background image

INSTALLATION PREPARATION

Verify existing wall sleeve/enclosure:

1. 

RetroAire PTAC/PTHP's are to be used with metal wall 

sleeves.

2. 

Existing front panels must be secured by screws that 

prevent contact with all parts.

3. 

Minor dimensions of openings must not exceed ½ inch 

(12.5mm). 

4. 

Indoor air discharge grill must have dimensions not 

less than 26” x 4”. Grill must separate top surface of 

chassis from top surface of discharge grill by minimum 

of 1 in (25.4mm).

5. 

For all models, outdoor openings must prevent contact 

of all moving parts by means of louvers or grills, with 

minor dimension not exceeding 1 in (25.4mm).

DANGER

Electrical shock hazard — Verify power to existing 

unit is disconnected before removing.  Failure to do 

so will result in death or serious injury.

!

  

CAUTION

Moving parts can cause personal injury. Avoid 

contact with moving parts when testing or servicing 

the unit. Failure to follow these instructions could 

result in minor or moderate injury. 

!

  

Electrical Power Connection

All  wiring shall conform to requirements of authority 

having jurisdiction or in absence of such requirements: 

• United States 

National Electrical Code, ANSI/NFPA 70

UL 1995 4th Addition.

• Canada 

CSA C22.1 Canadian Electrical Code Part 1.

Installer is responsible for ensuring units are installed in 

accordance with all applicable national and local codes. 
UNITS RATED 208/230V — RetroAire unit is wired for 230v 

primary voltage from manufacture. 
Transformer must be rewired by installer if job site voltage 

is 208V. Change transformer tap from orange to red. See 

wiring diagram for details.

1. 

Verify RetroAire unit rating plate for circuit ampacity 

and required breaker or fuse size.

2. 

Verify existing breaker or fuse is correct size.
A.  Replace breaker or fuse if incorrectly sized.
B.  Breakers must be type HACR only.

3. 

Cord connected units — verify wall outlet is correct 

rating. Outlet's blade configuration must match that of 

cord supplied with RetroAire unit.

4. 

Hard-wired units — verify power wiring is correctly 

sized. Inspect existing wiring for deficiencies, such as 

cuts or frayed wires. Replace any deficient wiring if 

found.

5. 

Each unit must have separate branch circuit protected 

by fuse or breaker. Refer to unit rating plate for proper 

wire and breaker or fuse size. Use of extension cords is 

prohibited. 

6. 

DO NOT connect RetroAire unit to circuit with 

incorrectly sized overcurrent protection device.

7. 

All cord-connected 265-volt units must be plugged into 

receptacles within unit subbase or chassis.

8. 

Open power supply disconnect switch. Secure in open 

position during installation. Attach sign stating, "DO 

NOT TURN ON."

9. 

On a plug and receptacle connection, unplug existing 

unit at the wall outlet. DO NOT plug in the new unit 

until installation is complete and start-up checklist has 

been completed.

Remove Old Chassis 

1. 

Disconnect power or unplug cord before proceeding. 

2. 

Remove front of the existing room enclosure to expose 

old chassis.

3. 

Loosen any tie-down bolts or screws. Remove old 

chassis. 

NOTICE

Dispose of old chassis following existing state and 

federal regulations.

4. 

Inspect wall sleeve/cabinet for any rust, holes, or 

damage.
A.  Clean wall sleeve of any dirt.
B.  Repair any damage.
C.  Ensure proper drainage of condensate or rainwater 

to exterior of building.

5. 

Remove or repair old weather seals. Note location for 

installation of any new seals.

6. 

Check wall sleeve/cabinet to ensure all drain holes are 

open and:
A.  Wall sleeve/enclosure is level left to right
B.  Back is pitched to outside by ½ in (12.5mm) 

maximum.

7. 

Before installing new chassis, inspect outdoor louver 

for minimum free area of 70% and remove any 

obstructions. Obstructions restrict air flow over 

condenser coil and may cause damage to the chassis. 

