ecosens EL-M0751 Manual Download Page 2

INSTALLATIION:

 (see the diagram)

 

  Shut off power. 

  Loosen the screw on the bottom lid, 

open  the  wiring  hole,  pass  the  wire 

of  power  and  load  through  the 

bottom lid. 

  Fix the bottom lid with inflated screw 

on the selected position. 

  Connect  the  power  and  load  wire 

into 

connection-wire 

column 

according to the connecting figure. 

 

Put the sensor on the bottom lid, twist the screw tightly then electrify it and test it. 

 

CONNECTION-WIER SKETCH DIAGRAM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST:

 

 

  Turn the SENS knob clockwise on the maximum. Turn the TIME knob anti-clockwise on the 

minimum, Turn the LUX knob clockwise on the maximum. 

 

 

 

When you switch on the power, the light will be on at once, and 5-30 seconds later will be 

off automatically. Then if the sensor receives induction signal, it can work normally. 

  After 5-10sec of the first detection, the light could work again. If there is no induction signal, 

the load should be stopped working within 5-15sec. 

Note: when testing in daylight, please turn LUX knob to          (SUN) position, otherwise the 

sensor lamp could not work! 

NOTES

 

 

The unrest objects can’t be regarded as the installation basis-face. 

  In 

front  of  the  detection  window  there  shouldn’t  be  hinder  or  unrest  objects  affecting 

detection. 

  Avoid installing it  near  air temperature  alteration  zones  for example:  air  condition,  central 

heating, etc. 

  In order to avoid the unexpected damage of product, please add a safe device of 6A when 

installing microwave sensor, for example, fuse, safe tube etc. 

SOME PROBLEM AND SOLVED WAY 

 

The load don’t work: 

a. Check the power and the load. 

b. Whether the indicator light is turned on after sensing? If yes, please check load. 

c. If the indicator light  is

 

not turn on after sensing, please check if the working light 

corresponds to the ambient light.   

d. Please check if the working voltage corresponds to the power source. 

  The sensitivity is poor: 

a. Please check the ambient temperature. 

b. Please check if the signals source is in the detection fields. 

c. Please check the installation height. 

 

The sensor can’t shut automatically the load: 

a. If there are continual signals in the detection fields. 

b. If the time delay is set to the longest. 

c. If the power corresponds to the instruction. 

d. If the air temperature changes near the sensor, air condition or central heating etc. 

 