ECR International Iverter Installation, Operation And Maintenance Manual Download Page 20

Page 

20

 

6. Feed the signal wire through this slot, from

the back of the unit to the front.

7. Facing the front of the unit, match the wire

colors with the labels on the terminal block,
connect the u-lug and and firmly screw each
wire to its corresp onding terminal.

 CAUTION

DO NOT MIX UP LIVE AND NULL WIRES

This is dangerous, and can cause the air 
conditioning unit to malfunction.

8. After checking to make sure every conn ection

is secure, use the cable clamp to fasten the
signal cable to the unit. Screw the cable clamp
down tightly.

9. Replace the wire cover on the front of the

unit, and the plastic panel on the back.

 NOTE ABOUT WIRING

 

 

 

 

 

Step 7: Wrap piping and cables

Before passing the piping, drain hose, and the 
signal cable through the wall hole, you must 
bundle them together to save space, protect 
them, and insulate them.
1. Bundle the drain hose, refrigerant pipes, and

signal cable according to 

Fig. 

4

.1

0

 

.

Indoor Unit

Space behind unit

Refrigerant piping

Drain hose

Signal wire

Insulation tape

DRAIN HOSE MUST BE ON BOTTOM

Make sure that the drain hose is at the bottom 
of the bundle. Putting the drain hose at the 
top of the bundle can cause the drain pan 
to overflow, which can lead to fire or water 
damage.

DO NOT INTERTWINE SIGNAL CABLE WITH 
OTHER WIRES

While bundling these items together, do not 
intertwine or cross the signal cable with any 
other wiring.

2.

Using adhesive vinyl tape, attach the drain
hose to the underside of the refrigerant pipes.

3.

Using insulation tape, wrap the signal wire,
refrigerant pipes, and drain hose tightly
together. Double-check that all items are
bundled in accordance with 

Fig. 

4

.1

0

 

.

DO NOT WRAP ENDS OF PIPING

When wrapping the bundle, keep the ends 
of the piping unwrapped. You need to access 
them to test for leaks at the end of the 
installation process (refer to 

Electrical Checks 

and Leak Checks

 section of this manual).

Step 8: Mount indoor unit
If you installed  new connective piping to the 
outdoor unit,

 do the following:

1. If you have already passed the refrigerant

piping through the hole in the wall, proceed
to Step 4.

2. Otherwise, double-check that the ends of the

refrigerant pipes are sealed to prevent dirt or
foreign materials from entering the pipes.

3. Slowly pass the wrapped bundle of refrigerant

pipes, drain hose, and signal wire through the
hole in the wall.

4. Hook the top of the indoor unit on the upper

hook of the mounting plate.

5. Check that unit is hooked firmly on mounting

by applying slight pressure to the left and
right-hand sides of the unit. The unit should
not jiggle or shift.

6. Using even pressure, push down on the

bottom half of the unit. Keep pushing down
until the unit snaps onto the hooks along the
bottom of the mounting plate.

7. Again, check that the unit is firmly mounted

by applying slight pressure to the left and the
right-hand sides of the unit.

Fig. 

4

.12

Indoor Unit 

Installation

THE WIRING CONNECTION PROCESS MAY
DIFFER SLIGHTLY BETWEEN UNITS. 

Summary of Contents for Iverter

Page 1: ...ler Ductless Split System Heat Pumps Installation Operation Maintenance Manual ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Phone 800 325 5479 Web enviromaster com PN 615000156 REV A 01 04 2...

Page 2: ...plate to wall 14 3 Drill wall hole for connective piping 14 4 Prepare refrigerant piping 16 5 Connect drain hose 17 6 Connect signal cable 19 7 Wrap piping and cables 20 8 Connect indoor power wire 20...

Page 3: ...B Connection Instructions Refrigerant Piping 23 1 Cut pipe 23 2 Remove burrs 24 3 Flare pipe ends 24 4 Connect pipes 25 Air Evacuation 27 1 Evacuation Instructions 27 2 Note on Adding Refrigerant 28 E...

Page 4: ...Unit Specifications and Features 32 Owner s Manual Table of Contents 9 SAFETY FIRST Manual Operation Without Remote 37 10 Care and Maintenance 38 Troubleshooting 40 11 12...

Page 5: ...can cause explosion and injury Do not allow children to play with the air conditioner Children must be supervised around the unit at all times 1 Installation must be performed by an authorized dealer...

Page 6: ...gned air conditioning units is highly recommended CAUTION Do not installthe unit in a location that may be exposed to combustible gas leaks If combustible gas accumulates around the unit it may cause...

Page 7: ...e Safety Precautions CAUTION If the air conditioner is used together with burners or other heating devices thoroughly ventilate the room to avoid oxygen deficiency Turn off the air conditioner and unp...

Page 8: ...ontroller holder Dry battery AAA LR03 Air freshening filter Seal Drain joint Mounting plate 1 Accessories The air conditioning system comes with the following accessories Use all of the installation p...

Page 9: ...Page 9 Name Shape Quantity Parts you must purchase Consult the dealer about the pipe size Connecting pipe assembly Liquid side Gas side 6 35 1 4i n 9 52 3 8in 9 52 3 8in 12 7 1 2in 16 5 8in...

Page 10: ...ion Location Page 14 Attach Mounting Plate Page 15 Drill Wall Hole Page 15 Installation Summary Indoor Unit 2 Installation Overview Determine Wall Hole Position Page 15 1 2 3 4 12cm 4 75in 2 3m 90 55i...

Page 11: ...Page 11 Mount Indoor Unit Page 20 STEP 8 Wrap Piping and Cable Page 20 L N S Connect Piping Page 23 Connect Wiring Page 19 Prepare Drain Hose Page 16 5 6 7 8 9 Installation Overview...

Page 12: ...The actual shape of your indoor unit may be slightly different The actual shape shall prevail Wall Mounting Plate Power Cable Some Units Refrigerant Piping Signal Cable Remote Control Some Units Drai...

Page 13: ...rate Strong enough to support the weight of the unit A location at least one meter from all other electrical devices e g TV radio computer DO NOT install unit in the following locations Near any sourc...

Page 14: ...the wall by tightening the screws directly into the clip anchors Step 3 Drill wall hole for connective piping You must drill a hole in the wall for refrigerant piping the drainage pipe and the signal...

Page 15: ...2 1in 47mm 1 85in 76mm 3in 53 5mm 2 1in 47mm 1 85in 148 7mm 5 85in 151mm 5 95in 174 3mm 6 85in Indoor unit outline 172mm 6 8in 362mm 14 25in Left rear wall hole 65mm 2 5in Right rear wall hole 65mm 2...

Page 16: ...s too difficult to remove by hand Knock out Panel 3 Use scissors to cut down the length of the insulating sleeve to reveal about 15cm 6in of the refrigerant piping This serves two purposes To facilita...

Page 17: ...r a small amount of water into the drain pan to make sure that water flows from the unit smoothly NOTE ON DRAIN HOSE PLACEMENT Make sure to arrange the drain hose according to Fig 4 5 DO NOT kink the...

Page 18: ...1 5 times the maximum current of the unit 6 If connecting power to fixed wiring a switch or circuit breaker that disconnects all poles and has a contact separation of at least 1 8in 3mm must be incor...

Page 19: ...is designed with a fuse to provide overcurrent protection The specifications of the fuse are printed on the circuit board such as T3 15A 250VAC T5A 250VAC etc 1 Prepare the cable for connection a Str...

Page 20: ...2 Using adhesive vinyl tape attach the drain hose to the underside of the refrigerant pipes 3 Using insulation tape wrap the signal wire refrigerant pipes and drain hose tightly together Double check...

Page 21: ...structions 4 Keep pipe connection point exposed to perform the leak test refer to Electrical Checks and Leak Checks section of this manual 5 After the leak test wrap the connection point with insulati...

Page 22: ...her and nut on the end of each expansion bolt 5 Thread expansion bolts through holes in mounting brackets put mounting brackets in position and hammer expansion bolts into the wall 6 Check that the mo...

Page 23: ...plit Air Conditioner 15 000 25 82ft 10 33ft 15 000 and 24 000 30 98 5ft 20 66ft 24 000 and 36 000 50 164ft 25 82ft 36 000 and 60 000 65 213ft 30 98 5ft Connection Instructions Refrigerant Piping Step...

