Dehumidification
When in cooling mode, a dehumidification function can be set using system switch 3 as follows:
OFF - Normal cooling fan runs at rate set by COOL CFM switch
ON - Fan Cooling runs at lower COOL CFM rate for 15 min. and then goes to higher rate
Fan Mode
R is connected to G
If fan is set to “ON” on thermostat, fan runs as follows:
If OPTION switch 1 is OFF, fan runs at selected HEAT CFM rate
If OPTION switch 1 is ON, fan runs at 300 CFM (ES50LVS), 400CFM (ES90LVS)
If fan is set to “OFF” on thermostat, fan runs at HEAT or COOL CFM settings
Constant Low Fan Circulation
Fan may be run at a low rate using OPTION switch 1 as follows:
OFF – fan runs at rate set by HEAT CFM switch
ES50LVS runs at 300 CFM, ES90LVS runs at 400 CFM
Condenser Lockout
If the air out falls below 40°F, the condenser will turn off until the temperature warms. This is
to prevent DX coil ice-up. This accomplished by breaking the connection at the C terminal from
the 24VAC return.