mm 178 mm Supply Return Tappings 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT 1 1 4 NPT Natural Gas Inlet 1 2 NPT 1 2 NPT 1 2 NPT 1 2 NPT 1 2 NPT 3 4 NPT 3 4 NPT Relief Valve NPT 3 4 NPT 3 4 NPT 3 4 NPT 3 4 NPT 3 4 NPT 3 4 NPT 3 4 NPT D...

Page 5: ...tand all requirements before beginning installation FOR YOUR SAFETY READ BEFORE OPERATING Hot Water Can Scald Water heated to temperature for clothes washing dish washing and other sanitizing needs can scald and cause permanent injury Children elderly and infirm or physically handicapped persons are more likely to be permanently injured by hot water Never leave them unattended in bathtub or shower...

Page 6: ... Current NIOSH recommendations can be found on the NIOSH website https www cdc gov niosh topics silica NIOSH approved respirators manufacturers and phone numbers are also listed on this website Wear long sleeved loose fitting clothing gloves and eye protection Apply enough water to the combustion chamber lining to prevent dust Wash potentially contaminated clothes separately from other clothing Ri...

Page 7: ...ate boiler on level solid base as near chimney as possible and centrally located with respect to heat distribution system as practical 6 Horizontal vent run to chimney shall be as short as practicable Refer to NFPA 54 to determine maximum permissible horizontal run for chimney type and height 7 Verify floor will support weight of boiler water and equipment 8 May be installed on combustible floor D...

Page 8: ...ine etc Cleaning Solvents Hydrochloric acid muriatic acid Cements adhesives and glues Photo processing plants Garages with workshops Furniture refinishing areas and establishments Laundry Chemicals Laundry detergents bleaches fabric softeners etc Antistatic fabric softeners dryer sheets Dry cleaning laundry areas and establishments Other Permanent wave solutions Refrigerants Freon etc only where t...

Page 9: ... and or hot water during operation Discharge line shall A connect to relief valve outlet and piped down to safe point of disposal Check local codes for maximum distance from floor or allowable safe point of discharge B be of pipe size equal to or greater than that of the relief valve outlet over the entire length of discharge line C have no intervening shutoff valve between safety relief valve and...

Page 10: ...s a possibility install appropriate safeguards and alarms on the heating system to prevent property damage due to frozen and burst pipes should the boiler heating system become inoperative due to a power outage safety lockout or component failure 4 4 Water Treatment Manufacturer recommends a water analysis be done on water used to fill the system Treatment may be required based on the analysis res...

Page 11: ...ng cycle Do not expose boiler and piping to freezing temperatures Note WARNING Asphyxiation hazard Gradual flueway blocking resulting from condensate induced corrosion may block boiler passages resulting in carbon monoxide and or flame rollout Install bypass piping if return temperature is under 130 F Failure to follow these instructions could result in death or serious injury 4 Boiler connected t...

Page 12: ...closed water heating system Do not use automotive or ethylene glycol Do not expose boiler and piping to freezing temperatures Note Boiler installed above radiation level or as required by authority having jurisdiction Integral low water switch is provided in boiler Boiler used in connection with refrigeration system Install piping in parallel with boiler with appropriate valves to prevent chilled ...

Page 13: ...4 CONNECTING SUPPLY RETURN PIPING Figure 4 3 Bypass Piping With Automatic Mixing Valve BACK FLOW VALVE PIPING LEGEND PURGE VALVE DRAIN VALVE ASME RELIEF VALVE Back Flow Valve PN 240012809 Rev C 11 15 2020 ...

Page 14: ...N PIPING Figure 4 4 Bypass Piping Fixed Low Temp Only With Zone Valve BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Manually adjust until proper system temperature is reached Drain Valve Drain Valve PN 240012809 Rev C 11 15 2020 ...

Page 15: ...CTING SUPPLY AND RETURN PIPING Figure 4 5 Bypass Piping 4 Way Valve Option With Circulator On Supply side BACK FLOW VALVE PIPING LEGEND ASME RELIEF VALVE Back Flow Valve Drain Valve PN 240012809 Rev C 11 15 2020 ...

Page 16: ... Figure 4 6 Single Zone System With DHW Priority BACK FLOW VALVE PIPING LEGEND 4 CONNECTING SUPPLY AND RETURN PIPING ASME RELIEF VALVE Back Flow Valve Drain Valve Purge Valve PN 240012809 Rev C 11 15 2020 ...

Page 17: ...quires all domestic hot water DHW installations use an anti scald valve Local codes may require additional equipment expansion tank relief valves etc Select and size equipment to suit installation and meet code requirements Note Refer to pump manufacturer literature for proper pump sizing 1 4 CONNECTING SUPPLY AND RETURN PIPING BACK FLOW VALVE PIPING LEGEND Figure 4 7 Multi Zone System With Zone V...