Page 24: ...nds with PVC tape to prevent foreign materials from entering the pipe 2 Sheath the pipe with insulating material 3 Place flare nuts on both ends of pipe Make sure they are facing in the right directio...

Page 25: ...ft 6 35 0 25 1 500 11lb ft 1 600 11 8lb ft 9 52 0 375 2 500 18 4lb ft 2 600 19 18lb ft 12 7 0 5 3 500 25 8lb ft 3 600 26 55lb ft 16 0 63 4 500 33 19lb ft 4 700 34 67lb ft DO NOT USE EXCESSIVE TORQUE...

Page 26: ...nd 4 Using a spanner grip the body of the valve Do not grip the nut that seals the service valve See Fig 5 10 USE SPANNE R TO GRIP MAIN BOD Y OF VALVE Torque from tightening the flare nut can snap off...

Page 27: ...ipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual Check to make sure all wiring is connected properly Evacuat...

Page 28: ...hose from the service port 12 Using hexagonal wrench fully open both the high pressure and low pressure valves 13 Tighten valve caps on all three valves service port high pressure low pressure by hand...

Page 29: ...resolve the cause of the leakage Gas Leak Checks There are two different methods to check for gas leaks Soap and Water Method Using a soft brush apply soapy water or liquid detergent to all pipe conn...

Page 30: ...oller to turn it on 3 Press the MODE button to scroll through the following functions one at a time COOL Select lowest possible temperature HEAT Select highest possible temperature 4 Let each function...

Page 31: ...control return unit to normal operating temperature b Using insulation tape wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process IF AMBIENT...

Page 32: ...ing when anti cold air feature is turned on when unit is self cleaning when freeze protection is turned on Display Code Meanings Functional Filter On Front of Main Filter Some Units Louver Front Panel...

Page 33: ...ormance of your unit do the following Keep doors and windows closed Limit energy usage by using TIMER ON and TIMER OFF functions Do not block air inlets or outlets Regularly inspect and clean air filt...

Page 34: ...s the air conditioner will continue operate at very low power to dry up condensed water and prevent mildew growth Unit Specifications and Features Wi Fi Control some units Wi Fi control allows you to...

Page 35: ...Fig 9 2 When using COOL or HEAT mode setting the louver at too vertical an angle can reduce the performance of the unit due to restricted air flow Do not move louver by hand This will cause the louver...

Page 36: ...after 1 hour and will increase an additional 1 C 2 F after another hour When in HEAT mode the unit will decrease the temperature by 1 C 2 F after 1 hour and will decrease an additional 1 C 2 F after...

Page 37: ...nel of the indoor unit 2 Locate the MANUAL CONTROL button on the right hand side of the unit 3 Press theMANUAL CONTROL button one time to activate FORCED AUTO mode 4 Press theMANUAL CONTROL again to a...

Page 38: ...th Make sure to clean the filter once every two weeks 1 Lift the front panel of the indoor unit 2 Grip the tab on the end of the filter push it up slightly then pull it a little towards yourself 3 Now...

Page 39: ...on the indoor unit will flash nF This is a reminder to replace your filter After 15 seconds the unit will revert to its previous display To reset the reminder press the LED button on your remote cont...

Page 40: ...the unit from overloading The unit cannot be restarted within three minutes of being turned off The unit may change its setting to prevent frost from forming on the unit Once the temperature increases...

Page 41: ...e Dust is emitted from either the indoor or outdoor unit The unit may accumulate dust during extended periods of non use which will be emitted when the unit is turned on This can be mitigated by cover...

Page 42: ...et of either unit is blocked Turn the unit off remove the obstruction and turn it back on Doors and windows are open Make sure that all doors and windows are closed while operating the unit Excessive...

Page 43: ...the voltage Poor heating performance The outdoor temperature is lower than 7 C 44 5 F Use auxiliary heating device Cold air is entering through doors and windows Make sure that all doors and windows a...

Page 44: ...CS368U AB 16122000002334 20150820 The design and specifications are subject to change without prior notice for product improvement Consult with the sales agency or manufacturer for details...

Reviews: