CONNECTION:
Warning. Danger of death through electric shock!
Must be installed by professional electrician.
Disconnect power source.
Cover or shied any adjacent live components.
Ensure device cannot be switched on.
Check power supply is disconnected.
Unload the faceplate of sensor and adjust the time and LUX knob.(refer to figure 1)
Loose the screws in the connection terminal, and then connect the power to connection
terminal of sensor according to connection-wire diagram.
If you want to install it in circular hole, put the sensor into the hole and tighten the splay bolt
on both sides (refer to figure 2). If you want to install in quadrate hole, put the sensor into
the hole, fix the screw through the mounting hole (refer to figure 3).
Install back the faceplate, switch on the power and then test it.
Figure1 Figure2 Figure3
CONNECTION-WIRE DIAGRAM:
(See the right figure)
TEST:
Set the function switch to “ON”, set “TIME”
anti-clockwise to minimum,
“LUX” clockwise to
maximum.
Switch on the power, the lamp should be on.
Set the function switch to “OFF”, the lamp should be off immediately.
Set the function switch to “PIR”, at first the load and the indicator lamp don’t work. After
Warm-up 30sec, the indicator lamp turns on .Under the condition of no sense signal, the
load should stop working within 10sec
±
3sec and the indicator lamp would turn off.
Set “LUX” anti-clockwise to minimum, if the ambient light is more than 3LUX, the inductor
load should not work after the load stop working. If you cover the detection window with
the opaque objects (towel etc), the load would work .Under no induction signal condition,
the load should stop working within 10sec
±
3sec.
Note: when testing in daylight, please turn LUX knob to (SUN) position, otherwise
the sensor lamp could not work! If the lamp is more than 60W, the distance between lamp
and sensor should be 60cm at least.
SOME PROBLEM AND SOLVED WAY:
The load do not work:
a. Please check if the connection-wiring of power and load is correct.
b. Please check if the load is good.
c. Please check if the working light sets correspond to ambient light.
The sensitivity is poor:
a. Please check if there has any hindrance in front of the detection window to affect to
receive the signal.
b. Please check if the ambient temperature is too high.
c. Please check if the induction signal source is in the detection fields.
d. Please check if the installation height corresponds to the height showed in the
instruction.
e. Please check if the moving orientation is correct.
The sensor can not shut off the load automatically:
a. Please check if there is continual signal in the detection field.
b. Please check if the time delay is the longest.
c. Please check if the power corresponds to the instruction.