8. 

Follow the installation instructions on the following 

pages.

9. 

DO NOT connect power to the unit or plug in the cord 

until instructions in this manual have been completed.

The Right Fit for Comfort

                                                      

 12 

P/N 240010598, Rev. A [05/12/2014

]

Summary of Contents for R40C

Page 1: ...minal Air Conditioner PTAC Installation Operation Maintenance Manual Replacement for Fedders Model CMEA packaged Terminal Unit TM R40C R41C ECR International Inc 2201 Dwyer Avenue Utica New York 13501 Ph 800 325 5279 Web retroaire com R40C R41C ...

Page 2: ...on Institute These units are tested and rated in accordance with AHRI Standards 310 380 UL 484 Receiving Information 3 Important Safety Information 4 R40C Dimensional Physical Data 5 R41C Dimensional Physical Data 8 General Product Information 10 Features 11 Installation Preparation 12 Installation 13 R40C Baffle Installation 14 R41C Baffle Installation 15 Sequence of Operation 16 Final Inspection...

Page 3: ...l damage identified and complete carrier inspection report Purchaser must notify Manufacturer s Service department of all damage and is responsible for filing any necessary claims with carrier Customer Service 800 228 9364 General Information Installation shall be completed by qualified agency Retain this manual for future reference Installer review this manual to verify unit has been installed co...

Page 4: ...RNING Fire and electrical shock hazard Improper installation could result in death or serious injury Read this manual and understand all requirements before beginning installation The Right Fit for Comfort 4 P N 240010598 Rev A 05 12 2014 WARNING Tampering with PTAC PTHP is dangerous and could result in death or serious injury Do not modify or change this unit Safety Information Installation by qu...

Page 5: ...Figure 1 R40C Dimensions Inches mm Front View Figure 2 R40C Dimensions Inches mm Rear View 5 Made in USA P N 240010598 Rev A 05 12 2014 R40C DIMENSIONAL PHYSICAL DATA ...

Page 6: ...e 3 R40C Chassis Unit Mount Remote Mount Thermostat System Switch SS Fan Speed Switch FSS High Pressure Switch HPS reset 5 POS Terminal Block Optional Knockouts Optional Knockouts The Right Fit for Comfort 6 P N 240010598 Rev A 05 12 2014 ...

Page 7: ...R40C DIMENSIONAL PHYSICAL DATA Figure 4 R40C Chassis Electrical Box Rating Plate Remove Screws to Open Door Electrical Diagram Open Close 7 Made in USA P N 240010598 Rev A 05 12 2014 ...

Page 8: ...nsions Inches mm Front View R41C DIMENSIONAL PHYSICAL DATA Ground Terminal Block High Pressure Switch HPS reset 12 Position Molex Knockouts for Optional Switches The Right Fit for Comfort 8 P N 240010598 Rev A 05 12 2014 ...

Page 9: ...Figure 6 R41C Chassis Electrical Box R41C DIMENSIONAL PHYSICAL DATA Rating Plate Remove Screw to Open Door Electrical Diagram Open Close 9 Made in USA P N 240010598 Rev A 05 12 2014 ...

Page 10: ... of hydronic valve motor Remote mount controls include fan speed control and fresh air switch if equipped All units are equipped with manual reset high pressure switch which prevents abnormal high pressure operation increasing compressor reliability Microprocessor Control Board Universal control board is used in straight cooling electric resistance heat hydronic heat or cooling heat pump applicati...

Page 11: ... a fire can occur Tested in accordance with Underwriters Laboratories cord set offers a unique passive operation meaning unit does not require resetting if main power is interrupted FEATURES Hydronic Heating Optional Hydronic heat package may be selected in lieu of electric heat Heating operation is same as that of units with electric heat Aquastat Connection Optional All replacement PTAC PTHP s w...

Page 12: ...configuration must match that of cord supplied with RetroAire unit 4 Hard wired units verify power wiring is correctly sized Inspect existing wiring for deficiencies such as cuts or frayed wires Replace any deficient wiring if found 5 Each unit must have separate branch circuit protected by fuse or breaker Refer to unit rating plate for proper wire and breaker or fuse size Use of extension cords i...

Page 13: ... to jumper using 2 crimp popcorns C Place connector back into original location Refer to wiring diagram on unit for details INSTALLATION 4 Install Baffles Install correct condenser baffles for proper performance of unit See Figures 7 and 8 A Slide unit back out of wall sleeve B Remove both sets of provided baffles from accessory bag Install only one set of left and right side baffles on the conden...

Page 14: ...R40C BAFFLE INSTALLATION Figure 7 R40C Baffle Options Standard Baffle Standard Baffle Standard Baffle Standard Baffle The Right Fit for Comfort 14 P N 240010598 Rev A 05 12 2014 ...

Page 15: ...ptions and Field Ground Connection Standard Baffle Standard Baffle Optional Baffle For Deeper Wall Sleeves Optional Baffle For Deeper Wall Sleeves Standard Baffle Field GRND Connected to Ground Terminal 15 Made in USA P N 240010598 Rev A 05 12 2014 ...

Page 16: ...ED is set to blink a 2 flash code Timer prevents compressor from rapid cycling After Anti Short Cycle Timer expires Processor Board Trouble Code LED is set to blink 1 blink Trouble Code indicating normal operation R_ _C Cooling Operation Unit Mount Controls With System Switch SS set to Cool and Fan Cycle Switch FCS set to On Continuous Fan Operation indoor fan motor starts If Fan Cycle Switch FCS ...

Page 17: ...180 seconds at anytime during heating call compressor and outdoor fan motor are de energized and auxiliary heat is energized Anti Short Cycle Timer is initiated prohibiting compressor operation for 180 seconds Processor Board Trouble Code LED flashes 3 blink Trouble Code indicating auxiliary heat operation Heating operation with auxiliary heat continues until outdoor coil sensor reaches 50º F 10º ...

Page 18: ...eet metal panels are in place and secure 8 Attach front panel to the existing cabinet enclosure 9 Verify nothing interferes with room discharge air or return air of units Examples Check for curtains or drapes that obstruct air flow See Figure 10 and Figure 11 Check for plush carpeting that can obstruct return air These types of obstructions can cause serious damage to the chassis Any obstruction o...

Page 19: ...ects heat pump or straight cooling Pins determine whether unit operates as straight cooling or as heat pump See Figures 12 and 13 Jumper right pin to center pin for heat pump operation Jumper left pin to center pin for straight cooling operation TEST Jumper selects normal or test mode NOTICE Do not leave unit operating with TEST jumper in TEST position Jumper is for testing only See Figure 13 and ...

Page 20: ...FINAL INSPECTION START UP TEST JUMPER HEAT PUMP JUMPER Figure 14 TEST jumper selects normal or test mode The Right Fit for Comfort 20 P N 240010598 Rev A 05 12 2014 ...

Page 21: ... time delays including anti short cycle and purge times See Figure 13 page 19 6 Verify unit is wired correctly including requirements on page 16 7 Connect Electric power to unit 8 Turn unit on Verify proper operation 9 Verify condensate removal A Pour water into base pan B Place unit in cooling mode with condenser fan operating verify water is picked up by slinger ring and thrown onto outdoor coil...

Page 22: ...ond purge time has elapsed 9 If warmer room temperature is desired adjust thermostat to warmer temperature setting which opens the hydronic valve and turns on the indoor fan 10 If cooler room temperature is desired adjust thermostat to cooler temperature setting Hydronic valve closes and indoor fan switches off after sixty second purge time has elapsed 11 Place thermostat or system switch in OFF p...

Page 23: ...perature is desired adjust thermostat to warmer temperature setting which will turn electric heater back on 5 If cooler room temperature is desired adjust thermostat to cooler temperature setting until electric heater turns off Indoor fan will switch off after sixty second purge time has elapsed 6 Place thermostat or system switch in OFF position All operation stops Electric Heat Models Manually r...

Page 24: ...s along rear flange of base pan are free of debris WARNING Electrical shock hazard Disconnect power to unit before servicing or accessing control compartment Failure to do follow these instructions could result in death or serious injury NOTICE Perform regular service and maintenance by qualified service agency at least once every 12 months to assure safe trouble free operation and maximum efficie...

Page 25: ... K 35 F 1 6 C 30 0 K 30 F 1 1 C 34 4 K Figure 17 Control Board Sensor Connections Indoor Sensor Connections Outdoor Sensor Connections 11 Air leaks may make the conditioned area uncomfortably drafty or produce noises Visually inspect foam gasket between wall and unit taking note of separation between air inlet for condenser and condenser coil discharge These two areas must be sealed off from each ...

Page 26: ...utton will pop out when limit switch opens Push in to reset Use long blunt tool to depress limit switch reset button Use long blunt tool to depress limit switch reset button Remove plug to access Limit Switch Reset Button Replace Plug when complete Remove plug to access Limit Switch Reset Button Replace Plug when complete The Right Fit for Comfort 26 P N 240010598 Rev A 05 12 2014 ...

Page 27: ...rol board and make resistance measurements compare to following sensor resistances Indoor and outdoor coil sensor wires are labeled as is control board 77 F 10KOhms 50 F 19 9KOhms 35 F 30KOhms 30 F 34 4KOhms Thermostat is satisfied but fan is still running If thermostat is set to auto mode once thermostat is satisfied fan will stay energized for extra 60 seconds to purge unit of excess cool or war...

Page 28: ... W HA TCA THA MCA MOCP Plug 115V 104 8 0 45 6 1 4 0 09 1 6 0 125 N A N A N A N A 11 N A 13 0 20 5 15P 208 230V 197 4 0 22 2 0 6 0 08 0 71 0 09 0 N A N A N A 5 3 N A 6 3 15 6 15P 2 208 1636 7 9 8 5 10 6 15 6 15P 230 2000 8 7 9 3 11 6 3 208 2454 11 8 12 4 15 5 20 6 20P 230 3000 13 13 6 17 1 4 208 3271 15 7 16 3 20 4 25 6 30P 230 4000 17 4 18 22 5 5 208 4089 19 7 20 3 25 3 30 6 30P 230 5000 21 7 22 3...

Page 29: ...door Fan Motor Outdoor Fan Motor Electric Heat Unit Electrical Ratings Volt Min RLA LRA FLA Hp FLA Hp Htr Volt W HA TCA THA MCA MOCP Plug 115V 104 7 5 47 1 4 0 09 1 6 0 125 5 115 1250 10 9 10 5 12 3 15 3 20 5 20P LEGEND RLA Rated Load Amps FLA Full Load Amps Hp Horse Power W Watts HA Heater Amps TCA Total Cooling Amps THA Total Heating Amps MCA Minimum Circuit Amps MOCP Maximum Over Current Protec...

Page 30: ...NOTES The Right Fit for Comfort 30 P N 240010598 Rev A 05 12 2014 ...

Page 31: ...ely corrosive installation environments equipment usage during construction shipping or handling RETROAIRE IS ALSO NOT RESPONSIBLE FOR Damages caused by faulty or interrupted power supply or electrical service Damages caused by acts of God including but not limited to wind hail floods lightning earthquakes or other conditions beyond the control of RetroAire FURTHER LIMITATIONS All implied warranti...

Page 32: ...TM ECR International Inc 2201 Dwyer Avenue Utica New York 13501 Phone 1 800 325 5279 Web retroaire com ...

Reviews: