background image

 

Range DL 

– DS32 

Instruction manual

 

Série DL 

– DLP64 

Manuel d’utilisation

 

 

ECOSAFE | Date of the document : 30/04/2019 – Version : 01 

 

1.  DESCRIPTION / USE 

 

For people’s safety, the safety showers and eyewashers are essential in the premises where risks of chemicals projection exist. They 

are  recommended  in  the  chemical  and  pharmaceutical  industries,  automobile  and  food-processing  industries,  hospitals,  water-

treatment plants and swimming pools… 

 

The first-aid equipments such as showers and eye-washers have to be installed near the zones of danger. They must remain easy to 

access at all time and have clear normalized pictogram indications (supplied with our equipments). 

 

2.  TECHNICAL FEATURES 

 

 

Safety shower for internal use 

 

Compliance with the EN 15154-1 and NF X 15-221 standards 

 

Floor fixation 

 

Manual operation 

 

Pipe in stainless steel 

 

Shower head in stainless steel 

 

Water supply : F 1” 

 

Shower flow : 75L /min 

 

Weight : 14 KG 

 

 

3.  LOCATION 

 
Safety  showers  have  to  be  installed  right  next  to  the  hazard  zone.  They  have  to  be  reachable  within  10  seconds  or  30  meters 

maximum. We recommend having multiple sets of first-aid equipment in case of simultaneous risk of accidents.  

 

First-aid equipments have to be visible and clearly identifiable through normalized pictograms it is supplied with.  

The staff of the company has to be trained to the use of these equipments.  

The safety shower has to be connected to a water supply.  

 

The pressure has to be situated between 2 and 3 bars.  

The staff of the company has to be trained to the use of these first-aid equipments.  

 
 

4.  INSTALLATION 

 
 
Once your equipment has been delivered, please ensure that you received all the elements, thanks to the schema in annex.  

Then, assemble the equipment, thanks to the outline, too.  

We remind you that these equipments ha

ve to be mounted and installed by a qualified staff (plumber…).  

 

 
 

Summary of Contents for DS32

Page 1: ...Range DL DS32 Instruction manual ECOSAFE Date of the document 30 04 2019 Version 01 0 Instruction manual For safety shower Model DS32 ...

Page 2: ...document 30 04 2019 Version 01 1 CONTENT 1 Description Use Page 2 2 Technical features Page 2 3 Location Page 2 4 Installation Page 2 5 Safety controls Page 3 6 Spare parts Page 3 7 Warranty Page 3 8 Control sheet for the user Page 5 9 Annex Schema Page 6 ...

Page 3: ...wer head in stainless steel Water supply F 1 Shower flow 75L min Weight 14 KG 3 LOCATION Safety showers have to be installed right next to the hazard zone They have to be reachable within 10 seconds or 30 meters maximum We recommend having multiple sets of first aid equipment in case of simultaneous risk of accidents First aid equipments have to be visible and clearly identifiable through normaliz...

Page 4: ...ment holds a 12 months warranty against every manufacturing defect limited to ordinary conditions of use from the date indicated on the delivery note Our warranty can be applied only in case of manufacturing defects or hidden fault The warranty covers only the replacement of the faulty goods or pieces indicated by our quality or technical department as they are the only one able to determine the c...

Page 5: ...cument 30 04 2019 Version 01 4 In case of damage caused by the corrosion The activation of the warranty won t extend the term Our warranty stops if the customer has not notified us in a 7 days term after seeing the fault date that the customer has to prove ...

Page 6: ... manual ECOSAFE Date of the document 30 04 2019 Version 01 5 8 CONTROL SHEET FOR THE USER YES NO The valves work properly The water flow works properly The pictograms are visible and in good condition Remarks Date By Signature ...

Page 7: ...Range DL DS32 Instruction manual ECOSAFE Date of the document 30 04 2019 Version 01 6 Annex Schema ...

Reviews: