 DPM-2 SETUP

Common Terminology

Reset Ratio:

 The ratio between supply water temperature 

and outdoor temperature� For example, a ratio of 1�0 or 

1:1 means, for every one degree the outdoor temperature 

decreases, there will be a one degree increase in supply 

water temperature�

Max. Temp:

 The maximum supply water temperature when 

the outdoor temperature is 0°F�

Differential:

 

Measurement used to determine when the 

boiler will turn on and off. A ten degree differential will turn 

the boiler on at five degrees below the control point and 

off at five degrees above while a twenty degree differential 

will turn the boiler on at ten degrees above and off at ten 

below. The effect of differential is to prevent quick cycling of 

the boiler� 

General Wiring Notice

All primary wiring must be 14 AWG minimum. Torque 

terminal screws 6 to 7 inch pounds.

U.S.A. - 

National Electric Code and any other nation-

al, state, or local code requirements. Wiring must be 

N.E.C. Class 1.

CANADA -

 C.S.A. C22.1 Canadian Electrical Code 

Part 1 and any other national, provincial, or local 

code requirements. Wiring must be C.S.A. C22.1 

C.E.C. Part 1.

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

Electrical Specifications & Wiring

 WARNING

Electrical shock hazard� Disconnect power before 

installing or servicing� Failure to follow these 

instructions could result in death or serious injury�

!

  

DPM-2 Control Set-up

1. 

Determine the reset ratio and adjust “Reset Ratio Trim 

Pot.” If  heat curve is unknown, try ratio of 1.0.

2. 

Turn “Max. Temp. Trim Pot” to design temperature of 

supply water (water temperature needed when outdoor 

temperature is 0°F)�

IMPORTANT:

 Boiler high limit must be set higher than 

“Max. Temp.” setting 

plus

 “Differential” or unit may operate 

erratically� 

3. 

Set “Differential Trim Pot” to scale (10°F). Boiler will 

turn off when water is 5°F above control point and 

back on again when water is 5°F below control point� 

If boiler does “Quick Cycle,” increase trim pot. Optimal 

performance is obtained when this setting is as low as 

possible, but still allows for a reasonable cycle time�

6

PN 240005132 Rev. D [11/15/2021]

Summary of Contents for ARGO DPM-2

Page 1: ...OPERATION MAINTENANCE MANUAL Information and specifications outlined in this manual in effect at the time of printing of this manual ECR International Inc reserves the right to discontinue change specifications or system design at any time without notice and without incurring any obligation whatsoever ARGO DPM 2 OUTDOOR TEMPERATURE SETBACK CONTROL DPM 2 ...

Page 2: ...ctions 5 OutdoorSensorInstallation 5 WaterSupplySensorInstallation 5 Electrical Specifications Wiring 6 DPM 2 Setup 6 Wiring Applications 7 Sequence of Operation 10 Troubleshooting 10 Replacement Parts 11 Technical Support 12 TABLE OF CONTENTS Keep this manual near boiler Retain for future reference 2 PN 240005132 Rev D 11 15 2021 ...

Page 3: ...PM 2 Outdoor Temperature Setback Control with its installation and operation to assure normal trouble free operation Argo controls are designed and manufactured with quality components for maximum life and durability and require minimal service To ensure a satisfactory installation it is imperative that the instructions be followed carefully before operating the control Failure to do so may result...

Page 4: ...Block 2 Outdoor Sensor Terminal Block 3 Priority Input Terminal Block 4 Priority LED 5 Max Temp Trim Pot 6 Differential Trim Pot 7 Reset On LED 8 Power Switch 9 24 VAC IN Common Terminal Block 10 To Boiler T T Terminal Block 11 From T Stat or X X Terminal Block 12 Ribbon Cable Data Port 13 Reset Ratio Trim Pot 4 PN 240005132 Rev D 11 15 2021 ...

Page 5: ...es amplified by mounting surfaces such as sheet metal plasterboard and similar materials place rubber or felt washers between the case and the mounting surface 1 Position the control and mark the mounting holes 2 Start screws not provided for the keyhole type mounting holes in the upper corner s Tighten the screws down to about 3mm from the surface 3 Hang the control on the screw s position the ca...

Page 6: ...ust be N E C Class 1 CANADA C S A C22 1 Canadian Electrical Code Part 1 and any other national provincial or local code requirements Wiring must be C S A C22 1 C E C Part 1 INSTALLATION MANUAL AND OPERATING INSTRUCTIONS Electrical Specifications Wiring WARNING Electrical shock hazard Disconnect power before installing or servicing Failure to follow these instructions could result in death or serio...

Page 7: ...T USE 210 MAX TEMP OR X X FROM T STAT POWER ON O DATA PORT FROM ARM 1 5 RESET RATIO W C 1 0 5 150 0 7 0 6 0 8 1 0 180 24VAC COMMON TO T T BOILER DIFF 5 REG 2 REG 1 15 10 ON PRIORITY OUTDOOR RESET CONTROL DPM 2 OUTDOOR SENSOR WATER SENSOR PRIORITY INPUT CIRC L1 HOT N ZONE 2 24 VAC X2 END SW 2 END SW 1 X1 X1 X2 COM ZONE 1 1 2 3 4 1 2 T ON X X T T Zone Valve Controller AZ 3 ZONE 3 4 3 1 2 4 3 T T T R...

Page 8: ...WITCHES ZR ZC DPM 2 ZONE VALVE PUMP PRIORITY Z1 Z2 Z3 Z4 T T T T T T T T NOTE REFER TO AZ CP MANUAL FOR AZ CP OPERATION ON OFF KEY ON OPTION SWITCHES ZONE VALVE PUMP ZR ZC DPM 2 PRIORITY WATER SENSOR INPUT PRIORITY DO NOT USE SENSOR OUTDOOR SENSOR OUTDOOR SENSOR WATER DPM 2 ON PRIORITY TRIMPOTS FOR DO NOT USE FACTORY CALIBRATION OUTDOOR RESET CONTROL DPM 2 DO NOT USE RIBBON CABLE RED WIRE MAD 1 RE...

Page 9: ...INSTALLATION MANUAL AND OPERATING INSTRUCTIONS DPM 2 OUTDOOR TEMPERATURE SETBACK CONTROL WITH ARGO ARM 4P CONTROL 9 PN 240005132 Rev D 11 15 2021 ...

Page 10: ...o confirm RTD Sensor is functioning properly 1 Remove both RTD leads from the terminal block on the control board 2 Use a multimeter to take an ohm reading across the RTD leads A properly functioning RTD Sensor will produce a reading of approximately 1005 ohms at 70 F while a faulty RTD will read either 0 or 1 3 Replace RTD if necessary Troubleshooting Tips 1 If the setup check is okay a problem m...

Page 11: ...INSTALLATION MANUAL AND OPERATING INSTRUCTIONS REPLACEMENT PARTS DESCRIPTION PART NUMBER Temperature Sensor Z63 Outdoor Sensor Shield S60 Replacement Parts 11 PN 240005132 Rev D 11 15 2021 ...

Page 12: ... your model number available when calling Information Needed When Calling Model Number Installation Date Installer INSTALLATION MANUAL AND OPERATING INSTRUCTIONS Technical Support All specifications subject to change without notice 2021 ECR International Inc 2201 Dwyer Avenue Utica NY 13501 Tel 800 325 5479 www ecrinternational com ...

Reviews: