12 |
P a g e
Rear Piping Connections
The heating coil may be reversed to allow rear piping:
•
Remove upper door
•
Disconnect supply air sensor from extension cable
•
Slide out heating coil
•
Re-mount supply air sensor and grommet to opposite end of heating coil
•
Remove rear knock-outs
•
Slide in heating coil
•
Use plastic plugs (provided) to close up holes on upper door
Ecosmart Mounting
The
ecosmart
can be installed in up flow, down flow and left or right horizontal applications.
Install the
ecosmart
with the door in place to make sure the cabinet remains square. Flip the
unit for down flow applications so that the top of the unit is now the bottom. No modification is
required for any configuration.
The
ecosmart
can be suspended from floor joists, rafters or concrete using rods, pipe, angle
supports or straps. Units must be hung level to ensure quiet operation.
CAUTION - Use any of the existing screw holes in the cabinet when using straps. If
the existing screw is too short for securing a mounting strap, a longer screw should
be used provided care is taken not to damage any internal components. Product
warranty does not cover any damage or claims resulting from damage from longer
screws or from the unit being improperly suspended.
The cabinet is designed so that the return air can be located on either side of the cabinet, or
from the bottom of the cabinet. Position a filter rack so that the filter is readily accessible. A
filter and filter rack are not included. Sides are marked for a standard 16 x 20 in filter rack.
WARNING - Special care should be taken in the vicinity of the coil to avoid
puncture. Screw into opening flange instead of top of cabinet when fastening the
supply air duct.
Plumbing
Install a sediment faucet or ball valve for use as a drain/purge valve. The drain valve must be
located downstream of the pump and check valve, and upstream of the isolation valve (if