Page 18: ...Air Infiltration Rate See Table 5 1 for space with boiler only Use equation for multiple appliances Do not use an air infiltration rate ACH greater than 0 60 Volume 21 ft3 ACH x Total Input BTU HR 1 000 C Refer to National Fuel Gas Code for opening requirements between connected indoor spaces All Outdoor Air Provide permanent opening s communicating directly or by ducts with outdoors A Two Permane...

Page 19: ...r exhaust fan Close fireplace dampers 4 Place in operation the appliance being inspected Follow the lighting instructions Adjust thermostat so appliance will operate continuously 5 Test for spillage at the draft hood relief opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe 6 Minimum draft should be 02 w c 7 After it has been...

Page 20: ...d in good condition Installation must conform to requirements of the authority having jurisdiction or in absence of such requirements to The National Fuel Gas Code ANSI Z223 1 NFPA 54 7 4 Vent Pipe Connect draft hood to boiler using 2 screws provided onto flue collector Connect two safety circuit wires attached to vent damper harness to blocked vent switch See Figure 13 1 Fasten sections of vent p...

Page 21: ...ate damper so it is accessible for servicing See Figure 8 2 4 Damper must be in the open position when appliance main burners are operating 5 Boiler is equipped with factory wired harness that plugs into vent damper 6 Slope pipe up from boiler to chimney not less than 1 4 per foot 7 Run pipe as directly as possible with as few elbows as possible 8 Do not connect to fireplace flue 9 End of vent pip...

Page 22: ...22 Figure 8 2 Vent Damper Placement Figure 8 3 Vent Damper Position Indicator 8 VENT DAMPER INSTALLATION INSTRUCTIONS PN 240012809 Rev C 11 15 2020 ...

Page 23: ... Hazard Do not use matches candles open flames or other methods providing ignition source Failure to comply will result in death or serious injury WARNING Fire explosion asphyxiation and burn hazard Boiler piping and gas connections shall be leak tested before placing boiler in operation Failure to follow these instructions and or improper installation could result in death or serious injury NOTIC...

Page 24: ...on 1 Use a thermostat with dry contacts which does not pull any load from the control Use a separate transformer for zone valve wiring 2 Thermostat should be installed on inside wall about four feet above floor 3 NEVER install thermostat on outside wall 4 Do not install thermostat where it will be affected by drafts hot or cold pipes sunlight lighting fixtures televisions fireplace or chimney 5 Ch...

Page 25: ...Modification substitution or elimination of factory equipped supplied or specified components may result in personal injury or loss of life Figure 11 1 Integrated High Limit Electronic Ignition Control PN 240012809 Rev C 11 15 2020 ...

Page 26: ...26 11 WIRING DIAGRAM Figure 11 2 Integrated High Limit Electronic Ignition Control PN 240012809 Rev C 11 15 2020 ...

Page 27: ...ified service technician or your gas supplier 12 3 TO TURN OFF GAS TO THE APPLIANCE 1 Set the thermostat to lowest setting 2 Turn off all electric power to the appliance if service is to be performed 3 Push in gas control knob slightly and turn clockwise to OFF DO NOT FORCE 4 Call qualified service technician WARNING If you do not follow these instructions exactly a fire or explosion may result ca...

Page 28: ...hese instructions could result in death or serious injury A Power remains off until boiler water temperature drops below high limit setting B Circulator continues to operate under this condition until thermostat is satisfied 3 In event the flow of combustion products through boiler venting system becomes blocked A Blocked vent safety switch shuts main burner gas off B If boiler flue way becomes bl...

Page 29: ...e lamp in flue collector through draft relief opening or flue inspection cover With mirror positioned above burners flue gas passageways can be checked for soot or scale Follow this procedure to clean flue gas passageways 1 Remove burner tray from heat exchanger by disconnecting gas valve remove two 2 nuts and pull out the assembly See Figure 14 1 page 30 2 Remove top jacket panel 3 Remove flue in...

Page 30: ...buildup Area around boiler shall be clear and free of combustible materials gasoline and other flammable vapors and liquids Free flow of combustion and ventilating air to boiler and boiler room shall not be restricted or blocked Inspect factory supplied and field sourced low water cutoffs annually or as recommended by low water cutoff manufacturer Flush float type low water cutoffs per manufacture...

Page 31: ...r column from specified pressure listed on boiler rating plate 7 Primary air adjustment is not necessary therefore air shutters are not furnished CHECK SAFETY CONTROL CIRCUIT Test ignition system safety shutoff device after placing boiler in operation Test ignition system safety shutoff device after placing boiler in operation Blocked vent switch and rollout switch can be tested by removing one of...

