09.06.2017 Rev. 08
54
Emission Measurement
In emission measurements, the following values are accepted as reference according to TS EN 676 +A2
standard.
Ø
CO < 100 mg/ kWh
Ø
%3
≤
O
2
≤
%5
Ø
NO
x
< 170 mg/ kWh
Ø
Excess air ratio 1,2
≤
λ
≤
1,3
In emission measurements, the following values are accepted as reference according to TS EN 267
standard.
Ø
CO < 110 mg/ kWh
Ø
%3
≤
O
2
≤
%5
Ø
NO
x
< 250 mg/ kWh
Ø
Excess air ratio 1,2
≤
λ
≤
1,3
It is important for the boiler to be sealed in order to avoid incorrect measurements during
emission measurements.
Boiler temperature must be between 40 C
˚
and 80 C
˚
while making emission measurement in
hot water boilers.
Program Relay
LFL 1.32
Summary of Contents for ECO 50 K L C 2
Page 10: ...09 06 2017 Rev 08 9 Burner Components ECO 50 KLC2...
Page 12: ...09 06 2017 Rev 08 11 ECO 55 KLC2 2a...
Page 14: ...09 06 2017 Rev 08 13 ECO 60 KLC2...
Page 16: ...09 06 2017 Rev 08 15 ECO 65 KLC2...
Page 18: ...09 06 2017 Rev 08 17 ECO 70 KLC2...
Page 20: ...09 06 2017 Rev 08 19 ECO 50 KLC3...
Page 22: ...09 06 2017 Rev 08 21 ECO 55 KLC3 3a...
Page 24: ...09 06 2017 Rev 08 23 ECO 60 KLC3...
Page 26: ...09 06 2017 Rev 08 25 ECO 65 KLC3...
Page 28: ...09 06 2017 Rev 08 27 ECO 70 KLC3...
Page 30: ...09 06 2017 Rev 08 29 ECO 75 KLC3...
Page 33: ...09 06 2017 Rev 08 32 Back Pressure Capacity Diagrams...
Page 34: ...09 06 2017 Rev 08 33 Burner Dimensions...
Page 36: ...09 06 2017 Rev 08 35...
Page 37: ...09 06 2017 Rev 08 36...
Page 49: ...09 06 2017 Rev 08 48 MB ZRD LE 405 412 Series Gas Valve...
Page 58: ...09 06 2017 Rev 08 57 Light Oil Burner Fuel Ring Line...