![Econex AB1 SE Series Installation And Operating Instructions Manual Download Page 11](http://html1.mh-extra.com/html/econex/ab1-se-series/ab1-se-series_installation-and-operating-instructions-manual_2354952011.webp)
AB1…SE instructions 11 of 12
Form 140516
13.2
E
LECTRONIC
C
ONFIGURATION
AB1…SE4
I
NPUT SIGNAL
0-10V
DIP SWITCH POSITION
D
IP
S
WITCH
D
IP
S
WITCH
O
N
LEFT
O
FF
D
IP
S
WITCH
O
N
RIGHT
O
N
1
Clockwise Rotation
(from Power End side)
Counter-Clockwise Rotation
(from Power End side)
2
Low Resolution 125 steps
High Resolution 200 steps
3
4
Please refer to the below reported scheme**
5
N.A.
Input Signal 0-10 V
6
N.A.
DS-6 MUST be turned ON
** For special setting please look here below:
3
•
4
OFF
•
ON
DS-3 turned ON and DS-4 turned OFF. Actuator rotates for 90°
with Mid-Low Input Signal. For example 0-5V with rotation of 90°.
3
•
4
OFF
•
ON
DS-3 turned OFF and DS-4 turned ON. Actuator rotates for 90°
with Mid-High Input Signal. For example 5-10V with rotation of 90°.