Page 32: ...Volts 15 Amps 60 Hz The MEA number for the this boiler is 19 79 E 1 Input rating for sea level to 2 000 ft 610m above sea level United States over 2000 ft 610m above sea level Reduce input rate 4 for every 1 000 ft 304m above sea level 2 Net AHRI Water Ratings shown based on piping and pickup allowance of 1 15 Consult manufacturer before selecting boiler for installations having unusual piping and...

Page 33: ...rential 15 F default setting adjustable between 10 and 30 F о F_ Degrees Fahrenheit Press UP or DOWN button until parameter has reached desired value After 60 seconds without any button inputs control automatically returns to READ mode A 4 Display In RUN mode status items and parameters are viewable Example to display setpoint control flashes sp setpoint followed by temperature i e 135 followed by...

Page 34: ...tch closes to do this The control is waiting for this to occur This may last up to one minute If the vent damper switch has not closed after one minute ERR 55 will be displayed e 17 Diagnostics Another diagnostic check The control will also check the safety switches rollout and vent are closed This will be so quick the control may move on before the STA code is flashed Should the safety switches b...

Page 35: ... 2 hard lockouts on this model m 15 Wait for limit to close One of the safety limits rollout vent spill or low water cutoff has been activated Control will resume normal operation once limit is reset Underlying cause why the limit switch opened MUST be investigated n 16 Flame out of sequence Flame signal sensed before trial ignition Appropriate alarm is sent OR Flame signal sensed out of sequence ...

Page 36: ...y models wait for retry or reset at thermostat Check for correct installation and wiring before replacing any component Control module cannot be repaired If it malfunctions it must be replaced Use only qualified service agent to service ignition systems 1 Perform checkout as first step in troubleshooting Check troubleshooting guide to pinpoint cause of problem See Table A7 2 If troubleshooting ind...

Page 37: ...cted reading 1 Check sensor is plugged into control board 2 Check sensor wiring is not damaged 3 Scroll display reading to bt and hold sensor bulb securely in you hand It should read a temperature close to body temperature If not replace sensor 55 Damper end switch failed to close Vent damper must confirm it is open switch closes to do this Control did not receive this signal after waiting one min...

Page 38: ...2 Check all electrical connections are tight 3 Check pilot rod is clean 4 Check for adequate draft 5 Check for adequate combustion air 64 Soft Lockout Internal failure Control is sensing something wrong with electrical circuitry 1 Check all wiring is correct Refer to wiring diagram 2 Check there is a good ground to pilot bracket 65 Hard Lockout Temperature above limit Soft Lockout on S9361A2098 S9...

Page 39: ...r module and pilot burner igniter sensor Check for good metal to metal contact between pilot burner bracket and the main burner Check ground lead from GND BURNER terminal on module to pilot burner Verify connections are clean and tight If wire is damaged or deteriorated replace with No 14 18 gauge moisture resistant thermoplastic insulated wire with 105 C 221 F minimum rating Check ceramic flame r...

Page 40: ...clockwise to increase pilot flame Following adjustment always replace pilot adjustment cover screw and tighten firmly to assure proper gas control operation Figure 12 1 page 27 3 If pilot does not stay lit ensure adequate flame current as follows Turn off boiler at circuit breaker or fuse box Clean flame rod with emery cloth Verify electrical connections are clean and tight Replace damaged wire Ch...

Page 41: ...eturns to closed position 4 Return thermostat to desired position 5 Place vent damper in open position to permit burner operation by using HOLD DAMPER OPEN switch located on damper controller 6 Thermostat controls burner firing as before while damper remains open 7 DO NOT turn damper open manually motor damage will result 8 Set switch to AUTOMATIC OPERATION to close vent damper during burner off c...

Page 42: ...to step v v Place jumper wire across orange and yellow wires in Molex plug see Figure 4 This will create bypass of the damper boiler should then ignite If boiler ignites Go to section B 4 Vent Damper Troubleshooting Guide If boiler does not ignite Problem is not the damper Go to Damper harness Molex on Aquastat Step C NOTE Prior to replacing the damper be sure the problem is not with wire connecti...

Page 43: ...2 POWER Between 4 1 When calling for heat 1 Thermostat not calling for heat 2 Burned out heat anticipator 3 Loose or broken connections 4 Off On operating limit pressure control or low water cut off 5 Off On blocked vent switch or flame roll out 1 Turn thermostat up to call for heat 2 Replace thermostat 3 Tighten repair or replace connection 4 Turn operating limit pressure control or low water cut...

Page 44: ...S OVERRIDE MUST NOT BE USED UNLESS AT LEAST ONE OF THE FOLLOWING CONDITIONS IS TRUE An external energy management system is installed that reduces the boiler water temperature as the heating load decreases This boiler is not used for any space heating This boiler is part of a modular or multiple boiler system having a total input of 300 000 BTU hr or greater This boiler is equipped with a tankless...

Reviews: