10
8.OPERATION
Most single phase units are operated without start relay or start capacitor. Such systems should
be off for a minimum of 5 minutes before restarting to allow equalization of pressures. The
thermostat should not be moved to cycle unit without waiting 5 minutes. To do so may cause
the compressor to stop on an automatic open overload device or blow a fuse. Poor electrical
service can cause nuisance tripping in overloads or blow fuses.
The compressor has an internal overload protector. Under some conditions, it can take up to 2
hours for this overload to reset. Make sure overload has had time to reset before condemning
the compressor.
9.MISCELLANEOUS
9.1.
Replacement Parts
Contact your local distributor for a complete parts list.
9.2.
Troubleshooting Guide
Refer to the troubleshooting guide (
Table 6
) included in this manual.
9.3.
Wiring Diagram
Refer to the appropriate wiring diagram included in this manual.(P12)
Table 6:Troubleshooting Guide
! WARNING
- Disconnect all electrical power to the unit before servicing. Disconnect power to
both the indoor and outdoor units. NOTE: There may be more than one electrical disconnect switch.
Failure to shut off power can cause electrical shock resulting in personal injury or death.