Installation & Operation Manual Proven Quality since 1892
ECON actuator Fig. 7907, type ELA80 – 3000
Rev.13 - January 7, 2019
34
8
TROUBLE SHOOTING
The following instructions are listed in the order of the most common difficulties encountered
during the installation and start-up.
►
The actuator does not respond
Visually inspect the actuator and check if no damage has occurred during shipping and handling of
the actuator.
Verify the line voltage supplied to the actuator; it must match with the rating on the actuator’s
nameplate
Compare and check the internal wiring with the supplied wiring diagram of the actuator
Check the limit switch cams
►
The actuator is supplied with power but does not operate
Verify the line voltage supplied to the actuator; it must match with the rating on the actuator’s
nameplate.
Make sure that the actuator output torque is greater than the required valve torque
Check the limit switch cams
Check if the torque switches have not been tripped
Check the mechanical travel stop adjustment
Check if the rotating direction matches (According to the applicable standards, valves and actuators
must open in counter-clockwise direction)
Check the internal wiring
Check for any corrosion and condensation. Electrical or mechanical devices may have been
affected
Verify if coupler/bracket is correctly installed and may not block the actuator rotation
►
Actuator runs erratically
Check the ambient temperature
Verify that the duty cycle has not been exceeded
Check the position of the manual override lever
►
Optional Equipment(s)
1) Potentiometer
Check the resistance value
Check the potentiometer gear for jamming
Check the ZERO and SPAN calibration and confirm input/output signal
Check the board for any damage
2
) Current Position Transmitter
Verify the input signal
Check the configuration of the dip switches
Check the board for any damage