IR FLAME DETECTOR

RIV-601P/F 

EN 54-10 class 1

 

VdS approval G 211093

EC-certificate of conformity no. 0786 - CPD - 21103

 

 

application manual

Summary of Contents for GTS RIV-601F

Page 1: ...N 54 10 class 1 rev 5 NOV18 ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com IR FLAME DET...

Page 2: ......

Page 3: ...ation with PARTIAL area coverage 11 Diagonal application with FULL area coverage 12 Vertical application of two detectors with FULL area coverage 13 Diagonal application of two detectors with FULL are...

Page 4: ...ire detector device that responds immediately to the thermal infrared radiation emitted by fire and is tuned to the pulse frequency of the flame to ignore sun lamps and other light and infrared radiat...

Page 5: ...tle attenuated by dust much less than light is Therefore a frequent window cleaning is not required Also smoke does not blind the detector which is operating well with fires in heavy smoke IR flame de...

Page 6: ...y 2 3 of the distance which means that the smallest detectable flame size is 2 3 of the distance For example at 10m the smallest flame size is 20cm Typical covering figure is 400 square meters at 20m...

Page 7: ...the top of every terminal and on the circuit board just before the connector Note 1 It is highly recommended to connect the enclosure base to a good ground line using the ground terminal provided insi...

Page 8: ...me detector mechanical dimensions IP66 grade protection dust and water spray Dimensions 180x85x65 H mm mounting holes 125x70mm Weight 700grams 85 65 70 125 140 39 180 Cable fitting M25 RIV 601P F IR F...

Page 9: ...inside Sensitivity reduced to 4 of the distance M32x1 5 cable entry RIV 601P F 200 140 141 290 260 225 220 255 n 1 hole M32x1 5 FIELD OF VIEW 90 15 40 170 4 mounting holes 260x220mm 245 245 86 117 23...

Page 10: ...r during the installation by turning the one turn screwdriver potentiometer The detector field of view is a 90 cone starting at the optical window centre Outside the field of view the detector sensiti...

Page 11: ...looking down vertically on the centre at a height that is 0 7 times the side of the area square For example from a height of 10 m a floor area of 14x14m can be controlled This sort of installation us...

Page 12: ...areas on the corners are out The smallest detectable flame size is 20 cm on the centre 2 of 10m distance and 28cm on the border 2 of 14m distance The limit of this application could be a room 10m hig...

Page 13: ...two times as much as under the detector corner This disadvantage must be considered when choosing this type of application Also the diagonal mounting makes the detector seeing other strong infrared l...

Page 14: ...rformance than the C type of the previous page In the case of a room 10 m high with a floor of 14x28 m the smallest detectable flame size is 20cm on each area centre 2 of 10m distance and 28cm on each...

Page 15: ...first case the room is 10m high and has a floor of 20x40m In the second case the room is the same but the two detectors are mounted in a slightly different position The disadvantages of the diagonal m...

Page 16: ...revent both rain or snow to build up over the detector enclosure and to prevent as well the detector from seeing directly the sun or other strong lamps present around so as to avoid false alarms In th...

Page 17: ...ctor Normally it is high 24V In alarm goes low 0 1V or higher depending on the load Max load 50mA to 24V One changeover SPDT relay contact on the C R L terminals rated 1A 30Vdc C R normally closed con...

Page 18: ...r dirt build up but only the electronic circuit operation Then if the optical window is dirty the sensitivity is reduced and the fire could not be detected even if the test is ok Anywhere a small dust...

Page 19: ...L1 line must be delayed for at least 5 10 seconds before giving a fire alarm signal when C L closes The fault warning signal must be delayed for at least 10 20 seconds before the C R closure can be c...

Page 20: ...the detector from issuing false alarms still assuring a good sensitivity level One filter disc decreases the detector sensitivity from the standard value of 2 to 3 Then the smallest detectable flame s...

Page 21: ...esigned for IR Flame Detector RIV 601P F mounting Both the steering arm and the base plate are made of aluminium screw parts are of stainless steel and can be used in outdoor applications Specificatio...

Page 22: ...rev 1 DEC16 MAFP 21 GB...

Page 23: ...rev 0 NOV11 MAFP 22 GB...

Page 24: ......

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...ECOTECH GTS SRL Via del Plan del Sant 24 38012 Predaia Fraz Mollaro TN P IVA 02553340221 Tel 0463 461049 Fax 0463 461375 info ecotechgts com www ecotechgts com...

Reviews: