- 34 -
6. Malfunction protection and code
The controller judges various types of malfunction in running automatically, and the basis
of these types of malfunction , protection accordingly, and display correspond to malfunction code,
malfunction code display in clock.
E 1 : XX
Malfunction malfunction code
malfunction
Ma Function cause
Malfunction
code
Enter condition
Safeguard
Resume
condition
A/C outlet water
sensor is
damaged
E1
:
11
Sensor short circuit
or open circuit
System
Shutdown
Maintenance
and replacement
sensors
A/C inlet water
sensor is
damaged
E1
:
12
Sensor short circuit
or open circuit
System
Shutdown
Maintenance
and replacement
sensors
The air
temperature
sensor is
damaged
E1
:
13
Sensor short circuit
or open circuit
System
Shutdown
Maintenance
and replacement
sensors
Water tank
temperature
sensor is
damaged
EX
:
14
Sensor short circuit
or open circuit
Hot water
system
shutdown
Maintenance
and replacement
sensors
Phase Protection
E1
:
01
〖
B9
〗
to "1", lack of
reverse-phase
System
Shutdown
Maintenance
Switch off
air-conditioning
flow
E1
:
02
Main module water flow
switches off
〖
Cd
〗
seconds
System
Shutdown
Maintenance
Refrigeration ,Air
Conditioning
antifreeze switch
off
E1
:
03
Refrigeration
System
Shutdown
Maintenance
Ground-source
water switch off
E1
:
04
Main module water flow
switches off
〖
Cd
〗
seconds
System
Shutdown
Maintenance