8.2 Electrical Connections
• Boiler requires 120V 60Hz power supply. Verify
electrical supply is polarized.
• Boiler shall be grounded and on dedicated circuit.
• Shall be one common isolator, providing electrical
isolation for boiler and any external controls. Using
PVC insulated cable 18 AWGx3C 221°F (105°C).
• All wiring must be installed in accordance with
requirements of the National Electrical Code and any
additional national, state, or local code requirements
having jurisdiction. All wiring must be N.E.C. Class 1.
• Canada, installation must conform to CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
• If replacing original boiler wiring use only TEW 105°C
or equivalent.
•
If appliance is connected to in floor system, install
limit thermostat to prevent latter from overheating.
DANGER
Electrocution Hazard! HIGH VOLTAGE -
Connections in terminal block M1 are high
voltage (120V / 60Hz). Before making
connections, verify appliance is disconnected
from power supply. Respect the input polarity
on terminal block M1: L (LINE) - N (NEUTRAL).
Failure to follow these instructions WILL result in
death or serious injury.
!
8 - ELECTRICAL CONNECTIONS
FIGURE 8-1 Junction Box Left side of Boiler
Junction Box
with Knockouts
and grommets
8.1 General
Electrically bond boiler to ground in accordance with
requirements of authority having jurisdiction. Refer to:
• USA- National Electrical Code, ANSI/NFPA 70.
• Canada - Canadian Electrical Code, Part I, CSA
C22.1: Safety Standard for Electrical Installations.
• Install all wiring in accordance with requirements of
National Electrical Code and any additional national,
state, or local code requirements having jurisdiction.
• In Canada, installation must conform to CSA C22.1
Canadian Electrical Code Part 1 and any local codes.
• All wiring shall be N.E.C. Class 1.
• Boiler shall be electrically grounded in accordance
with the National Electrical Code, ANSI/NFPA No.
70-latest edition.
• Boiler requires a 120V 60Hz power supply. Ensure
electrical supply is polarized.
• There shall only be one common isolator, providing
complete electrical isolation, for boiler and any
external controls. Using PVC insulated cable 12
AWGx3C 221°F (105 ºC).
Model
Size
75 &
100
115
125
150
165
205
Power Supply
120V - 60Hz
Power
Consumption 118 W 125 W 133 W 142 W
173 W
182 W
Internal Fuse
(Qty. 2)
F3.15 A
Electrode
Spark Gap
1/8" to 3/16" [3.1 mm to 4.7 mm]
240013503 REV A, [03/15/2022]
Summary of Contents for UTICA BOILERS MACF-115
Page 2: ...MACF 150...
Page 4: ...MAHF 125...
Page 77: ...73 A 1 MODEL 75 100 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 78: ...74 A 2 MODEL 125 Heat Only APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 79: ...75 APPENDIX A WIRING DIAGRAMS A 3 MODEL 165 Heat Only 240013503 REV A 03 15 2022...
Page 80: ...76 APPENDIX A WIRING DIAGRAMS A 4 MODEL 115 Combi 240013503 REV A 03 15 2022...
Page 81: ...77 A 5 MODEL 150 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 82: ...78 A 6 MODEL 205 Combi APPENDIX A WIRING DIAGRAMS 240013503 REV A 03 15 2022...
Page 117: ...33 PN 240012875 REV D 03 15 2022 MODEL 75 100 HEAT ONLY 75 100 HEAT ONLY WIRING DIAGRAM...
Page 118: ...34 PN 240012875 REV D 03 15 2022 MODEL 125 HEAT ONLY 125 HEAT ONLY WIRING DIAGRAM...
Page 119: ...35 PN 240012875 REV D 03 15 2022 MODEL 165 HEAT ONLY 165 HEAT ONLY WIRING DIAGRAM...
Page 120: ...36 PN 240012875 REV D 03 15 2022 115 COMBI WIRING DIAGRAM MODEL 115 COMBI...
Page 121: ...37 PN 240012875 REV D 03 15 2022 MODEL 150 COMBI 150 COMBI WIRING DIAGRAM...
Page 122: ...38 PN 240012875 REV D 03 15 2022 MODEL 205 COMBI 205 COMBI WIRING DIAGRAM...
Page 128: ...44 PN 240012875 REV D 03 15 2022 LOW WATER CUTOFF LOW WATER CUTOFF DETAIL NO NO YES...
Page 133: ...49 PN 240012875 REV D 03 15 2022 3 FAULT SOLUTION SECTIONS...